Adaptive positioning current measurement method for multi-conductor system based on linear magnetic sensor array

被引:4
|
作者
Fan, Haoyang [1 ]
Zhang, Zhenyuan [1 ]
Huang, Qi [2 ]
Liao, Kaiji [3 ]
Jing, Shi [1 ]
机构
[1] Univ Elect Sci & Technol China, Xiyuan Ave 2006, Chengdu 610000, Peoples R China
[2] Chengdu Univ Technol, East Third Rd 1, Chengdu 610000, Peoples R China
[3] State Grid Sichuan Elect Power Corp Metering Ctr, Wanjing Rd 1, Chengdu 610000, Peoples R China
关键词
Non -contact measurement; Current positioning; Kalman Filter; Crosstalk rejection; Magnetic sensor array; INTERFERENCE; CONTACTLESS; SAG;
D O I
10.1016/j.ijepes.2022.108692
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As transmission and distribution networks now span a wider region, the difficulty of monitoring lines and the incidence of faults are both increased, which reduces the stability of the power system. During the troubleshooting procedure, quick problem identification, line selection, and placement are essential, and non-contact current measurement can be quite helpful. Its advantages include the capacity to monitor high-frequency current and line space position, both of which contain a range of fault characteristics, as well as a high-frequency band, compact size, low cost, and simple installation. In this paper, we present an adaptive positioning current measurement method for multi-conductor systems based on a linear magnetic sensor array. The method detects the position shifts of individual conductors when their locations are displaced to varying degrees using a novel conductor positioning calculation algorithm. Besides, it automatically adjusts the measurement matrix to provide precise current measurements. In the simulations, three-phase parallel currents with an amplitude of 100 A are analyzed based on the parameters of a 15-meter cup-type tensile tower. During the different displacements of the three conductors, the new method calculates the conductor displacements and the current in real-time. For all the three conductor positions change with the maximum amplitude of 2 m, the average error of all the conductor position measurements is about 0.1 m, and the root mean square error (RMSE) of the currents drops from 34.18A to 3.72A with correction, which proves the effectiveness of the algorithm.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Improved Multi-Conductor Interactive Rejection for Current Measurement with Magnetic Sensors Array
    Fan, Haoyang
    Huang, Qi
    Zhang, Zhenyuan
    Jing, Shi
    Zhao, Xihao
    He, Muyao
    2022 IEEE/IAS 58TH INDUSTRIAL AND COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE (I&CPS), 2022,
  • [2] Curved Trapezoidal Magnetic Flux Concentrator Design for Improving Sensitivity of Magnetic Sensor in Multi-Conductor Current Measurement
    Zhu, Ke
    Pong, Philip W. T.
    2016 5TH INTERNATIONAL SYMPOSIUM ON NEXT-GENERATION ELECTRONICS (ISNE), 2016,
  • [3] Positioning Method for Magnetic Sensor Array Based on Linear Regression
    Li, Jiaqi
    Xiao, Jin
    Zhang, Zhijie
    Sun, Dan
    PROCEEDINGS OF THE 2017 12TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2017, : 128 - 132
  • [4] Noninvasive current measurement in multi-conductor cables
    Boeller, Sebastian
    Alic, Belmin
    Hennig, Andreas
    Grabmaier, Anton
    2021 IEEE SENSORS, 2021,
  • [5] Optimisation of an alternating current multi-conductor system
    Munteanu, Calin
    Topa, Vasile
    Simion, Emil
    Mates, Gheorghe
    Grindei, Laura
    De Mey, Gilbert
    Purcar, Marius
    ENGINEERING ANALYSIS WITH BOUNDARY ELEMENTS, 2006, 30 (07) : 582 - 587
  • [6] Research Progress of Current Measurement Method Based on Magnetic Sensor Array
    Hu J.
    Ma H.
    Li P.
    Tian B.
    Liu Z.
    Lü Q.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (05): : 1779 - 1794
  • [7] ADAPTIVE FILTERING-BASED CURRENT RECONSTRUCTION IN NON-CONTACT MAGNETIC SENSOR ARRAY MEASUREMENT SYSTEM
    Chen, Yafeng
    Huang, Qi
    METROLOGY AND MEASUREMENT SYSTEMS, 2019, 26 (04) : 697 - 711
  • [8] A Novel Adaptive Filter for Accurate Measurement of Current with Magnetic Sensor Array
    Chen, Yafeng
    Huang, Qi
    Khawaja, Arsalan Habib
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [9] Rectangular Magnetic Sensor Array for Current Measurement by the Quadrature Method
    Guo, Q.
    Fu, Peng
    Gao, Ge
    Jiang, Li
    Wang, Lensen S.
    Bai, Yuerun R.
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2018, 46 (05) : 1227 - 1233
  • [10] A novel non-invasion magnetic sensor array based measurement method of large current
    Chen, Yafeng
    Huang, Qi
    Khawaja, Arsalan Habib
    Cai, Dongsheng
    Wu, Jie
    MEASUREMENT, 2019, 139 : 78 - 84