A Combined Controller for Closed-Loop Control Systems Affected by Electromagnetic Interference
被引:1
|
作者:
Baskys, Algirdas
论文数: 0引用数: 0
h-index: 0
机构:
Vilnius Gediminas Tech Univ, Fac Elect, Plytines Str 25, LT-10105 Vilnius, Lithuania
Ctr Phys Sci & Technol, Dept Funct Mat & Elect, Sauletekio Ave 3, LT-10257 Vilnius, LithuaniaVilnius Gediminas Tech Univ, Fac Elect, Plytines Str 25, LT-10105 Vilnius, Lithuania
Baskys, Algirdas
[1
,2
]
机构:
[1] Vilnius Gediminas Tech Univ, Fac Elect, Plytines Str 25, LT-10105 Vilnius, Lithuania
[2] Ctr Phys Sci & Technol, Dept Funct Mat & Elect, Sauletekio Ave 3, LT-10257 Vilnius, Lithuania
closed-loop control system;
electromagnetic interference;
noise signal;
combined controller;
noise signal resistance;
robustness;
PID CONTROLLERS;
DESIGN;
D O I:
10.3390/s24051466
中图分类号:
O65 [分析化学];
学科分类号:
070302 ;
081704 ;
摘要:
In this paper, a new approach for the solution of the electromagnetic interference impact problem in closed-loop control systems with proportional-integral-derivative (PID) controllers is proposed. The approach is based on the application of a combined controller that consists of three controllers: PID, PI and I, when only one of them is operating at a time, and which one is operating determines the control error value. The proposed combined controller allows for achieving better resistance of the control system to the noise signals produced by electromagnetic interference compared to PID and PID with low-pass filters in derivative term controllers without deteriorating the dynamic performance of the control system. The operation of the controller has been analysed using simulation and experiments with plants, the dynamics of which are described by first-order plus dead-time transfer functions.