Numerical and experimental assessment of a micro-combined cooling, heating, and power (CCHP) system based on biomass gasification

被引:21
|
作者
Perrone, D. [1 ]
Castiglione, T. [1 ]
Morrone, P. [1 ]
Pantano, F. [2 ]
Bova, S. [1 ]
机构
[1] Univ Calabria, Dept Mech Energy & Management Engn, Ponte Bucci,Cubo 46 C, I-87036 Arcavacata Di Rende, Italy
[2] SILPA srl, Via E Fermi 14, I-88900 Crotone, Italy
关键词
CCHP systems; biomass gasification; syngas fueled engines; waste heat recovery; INTERNAL-COMBUSTION ENGINE; TRIGENERATION SYSTEM; PRODUCER GAS; SIMULATION; OPTIMIZATION; PERFORMANCE; ENERGY; GENERATION; EMISSIONS; MODEL;
D O I
10.1016/j.applthermaleng.2022.119600
中图分类号
O414.1 [热力学];
学科分类号
摘要
The goal of this paper is to analyse an innovative micro-combined cooling, heating, and power (CCHP) system, whose power generation unit is composed of an internal combustion engine fuelled with syngas coming from a woody biomass gasification process. The internal combustion engine is directly coupled to the gasifier. The analysis of the existing plant, realized in South Italy, was carried out experimentally. Moreover, a numerical model was developed. The model, in particular, considers the impact of gasifier operating conditions, i.e., biomass feed rate and equivalence ratio (ER) on engine performance: electric, thermal, and overall efficiency of the micro-CCHP system, running on woody biomass at full and partial loads conditions. Modelling the coupled system at partial load with real thermophysical properties of the syngas produced by the gasification process is surely a novel contribution but even more relevant is the presentation of experimental data on an existing plant. Once the model was validated, the system performance was evaluated by comparing two different biomass compositions: W1, characterized by a lower heating value of 14.5 MJ/kg and W2, having a lower heating value of 16.8 MJ/kg. Results show that the biomass composition affects more significantly the gasifier efficiency (72.4-82.6 %) and the engine thermal efficiency (55.3-50.6 %), while the engine electric efficiency is weakly affected (26-27 %). An overall efficiency of the entire micro-CCHP system amounting to 55.2 % and 61.1 % for W1 and W2, respectively, was estimated. Lastly, the economic feasibility of the micro-CCHP system was investigated and includes a sensitivity analysis of the current costs of energy vectors. The results demonstrate the affordability of the biomass based CCHP system, which is further increased in this period of contingent inter-national political crisis and a payback period of about 2 years is currently predictable.
引用
收藏
页数:21
相关论文
共 50 条
  • [31] Increasing the energy efficiency of a building by thermal insulation to reduce the thermal load of the micro-combined cooling, heating and power system
    Paraschiv, Spiru
    Paraschiv, Lizica Simona
    Serban, Alexandru
    ENERGY REPORTS, 2021, 7 : 286 - 298
  • [32] Performance analysis and economic assessment of a combined cooling heating and power (CCHP) system in wastewater treatment plants (WWTPs)
    Farahbakhsh, Milad Tamjidi
    Chahartaghi, Mahmood
    ENERGY CONVERSION AND MANAGEMENT, 2020, 224
  • [33] Study of the off-design performance of a micro gas turbine-based combined cooling, heating and power (CCHP) cogeneration system
    He, Bin-Bin
    Yang, Yong-Ping
    Duan, Li-Qiang
    Reneng Dongli Gongcheng/Journal of Engineering for Thermal Energy and Power, 2008, 23 (06): : 615 - 619
  • [34] Laboratory research on combined cooling, heating and power (CCHP) systems
    Fu, L.
    Zhao, X. L.
    Zhang, S. G.
    Jiang, Y.
    Li, H.
    Yang, W. W.
    ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (04) : 977 - 982
  • [35] Multi-objective optimization of combined cooling, heating, and power (CCHP) system based on CNG engine
    Sheykhi, Mohammad
    Mehregan, Mahmood
    Emamian, Amin
    Ghorbani, Saeed
    Aliakbari, Karim
    Delouei, Amin Amiri
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 61
  • [36] Instruction of Solar CCHP (Combined Cooling, Heating and Power) Appliance
    Qiu, Luonan
    PROCEEDINGS OF THE 2016 6TH INTERNATIONAL CONFERENCE ON MACHINERY, MATERIALS, ENVIRONMENT, BIOTECHNOLOGY AND COMPUTER (MMEBC), 2016, 88 : 872 - 875
  • [37] Theoretical research of a silica gel-water adsorption chiller in a micro combined cooling, heating and power (CCHP) system
    Li, S.
    Wu, J. Y.
    APPLIED ENERGY, 2009, 86 (06) : 958 - 967
  • [38] Reliability and cost analysis of the redundant design of a combined cooling, heating and power (CCHP) system
    Jiang, Jinming
    Gao, Weijun
    Wei, Xindong
    Li, Yanxue
    Kuroki, Soichiro
    ENERGY CONVERSION AND MANAGEMENT, 2019, 199
  • [39] Fluid selection optimization of a combined cooling, heating and power (CCHP) system for residential applications
    Javan, Saeed
    Mohamadi, Vahid
    Ahmadi, Pouria
    Hanafizadeh, Pedram
    APPLIED THERMAL ENGINEERING, 2016, 96 : 26 - 38
  • [40] Micro-combined cooling, heating and power systems hybrid electric-thermal load following operation
    Mago, P. J.
    Chamra, L. M.
    Ramsay, J.
    APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) : 800 - 806