Feasibility study on energy harvesting with thermoelectric generators in a photovoltaic-ground source heat pump system

被引:0
|
作者
Chae, Hobyung [1 ]
Bae, Sangmu [1 ]
Jeong, Jae-Weon [3 ]
Nam, Yujin [2 ]
机构
[1] Pusan Natl Univ, Res Inst Ind Technol, Busan 46241, South Korea
[2] Pusan Natl Univ, Dept Architectural Engn, Busan 46241, South Korea
[3] Hanyang Univ, Coll Engn, Dept Architectural Engn, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Thermoelectric generator; Energy harvesting; Feasibility study; Hybrid system; Generated electricity; HIGH-PERFORMANCE; PROTOTYPE; EXCHANGER; DESIGN;
D O I
10.1016/j.egyr.2023.11.023
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Thermoelectric generators (TEGs) harness temperature differences to produce electricity and hold promise for diverse industrial applications. However, their limited conversion efficiency casts doubt on their role in achieving energy independence. This study introduces an advanced technique that exploits temperature gradients in water pipes, utilizing supplementary TEGs to augment power generation. This method maintains a stable temperature gradient for TEG operation. Additionally, TEG power output can be efficiently modulated via flow control. In the feasibility evaluation for residential settings, the temperature fluctuations across each system unit were analyzed. In the active system, the chosen sites for TEG integration were units equipped to manage heat transfer using working fluids. The inlet and outlet temperatures were calculated for photovoltaic-thermal (PVT) systems, ground heat exchangers (GHEs), and heat storage tanks (HSTs). The electricity produced by the TEGs was benchmarked against their conversion efficiency, zT. The results indicated that the TEGs yielded 10.95 kWh of electricity when systematically implemented in each unit. To realize a zero-energy building, an area of 64.5 m2 per unit is necessitated for TEG deployment, given a zT value of 1.
引用
收藏
页码:71 / 82
页数:12
相关论文
共 50 条
  • [31] Experimental study of subterranean heat exchangers in ground source heat pump system
    Wei, Jia-Xiang
    Tang, Zhi-Wei
    Ma, Chong-Fang
    Zhang, Hong-Yu
    Liu, Wen-Xue
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2007, 28 (01): : 146 - 148
  • [32] A study of photovoltaic/thermal (PVT)-ground source heat pump hybrid system by using fuzzy logic control
    Putrayudha, S. Andrew
    Kang, Eun Chul
    Evgueniy, E.
    Libing, Y.
    Lee, Euy Joon
    APPLIED THERMAL ENGINEERING, 2015, 89 : 578 - 586
  • [33] The Study on the Performance of Solar Photovoltaic and Air Source Heat Pump Composite Building Energy Supply System
    Tong, Jiannan
    Quan, Zhenhua
    Zhao, Yaohua
    Wang, Gang
    Cai, Junjie
    Chi, Yuanying
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 4082 - 4089
  • [34] Experimental investigation of the energy performance of a photovoltaic-thermal assisted ground source heat pump system for net plus energy houses
    Choi, Won-Jong
    Lee, Wangje
    Kim, Deuk-Won
    An, Youngsub
    Joo, Hong-Jin
    Hong, Joo Young
    Kim, Min-Hwi
    CASE STUDIES IN THERMAL ENGINEERING, 2025, 69
  • [35] Feasibility analysis for an integrated system using photovoltaic-thermal and ground source heat pump based on real-scale experiment
    Bae, Sangmu
    Nam, Yujin
    RENEWABLE ENERGY, 2022, 185 : 1152 - 1166
  • [36] Intermittent experimental study of a vertical ground source heat pump system
    Shang, Yan
    Dong, Ming
    Li, Sufen
    APPLIED ENERGY, 2014, 136 : 628 - 635
  • [37] Experimental study on a ground source heat pump system in cold area
    Liu, Yi
    Wang, Yaxuan
    Zhang, Yaning
    FRONTIERS OF GREEN BUILDING, MATERIALS AND CIVIL ENGINEERING, PTS 1-8, 2011, 71-78 : 2566 - +
  • [38] Study on the change of soil temperature in Ground Source Heat Pump System
    Han, Shili
    Su, Shunyu
    Liu, Lamei
    Zhou, Chuanhui
    Shi, Lei
    PROCEEDINGS OF THE 2015 INTERNATIONAL FORUM ON ENERGY, ENVIRONMENT SCIENCE AND MATERIALS, 2015, 40 : 178 - 183
  • [39] Parametric study of a vertically configured ground source heat pump system
    Madessa, Habtamu B.
    Torger, B.
    Bye, Pal F.
    Erlend, A.
    8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 1040 - 1049
  • [40] Operating characteristics of photovoltaic/thermal-ground source heat pump system in cold regions
    Wang, Fang
    Liu, Mengwei
    Pang, Dongqing
    Li, Zhiqiang
    Lu, Shixiang
    Du, Weifeng
    Guo, Wenliang
    Hu, Guangyu
    Yin, Jian
    APPLIED THERMAL ENGINEERING, 2024, 248