Simulation analysis on energy consumption and economy of CPU cooling system based on loop heat pipe for data center

被引:4
|
作者
Du, Sheng [1 ,3 ]
Zhang, Quan [1 ]
Zou, Sikai [2 ]
Meng, Fanxi [1 ]
Liu, Lijun [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Hunan, Peoples R China
[2] East China Jiaotong Univ, Sch Civil Engn & Architecture, Nanchang 330013, Peoples R China
[3] CRRC Zhuzhou Inst Co Ltd, Zhuzhou 412001, Peoples R China
基金
中国国家自然科学基金;
关键词
Data center; CPU cooling; Loop heat pipe; System energy model; Economic analysis; THERMAL MANAGEMENT; PRESSURE-DROP; CONDENSATION; TEMPERATURE; PERFORMANCE; EVAPORATOR; CAPACITY; POWER; FLOW;
D O I
10.1016/j.tsep.2023.102115
中图分类号
O414.1 [热力学];
学科分类号
摘要
The existing computer room air conditioner (CRAC) system hardly satisfies the rapidly increasing cooling demand of the server's CPU with high heat flux, and it has ultra-high refrigerating energy consumption. As a solution, a water-cooled loop heat pipe (LHP) system can be adapted to cool the CPU in the data center and decrease refrigerating energy consumption. In this study, a Hybrid cooling system combining a water-cooled LHP system and a water-cooled CRAC system is proposed, and the system energy model is developed to analyze its annual energy consumption and economy. Based on a case data center using a lake water source, the effects of system setting points on energy consumption are investigated. The results show the Hybrid system has a considerable energy saving rate of 34.9%-52.4% than the conventional CRAC system. Meanwhile, the annual energy consumption of the Hybrid system declines substantially with increasing CPU power ratio, while it drops slightly with increasing CPU safety temperature. Additionally, the economic analysis illustrates that although the initial investment of Hybrid cooling system is 44.13%-77.74% higher than CRAC system, the dynamic payback periods are 2.48-6.64 years for system retrofit under different operating stages, and the life cycle cost savings are 22.06%-36.45%.
引用
收藏
页数:15
相关论文
共 50 条
  • [41] ENERGY PERFORMANCE ANALYSIS OF A COMBINED COOLING HEATING AND POWER SYSTEM FOR A DATA CENTER
    Xu, Donghao
    Qu, Ming
    PROCEEDINGS OF THE ASME 6TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY - 2012, PTS A AND B, 2012, : 203 - 208
  • [42] Simplified server model to simulate data center cooling energy consumption
    Ham, Sang-Woo
    Kim, Min-Hwi
    Choi, Byung-Nam
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2015, 86 : 328 - 339
  • [43] A review on data centre cooling system using heat pipe technology
    Wang, Xianling
    Wen, Qiaowei
    Yang, Jingxuan
    Xiang, Jinwei
    Wang, Zhangyuan
    Weng, Chuangbin
    Chen, Fucheng
    Zheng, Siming
    SUSTAINABLE COMPUTING-INFORMATICS & SYSTEMS, 2022, 35
  • [44] Consumption Analysis of Telco and Data Center Cooling and Humidification Options
    Hellmer, Bruce A.
    ASHRAE TRANSACTIONS 2010, VOL 116, PT 1, 2010, 116 : 118 - 133
  • [45] Experimental Analysis and FEM Simulation of Novel Finned Loop Heat Pipe
    Gunnasegaran, Prem
    Bin Abdullah, Mohd Zulkifly
    Shuaib, Norshah Hafeez
    MICRO/NANO SCIENCE AND ENGINEERING, 2014, 925 : 481 - +
  • [46] Enhanced miniature loop heat pipe cooling system for high power density electronics
    Choi, J.H.
    Sung, B.H.
    Yoo, J.H.
    Kim, C.J.
    Borca-Tasciuc, D.-A.
    Journal of Thermal Science and Engineering Applications, 2012, 4 (02)
  • [47] CONTRIBUTION OF HEAT PIPE TO THE ENERGY CONSERVATION OF DATA CENTER AND CLOUD COMPUTERS
    Mochizuki, Masataka
    Thang Nguyen
    Mashiko, Koichi
    Saito, Yuji
    Wu, Xiao Ping
    Tien Nguyen
    Wuttijumnong, Vijit
    Singh, Randeep
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 653 - 661
  • [49] Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
    Zhou Feng
    Tian Xin
    Ma GuoYuan
    CHINESE SCIENCE BULLETIN, 2011, 56 (20): : 2185 - 2190
  • [50] Investigation into the energy consumption of a data center with a thermosyphon heat exchanger
    ZHOU FengTIAN Xin MA GuoYuan College of Environmental and Energy EngineeringBeijing University of TechnologyBeijing China
    Chinese Science Bulletin, 2011, 56 (20) : 2185 - 2190