Experimental study of air distribution and heating performances of deflection ventilation

被引:9
|
作者
Cheng, Fanghui [1 ,2 ]
Li, Yunhao [1 ,2 ]
Wu, Yuxin [3 ]
Cheng, Yong [1 ,2 ]
Lin, Zhang [4 ]
机构
[1] Chongqing Univ, Joint Int Res Lab Green Bldg & Built Environm, Minist Educ, Chongqing, Peoples R China
[2] Chongqing Univ, Natl Ctr Int Res Low carbon & Green Bldg, Minist Sci & Technol, Chongqing, Peoples R China
[3] Zhejiang Sci Tech Univ, Sch Civil Engn & Architecture, Hangzhou, Zhejiang, Peoples R China
[4] City Univ Hong Kong, Div Bldg Sci & Technol, Hong Kong, Peoples R China
基金
中国国家自然科学基金;
关键词
Deflection ventilation; Winter heating; Air distribution; Thermal comfort; Energy utilization coefficient; IMPINGING JET VENTILATION; STRATUM VENTILATION; MIXING VENTILATION; THERMAL COMFORT; ENERGY-CONSUMPTION; OPTIMIZATION; SYSTEM; DIFFUSION; QUALITY; IMPACT;
D O I
10.1016/j.enbuild.2023.112800
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Deflection ventilation uses a purposely-designed deflector to divert supply air jet into the occupied zone directly. A few numerical studies have shown good indoor air quality with deflection ventilation. However, there was a lack of research on thermal comfort, which is also important to ensure human wellbeing. This study conducted experimental measurements when deflection ventilation was operated for winter heating. Eleven cases with different supply air velocities, supply air temperatures and deflection angles were carried out in an office-layout experimental chamber. As a comparison, another case with mixing ventilation was also measured. The predicted mean vote (PMV), draft rate (DR), air diffusion performance index (ADPI) and energy utilization coefficient (EUC) were adopted to evaluate the heating performances. The results showed that the deflection angle played a decisive role on air distribution. An inclined deflector (deflection angle: 35 degrees downward) could elevate air temperature in the lower occupied zone as compared with a horizontal deflector (deflection angle: 0 degrees), which provided efficient air distribution for winter heating. The average PMV values were in the range of -0.7 - 0.5, and the values of DR and ADPI in the occupied zone were typically less than 20% and higher than 80%, respectively. According to ISO 7730 and ASHRAE 113, deflection ventilation achieved satisfactory indoor environment with regard to thermal comfort. The EUC was typically greater than unity, indicating high energy efficiency of deflection ventilation, especially for the cases with deflection angle of 35 degrees. In comparison with mixing ventilation, deflection ventilation can provide better thermal comfort as well as energy efficiency.(c) 2023 Elsevier B.V. All rights reserved.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Experimental Study of Air Distribution and Ventilation Effectiveness in a Room with a Combination of Different Mechanical Ventilation and Heating/Cooling Systems
    Olesen, Bjarne W.
    Simone, Angela
    Krajcik, Michal
    Causone, Francesco
    De Carli, Michele
    [J]. INTERNATIONAL JOURNAL OF VENTILATION, 2011, 9 (04) : 371 - 383
  • [2] Cooling effect of air movement on heating performances of advanced air distribution
    Zhang, Sheng
    Niu, Dun
    Li, Teng
    Lin, Zhang
    Cheng, Fanghui
    Cheng, Yong
    [J]. BUILDING AND ENVIRONMENT, 2022, 226
  • [3] Cooling effect of air movement of advanced air distribution under heating mode: Experimental analyses of stratum ventilation
    Zhang, Sheng
    Cheng, Fanghui
    Zhang, Xia
    Lin, Zhang
    Cheng, Yong
    [J]. BUILDING AND ENVIRONMENT, 2023, 231
  • [4] Experimental investigation on air heating and natural ventilation of a solar air collector
    Zhai, XQ
    Dai, YJ
    Wang, RZ
    [J]. ENERGY AND BUILDINGS, 2005, 37 (04) : 373 - 381
  • [5] Experimental Study of Indoor Air Distribution and Thermal Environment in a Ceiling Cooling Room with Mixing Ventilation, Underfloor Air Distribution and Stratum Ventilation
    Wu, Xiaozhou
    Gao, Hao
    Zhao, Mingming
    Gao, Jie
    Tian, Zhen
    Li, Xiangli
    [J]. BUILDINGS, 2023, 13 (09)
  • [6] An Experimental Study on External Ventilation to the Heating Performance of Household Air Source Heat Pump
    Zou, Hang
    Liu, Zhanqiang
    Long, Enshen
    [J]. FRONTIERS IN ENERGY RESEARCH, 2021, 9
  • [8] Experimental study on air change effectiveness: Improving air distribution with all-air heating systems
    Amai, Hideyuki
    Liu, Shichao
    Novoselac, Atila
    [J]. BUILDING AND ENVIRONMENT, 2017, 125 : 515 - 527
  • [9] Air Distribution and Ventilation Effectiveness in a Room with Floor/Ceiling Heating and Mixing/Displacement Ventilation
    Wu, Xiaozhou
    Fang, Lei
    Olesen, Bjarne W.
    Zhao, Jianing
    [J]. PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 1: INDOOR AND OUTDOOR ENVIRONMENT, 2014, 261 : 59 - 67
  • [10] Experimental study of ventilation effectiveness and air velocity distribution in an aircraft cabin mockup
    Wang, Aijun
    Zhang, Yuanhui
    Sun, Yigang
    Wang, Xinlei
    [J]. BUILDING AND ENVIRONMENT, 2008, 43 (03) : 337 - 343