Numerical simulation and analysis of contact erosion by high-current and low-voltage air arc considering the movement of arc

被引:3
|
作者
Wang, Yujie [1 ]
Xu, Nuo [1 ]
Wang, Lijun [2 ]
机构
[1] Chongqing Jiaotong Univ, Chongqing 400000, Peoples R China
[2] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
MODEL; EVAPORATION;
D O I
10.1063/5.0144666
中图分类号
TB3 [工程材料学];
学科分类号
0805 ; 080502 ;
摘要
When a low-voltage circuit breaker (LVCB) breaks a high current, the contact erosion caused by the arc greatly reduces the LVCB's breaking performance and service lifetime. Therefore, this paper uses AgW alloy contacts as a research object, which are commonly used for breaking high currents, and establishes a contact erosion model for an LVCB with a breaking current of 14 kA. The model considers the energy balance of a contact surface and uses a solidification and melting model and a dynamic mesh model to deal with the phase transition problem of the contact material and introduces the arc movement into this model. Using this model, the contact melting and evaporation width, erosion depth, erosion rate, and erosion mass are calculated when Ag and AgW30 and AgW70 alloys are used as contact materials. The influence of W-content on the erosion characteristics of a contact is analyzed. The results show that, although the introduction of element W significantly reduces the erosion mass, it advances the time when the melting point and boiling point are reached. The position, width, and depth of the melting pool and melting layer thickness change with the movement of the arc. In the process of contact erosion considering the movement of the arc, the introduction of W element will increase the width of the molten pool and the solidification time of the molten material. Especially when the mass percentage of element W in the contact material reached 70%, the solidification time of the molten material greatly increased, which weakened the welding resistance of the contact.
引用
收藏
页数:12
相关论文
共 50 条
  • [41] Low-voltage switching vacuum arc in a transverse magnetic field proportional to the arc current
    Klajn, Antoni
    PRZEGLAD ELEKTROTECHNICZNY, 2007, 83 (02): : 95 - 101
  • [42] High current arc erosion on copper electrodes in air
    Oyvang, Thomas
    Fjeld, Elin
    Rondeel, Wilhelm
    Hagen, Svein Thore
    2011 IEEE 57TH HOLM CONFERENCE ON ELECTRICAL CONTACTS, 2011,
  • [43] ANALYSIS OF ELECTRODE PHENOMENA IN THE HIGH-CURRENT ARC
    COBINE, JD
    BURGER, EE
    JOURNAL OF APPLIED PHYSICS, 1955, 26 (07) : 895 - 900
  • [44] Dynamics of energy release in a low-voltage pulsed arc in air
    A. N. Dovbnya
    K. V. Korytchenko
    M. A. Krasnogolovets
    Yu. Ya. Volkolupov
    Yu. D. Tur
    S. M. Shkirida
    A. I. Kosoi
    Technical Physics, 2003, 48 : 1586 - 1589
  • [45] Dynamics of energy release in a low-voltage pulsed arc in air
    Dovbnya, AN
    Korytchenko, KV
    Krasnogolovets, MA
    Volkolupov, YY
    Tur, YD
    Shkirida, SM
    Kosoi, AI
    TECHNICAL PHYSICS, 2003, 48 (12) : 1586 - 1589
  • [46] Simulation and experimental study of arc motion in a low-voltage circuit breaker considering wall ablation
    Ma, Qiang
    Rong, Mingzhe
    Murphy, Anthony B.
    Wu, Yi
    Xu, Tiejun
    Yang, Fei
    IEICE TRANSACTIONS ON ELECTRONICS, 2008, E91C (08) : 1240 - 1248
  • [47] Microstructure of Contact Material Modified by High-Current Vacuum Arc
    E. V. Yakovlev
    A. V. Schneider
    E. L. Dubrovskaya
    S. A. Popov
    Russian Physics Journal, 2018, 61 : 1034 - 1038
  • [48] Microstructure of Contact Material Modified by High-Current Vacuum Arc
    Yakovlev, E. V.
    Schneider, A. V.
    Dubrovskaya, E. L.
    Popov, S. A.
    RUSSIAN PHYSICS JOURNAL, 2018, 61 (06) : 1034 - 1038
  • [49] ARC VOLTAGE DURING CLOSING WITH REBOUNDS ON HIGH-CURRENT CONTACTS
    WALCZUK, E
    ETZ ARCHIV, 1982, 4 (08): : 249 - 252
  • [50] SIMULATION OF A NON CONVENTIONAL HIGH-CURRENT LOW-VOLTAGE POWER CONVERTER WITH EMTP
    GUIMARAES, C
    OLIVIER, G
    APRIL, GE
    MATHEMATICS AND COMPUTERS IN SIMULATION, 1995, 38 (4-6) : 323 - 333