Reduction of quadrature armature reaction in salient-pole synchronous generator by rotor flux barrier

被引:1
|
作者
Kim, Jin-Hyok [1 ]
Tae-Song, O. [2 ]
Ri, Yong-Sop [1 ]
Kim, Song-Ho [3 ]
Yun, Chang-Jin [1 ]
机构
[1] Kim Il Sung Univ, Fac Mech, Pyongyang, North Korea
[2] Hamhung Univ Hydraul & Power, Fac Elect Engn, Hamhung, North Korea
[3] Adv Sci & Technol Exchange Co, Pyongyang, North Korea
关键词
Armature reaction reactance; Flux barrier; Salient-pole synchronous generator; Synchronous reactance; REACTION FIELD;
D O I
10.1007/s00202-023-01955-8
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The estimation of armature reaction is of great importance in the design and operation of synchronous machines. This paper proposes a new method to reduce quadrature armature reaction in salient-pole synchronous generators. The proposed method is to reduce the quadrature axis synchronous reactance of a salient-pole synchronous generator by novel flux barrier to the rotor poles. Finite element analysis by Maxwell software was used to evaluate the nonlinearity of the synchronous reactances and to obtain the result that the quadrature axis synchronous reactance decreases when the flux barrier is introduced into the rotor pole of a salient-pole synchronous generator. As part of the study, a new flux barrier was introduced and experimented on the rotor pole of a 50 kW, 4-pole salient-pole synchronous generator without damper winding used for diesel generator.
引用
收藏
页码:4387 / 4398
页数:12
相关论文
共 50 条
  • [21] Artificial neural network approach for locating internal faults in salient-pole synchronous generator
    Yaghobi, Hamid
    Mashhadi, Habib Rajabi
    Ansari, Kourosh
    EXPERT SYSTEMS WITH APPLICATIONS, 2011, 38 (10) : 13328 - 13341
  • [22] A Detailed Analytical Model of a Salient-Pole Synchronous Generator Under Dynamic Eccentricity Fault
    Babaei, Mojtaba
    Faiz, Jawad
    Ebrahimi, Bashir Mahdi
    Amini, S.
    Nazarzadeh, Jalal
    IEEE TRANSACTIONS ON MAGNETICS, 2011, 47 (04) : 764 - 771
  • [23] Effect of rotor eccentricity on the branch induced voltage of the large salient-pole synchronous generator under different winding connection condition
    Zhu, Jiahui
    Qiu, Arui
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2009, 24 (10): : 1 - 5
  • [24] Torque Ripple Reduction of a Salient-Pole Permanent Magnet Synchronous Machine With an Advanced Step-Skewed Rotor Design
    Chen, Wei
    Ma, Jien
    Wu, Guichu
    Fang, Youtong
    IEEE ACCESS, 2020, 8 (08): : 118989 - 118999
  • [25] Analysis of leakage flux distributions in a salient-pole synchronous machine using finite elements
    Shima, K
    Ide, K
    Takahashi, A
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2003, 18 (01) : 63 - 70
  • [26] Modeling of salient-pole brake with hollow nonmagnetic rotor
    Potapov L.A.
    Babak S.Yu.
    Russian Electrical Engineering, 2011, 82 (5) : 260 - 263
  • [27] Electromagnetic torque components in the synchronous salient-pole machine
    Spalek, D
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 1997, 16 (03) : 129 - +
  • [28] APPRAISAL OF SATURATION IN SALIENT-POLE SYNCHRONOUS MACHINES.
    Abdel-Hamid, Radwan H.
    Morsi, M.F.
    Fahmi, M.A.
    Modelling, Measurement and Control A, 1987, 10 (04): : 17 - 28
  • [29] Determination of Load Angle for Salient-pole Synchronous Machine
    Sumina, D.
    Sala, A.
    Malaric, R.
    MEASUREMENT SCIENCE REVIEW, 2010, 10 (03): : 89 - 96
  • [30] Modeling of Salient-Pole Wound-Rotor Synchronous Machines for Population-Based Design
    Bash, Michelle L.
    Pekarek, Steven D.
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2011, 26 (02) : 381 - 392