Energy performance and thermal comfort of integrated energy recovery ventilator system with air-conditioner for passive buildings

被引:5
|
作者
Cho, Wonhee [1 ]
Heo, Juneyeong [1 ]
Park, Myeong Hyeon [1 ]
Seo, Hyeong Joon [2 ]
Lee, Kisup [2 ]
Lee, Dong Gyu [2 ]
Kim, Yongchan [1 ]
机构
[1] Korea Univ, Dept Mech Engn, Anam Ro 145, Seoul 02841, South Korea
[2] Samsung Elect Co Ltd, Samsung Ro 129, Suwon 16677, Gyeonggi Do, South Korea
基金
新加坡国家研究基金会;
关键词
Energy recovery ventilator; Air conditioner; Thermal comfort; Energy efficiency; Dehumidification; SOUTH; HEAT;
D O I
10.1016/j.enbuild.2023.113302
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study aims to provide a ventilation solution for energy-efficient buildings that suffer from high indoor moisture content during cooling seasons. With the decreased sensible load in highly insulated buildings, con-ventional energy recovery ventilators (ERVs) and air conditioners are inadequate to effectively handle the increased dehumidification load. Moisture removal through air conditioners requires cooling the air below its dew point, which makes precise control of indoor humidity difficult and reduces the level of indoor thermal comfort. Thus, an ERV system integrated with a cooling coil (ERV-CC) is proposed to enhance its latent heat effectiveness. Field measurements were conducted for the ERV and ERV-CC systems to compare their energy performances and levels of indoor thermal comfort. The results indicated that the ERV system did not satisfy the recommended range of indoor humidity even when the set-point temperature of the air conditioner decreased. However, the ERV-CC system could condition the indoor air within the comfort zone at higher energy effi-ciencies. In addition, the ERV-CC system was observed to benefit from the dehumidification effect through the enthalpy recovery process under a wider range of outdoor conditions. Especially, at low outdoor temperatures, the ERV-CC system dehumidified the incoming fresh air, whereas the ERV system humidified the fresh air. Overall, the optimum operating conditions for the ERV-CC system were determined to be a set-point temperature and relative humidity of 27 degrees C and 50%, respectively, while satisfying the thermal comfort criterion at an 8.24% predicted percentage dissatisfied index with minimum energy consumption. Furthermore, the ERV-CC system not only reduced the building load, but also improved the individual air conditioner performance.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Analysis and Optimization of Varying Door and Windows Opening on Energy Consumption and Thermal Comfort in Air-Conditioner Office
    Shen, Chunming
    Wang, Zhicheng
    Yao, Kailu
    Yuan, Wenying
    Sun, Fangtian
    [J]. Journal of Engineering Science and Technology Review, 2024, 17 (03) : 217 - 227
  • [2] Feasibility of a compact heat recovery ventilator module with an integrated air-cooled solar absorption air-conditioner
    Kim, D. S.
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2011, 50 (08) : 1604 - 1614
  • [3] Numerical experiment of thermal comfort in a bedroom equipped with air-conditioner
    Sin, VK
    Sun, HI
    Tam, LM
    Wong, KI
    [J]. COMPUTATIONAL METHODS IN ENGINEERING AND SCIENCE, PROCEEDINGS, 2003, : 787 - +
  • [4] A novel solar-assisted air-conditioner system for energy savings with performance enhancement
    Ha, Q. P.
    Vakiloroaya, V.
    [J]. INTERNATIONAL ENERGY CONGRESS 2012, 2012, 49 : 116 - 123
  • [5] Investigation of performance and energy cost of automobile air-conditioner using alternative refrigerants based on thermal comfort using various cooling seats
    Ham, Jeonggyun
    Shin, Yunchan
    Lee, Minjung
    Cho, Honghyun
    [J]. RESULTS IN ENGINEERING, 2023, 20
  • [6] Experimental investigations on the thermal performance of a domestic condensing heat recovery air-conditioner
    Qiu, Fuqiang
    Li, Baoguo
    Xu, Taoping
    [J]. ADVANCES IN MECHANICAL ENGINEERING, 2019, 11 (02)
  • [7] Performance evaluation and design considerations for a split air-conditioner with built-in thermal energy storage
    Ahmad, Jehanzeb
    Ul Islam, M. Najam
    Sabir, Jawwad
    [J]. BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2019, 40 (05): : 560 - 575
  • [8] Study on Thermal Comfort and Indoor Air Quality in the Classroom with System Air-conditioner and Ventilation System for Cooling Loads
    Noh, Kwang-Chul
    Jang, Jae-Soo
    Oh, Myung-Do
    [J]. TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2006, 30 (01) : 57 - 66
  • [9] A Novel Window Type Air-conditioner with Energy Recovering
    Luo, Qinghai
    Zhang, Pengfei
    Yang, Xiufei
    Zou, Jun
    [J]. ADVANCED BUILDING MATERIALS, PTS 1-4, 2011, 250-253 (1-4): : 3021 - 3024
  • [10] Evaluation of the energy performance and thermal comfort of an air conditioner with temperature and humidity controls in a cooling season
    Moon, Hyeun Jun
    Yang, Soo Hyeun
    [J]. HVAC&R RESEARCH, 2014, 20 (01): : 61 - 71