Air Distribution and Ventilation Effectiveness in a Room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

被引:7
|
作者
Wu, Xiaozhou [1 ]
Fang, Lei [2 ]
Olesen, Bjarne W. [2 ]
Zhao, Jianing [1 ]
机构
[1] Harbin Inst Technol, Sch Municipal & Environm Engn, Harbin 150006, Peoples R China
[2] Tech Univ Denmark, Int Ctr Indoor Environm & Energy, Dept Civil Engn, Copenhagen, Denmark
关键词
Floor heating (FH); Ceiling heating (CH); Mixing ventilation (MV); Displacement ventilation (DV); Air distribution; Ventilation effectiveness; DISPLACEMENT VENTILATION;
D O I
10.1007/978-3-642-39584-0_7
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The present study investigated different combinations of floor/ceiling heating with mixing/displacement ventilation and their impacts on the indoor air distribution and ventilation effectiveness. Measurements were performed in a room during heating season in December. The results show that indoor vertical air temperature differences and air velocities for different hybrid systems are less than 3 degrees C and 0.2 m/s when supply air temperature is 19 degrees C, air change rate is 4.2 h(-1), and heated surface temperature of floor/ceiling heating system is 25 degrees C. Ventilation effectiveness of mixing ventilation system combined with floor/ceiling heating systems is approximately equal to 1.0, and ventilation effectiveness of displacement ventilation system combined with floor/ceiling heating systems ranges from 1.0 to 1.2. The floor/ceiling heating systems combined with mixing ventilation system have more uniform indoor air distribution but smaller ventilation effectiveness compared with the floor/ceiling heating systems combined with displacement ventilation system. With regard to the building heat loss increased by non-uniform indoor air distribution and small ventilation effectiveness, there should be an optimal combination of floor/ceiling heating with mixing/displacement ventilation to have the minimal building heat loss.
引用
收藏
页码:59 / 67
页数:9
相关论文
共 50 条
  • [1] Indoor thermal environment and air distribution in a floor-ceiling heating room with mixing or displacement ventilation
    Wu, Xiaozhou
    Gao, Jie
    Wang, Haichao
    Fang, Lei
    Olesen, Bjarne W.
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2019, 25 (03) : 346 - 355
  • [2] Air distribution in a multi-occupant room with mixing or displacement ventilation with or without floor or ceiling heating
    Wu, Xiaozhou
    Fang, Lei
    Olesen, Bjarne W.
    Zhao, Jianing
    Wang, Fenghao
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (08) : 1109 - 1116
  • [3] Impact of chilled ceiling on indoor air distribution in a room with mixing ventilation
    Wu, Xiaozhou
    Gao, Jie
    Lv, Pin
    Wang, Haichao
    Wang, Shugang
    Wang, Fenghao
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (03) : 366 - 376
  • [4] Experimental Study of Indoor Air Distribution and Thermal Environment in a Ceiling Cooling Room with Mixing Ventilation, Underfloor Air Distribution and Stratum Ventilation
    Wu, Xiaozhou
    Gao, Hao
    Zhao, Mingming
    Gao, Jie
    Tian, Zhen
    Li, Xiangli
    [J]. BUILDINGS, 2023, 13 (09)
  • [5] An experimental study of air flow and temperature distribution in a room with displacement ventilation and a chilled ceiling
    Rees, Simon J.
    Haves, Philip
    [J]. BUILDING AND ENVIRONMENT, 2013, 59 : 358 - 368
  • [6] A nodal model to predict vertical temperature distribution in a room with floor heating and displacement ventilation
    Wu, Xiaozhou
    Olesen, Bjarne W.
    Fang, Lei
    Zhao, Jianing
    [J]. BUILDING AND ENVIRONMENT, 2013, 59 : 626 - 634
  • [7] Room air and contaminant distribution in mixing ventilation
    Heiselberg, P
    [J]. ASHRAE TRANSACTIONS 1996, VOL 102, PT 2, 1996, 102 : 332 - 339
  • [8] Comparison of Displacement Ventilation, Mixing Ventilation and Underfloor Air Distribution System
    Ren, Shouhong
    Tian, Shuo
    Meng, Xiangyi
    [J]. PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON ARCHITECTURAL, CIVIL AND HYDRAULICS ENGINEERING (ICACHE 2015), 2016, 44 : 79 - 82
  • [9] Thermal comfort and ventilation effectiveness in an office room with radiant floor cooling and displacement ventilation
    Krajcik, Michal
    Tomasi, Roberta
    Simone, Angela
    Olesen, Bjarne W.
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2016, 22 (03) : 317 - 327
  • [10] Room air stratification in combined chilled ceiling and displacement ventilation systems
    Schiavon, Stefano
    Bauman, Fred
    Tully, Brad
    Rimmer, Julian