VSC-HVDC control without PLL for unbalanced grid

被引:0
|
作者
Chen, Zhenliang [1 ]
Wu, Ke [1 ]
Lu, Haiyang [2 ]
Liu, Naiqi [1 ]
Shi, Jianquan [3 ]
机构
[1] Guangdong Power Grid Co, Dongguan Power Supply Bur, Dongguan 523000, Peoples R China
[2] NR Elect Co Ltd, Nanjing 211102, Peoples R China
[3] Nanjing Inst Technol, Nanjing 210000, Peoples R China
关键词
Free; -PLL; VSC-HVDC; Unbalanced grid; LOOP;
D O I
10.1016/j.egyr.2023.05.198
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
When unbalanced faults such as single-phase voltage drop occur in the power grid, VSC-HVDC will fail or become unstable due to sudden changes in amplitude, phase, frequency, etc. of the power grid voltage. Therefore, the role of PLL in a non-ideal power grid is particularly important, but often PLL needs to make a compromise between dynamic response and system stability. Therefore, this paper proposes a free-PLL control strategy under non ideal power grid. First, according to the power transmission model of VSC-HVDC under power grid imbalance, the control command required by the inverter is given, which is determined in the environment free-PLL. Therefore, PLL is not required to retrace the phase of the grid voltage. In addition, in order to overcome the impact of the sudden change of power grid frequency on the free-PLL strategy, a frequency locking strategy is proposed in the free-PLL environment, the response time is about 1 grid cycle. Finally, in order to verify the effectiveness and correctness of the proposed strategy, the VSC-HVDC system's active power transmission stability is guaranteed when the grid voltage encounters different degrees of single-phase sags. (c) 2023 Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
引用
收藏
页码:1439 / 1445
页数:7
相关论文
共 50 条
  • [31] Active and reactive power control of a VSC-HVdc
    Latorre, H. F.
    Ghandhari, M.
    Soder, L.
    ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (10) : 1756 - 1763
  • [32] The Research on the VSC-HVDC Control System Structure
    Yuan, Zhaoqiang
    Wang, Hairong
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [33] Research on Robust Control Strategies for VSC-HVDC
    Zhu, Kaicheng
    Bao, Hai
    2017 3RD INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SCIENCE AND MATERIAL APPLICATION (ESMA2017), VOLS 1-4, 2018, 108
  • [34] Analysis of Active Power Control for VSC-HVDC
    Wang, Wenyuan
    Beddard, Antony
    Barnes, Mike
    Marjanovic, Ognjen
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) : 1978 - 1988
  • [35] Power optimization control of VSC-HVDC system for electromechanical oscillation suppression and grid frequency control
    Bi, Chaohao
    Wu, Jiaqi
    Qian, Yang
    Luo, Xin
    Xie, Jianxiang
    Shi, Jianquan
    Luo, Fang
    FRONTIERS IN ENERGY RESEARCH, 2022, 10
  • [36] Model Predictive Control of VSC-HVDC Embedded into AC Grid Subject to State and Control Constraints
    Thau, E.
    Kanial, E.
    Marinescu, B.
    Denis, G.
    2019 IEEE MILAN POWERTECH, 2019,
  • [37] The Study of Control Strategy for VSC-HVDC applied in offshore wind farm and grid connection
    Dong, Huang
    Yuan, Mao
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [38] A novel control method for a VSC-HVDC system in a grid-connected wind farm
    Liu, Yingpei
    Li, Ran
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2015, 23 (06) : 1558 - 1570
  • [39] Generalized control strategy for grid-connected and island operation of VSC-HVDC system
    Guan, Minyuan
    Zhang, Jing
    Liu, Qiang
    Yang, Liping
    Zhu, Xuesong
    Wu, Guoqiang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (15): : 103 - 109
  • [40] Optimization Control Technology of VSC-HVDC Supporting Partition Interconnection of Urban Power Grid
    Tang X.
    Zhang Z.
    Han M.
    Wang J.
    Xie Y.
    Tian C.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2019, 43 (12): : 179 - 185