Refrigerant Selection for Heat Pumps: The Compressor Makes the Difference

被引:2
|
作者
Neumaier, Lisa [1 ]
Roskosch, Dennis [1 ]
Schilling, Johannes [1 ]
Bauer, Gernot [2 ]
Gross, Joachim [2 ]
Bardow, Andre [1 ]
机构
[1] Swiss Fed Inst Technol, Dept Mech & Proc Engn, Energy & Proc Syst Engn, Tannenstr 3, CH-8092 Zurich, Switzerland
[2] Univ Stuttgart, Inst Tech Thermodynam & Thermal Proc Engn, Pfaffenwaldring 9, D-70569 Stuttgart, Germany
关键词
compressor model; computer-aided molecular designs; heat pumps; PC-SAFT equation of state; piston compressor; refrigerant screening; RECIPROCATING-COMPRESSORS; THERMODYNAMIC EVALUATION; FLUID SELECTION; PERFORMANCE; EQUATION; DESIGN; STATE;
D O I
10.1002/ente.202201403
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Increasingly stringent regulations and new applications require selecting improved refrigerants for heat pumps. The selected refrigerants should be environmentally friendly and maximize the performance of the heat pump process. Systematic refrigerant selection methods usually model the compressor with one fixed isentropic efficiency identical for all refrigerants. However, compressor studies indicate that the isentropic efficiency may be highly refrigerant-dependent. Herein, the need for a refrigerant-dependent compressor model for refrigerant selection is investigated. For this purpose, a refrigerant-dependent compressor model is combined with an integrated design of refrigerant and heat pump process. To guarantee a comparable nominal heating power among refrigerants, the compressor design is tailored to the refrigerant by expanding the refrigerant-dependent compressor model toward compressor sizing. Integrating compressor design into systematic refrigerant selection is enabled by a computationally efficient model implementation. Accounting for refrigerant-dependent compression substantially changes the resulting refrigerant ranking compared to the widely used assumption of identical isentropic efficiencies for all refrigerants: The best-performing refrigerant is not even identified among the best ten refrigerants when assuming identical isentropic efficiencies. Consequently, compression is identified as the main driver for differences in refrigerant performance. Therefore, integrating refrigerant-dependent compressor models is crucial for systematic refrigerant selection.
引用
收藏
页数:10
相关论文
共 50 条
  • [21] Artificial neural network analysis of heat pumps using refrigerant mixtures
    Arcaklioglu, E
    Erisen, A
    Yilmaz, R
    ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (11-12) : 1917 - 1929
  • [22] Novel Turbo Compressor for Heat Pump Using Water as Refrigerant and Lubricant
    Shoyama, T.
    Kawano, B.
    Ogata, T.
    Matsui, M.
    Furukawa, M.
    Dousti, S.
    INTERNATIONAL CONFERENCE ON COMPRESSORS AND THEIR SYSTEMS 2019, 2019, 604
  • [23] Compressor Heat Pump Model Based on Refrigerant Enthalpy and Flow Rate
    Obstawski, Pawel
    Bakon, Tomasz
    Gajkowski, Jacek
    ADVANCES IN SCIENCE AND TECHNOLOGY-RESEARCH JOURNAL, 2023, 17 (05) : 12 - 27
  • [24] Machine vision lens selection makes the difference
    Bilton, Timne
    CONTROL ENGINEERING, 2007, 54 (12) : M1 - +
  • [25] Protege selection by mentors: what makes the difference?
    Allen, TD
    Poteet, ML
    Russell, JEA
    JOURNAL OF ORGANIZATIONAL BEHAVIOR, 2000, 21 (03) : 271 - 282
  • [26] To The Question of the Use of Working Substances in Vapor Compressor Heat Pumps
    Rachkovsky, N. O.
    Tatarenko, Yu. V.
    OIL AND GAS ENGINEERING (OGE-2019), 2019, 2141
  • [27] PARAMETERS OF PISTON COMPRESSOR OF HEAT PUMPS IN PARTIAL OPERATION MODES
    Barskii, I. A.
    Antipov, Yu. A.
    Shatalov, I. K.
    Terekhov, D. V.
    CHEMICAL AND PETROLEUM ENGINEERING, 2011, 47 (1-2) : 53 - 58
  • [28] Compressor-driven metal-hydride heat pumps
    Kim, KJ
    Feldman, KT
    Lloyd, G
    Razani, A
    APPLIED THERMAL ENGINEERING, 1997, 17 (06) : 551 - 560
  • [29] An economic and technical case for a compressor/expander unit for heat pumps
    Henderson, PC
    Hewitt, NJ
    Mongey, B
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2000, 24 (09) : 831 - 842
  • [30] Centrifugal compressor design for high-temperature heat pumps
    Jaatinen-Varri, Ahti
    Honkatukia, Juha
    Uusitalo, Antti
    Turunen-Saaresti, Teemu
    APPLIED THERMAL ENGINEERING, 2024, 239