Design of district heating system with dual-temperature supply based on thermal energy discretisation and matching method

被引:2
|
作者
Chen, Wei [1 ,2 ]
Li, Tiancheng [1 ,2 ]
Li, Xianting [1 ,2 ]
Wang, Baolong [1 ,2 ]
Cao, Yang [3 ]
Shi, Wenxing [1 ,2 ,4 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] Tsinghua Univ, Sch Architecture, Beijing Key Lab Indoor Air Qual Evaluat & Control, Beijing 100084, Peoples R China
[3] China Acad Bldg Res, Inst Bldg Environm & Energy, Beijing 100084, Peoples R China
[4] Tsinghua Univ Beijing, Sch Architecture, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
District heating; Dual temperature heating; Low return temperature; Combined heat and power; CHINA;
D O I
10.1016/j.jclepro.2023.138533
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
As heating requirements continue to evolve and heating technology advances, radiators and radiant floor heating devices, which require different supply-water temperatures, have gradually become the two main heating terminals in district heating systems. However, the primary return-water temperature of current solutions based on heat exchangers and heat pumps is relatively high and fails to recover waste heat from the combined heat and power plants, owing to improper use of heat sources. To address this issue, a heat exchanger network optimisation method-the thermal energy discretisation and matching method-was used to design a dual-temperature water district heating system consisting of two absorption heat pumps and two heat exchangers. The primary supply water flows through the two generators, two heat exchangers, and two evaporators of the absorption heat pumps. The radiator and floor heating return water was divided into two parts and heated by the heat exchanger and the absorber and condenser of the absorption heat pump, respectively. The performance of the designed heating station was evaluated using the coefficient of performance and the primary return-water temperature and compared with that of other district heating systems. The changes in the district heating system's configuration when the boundary conditions changed were investigated. Results showed that (1) the designed system based on thermal energy discretisation and matching method -had the lowest primary return-water temperature of 18.8 degrees C and the highest coefficient of performance of 5.62. (2) When the low-temperature load ratio changed from 0% to 100% while maintaining a constant total load, the system's form changed regularly. (3) When the primary supply-water temperature increased, the heating station's form remained unchanged and the capacity of the heat exchange equipment changed regularly. (4) When the secondary supply and return-water temperatures increased, the evaporation temperature of the absorption heat pump increased, resulting in a change in the system's form. This study provides valuable insight into the design of district heating systems that supply dualtemperature water under various design conditions.
引用
收藏
页数:18
相关论文
共 50 条
  • [31] Energy efficiency performance of multi-energy district heating and hot water supply system
    金楠
    赵靖
    朱能
    Journal of Central South University, 2012, 19 (05) : 1377 - 1382
  • [32] Energy efficiency performance of multi-energy district heating and hot water supply system
    Jin Nan
    Zhao Jing
    Zhu Neng
    JOURNAL OF CENTRAL SOUTH UNIVERSITY, 2012, 19 (05) : 1377 - 1382
  • [33] Energy efficiency performance of multi-energy district heating and hot water supply system
    Nan Jin
    Jing Zhao
    Neng Zhu
    Journal of Central South University, 2012, 19 : 1377 - 1382
  • [34] Various disturbances propagation analysis of district heating system based on the standardized thermal resistance method
    Chen, Zhuoxian
    Wang, Xingce
    Hao, Junhong
    Fang, Wanggang
    Du, Xiaoze
    Hong, Feng
    ENERGY SCIENCE & ENGINEERING, 2023, 11 (12) : 4611 - 4624
  • [35] Oberhausen District-Heating System - Part of an Integrated Energy-Supply System.
    Deuster, Gerhard
    Zenker, Peter
    Fernwaerme International, 1979, 8 (02): : 35 - 40
  • [36] Exergy Analysis for Utilizing Latent Energy of Thermal Energy Storage System in District Heating
    Yi, Joong Yong
    Kim, Kyung Min
    Lee, Jongjun
    Oh, Mun Sei
    ENERGIES, 2019, 12 (07)
  • [37] Droop control for district heating networks: Solution for temperature control of multi-energy system with renewable power supply
    Lan, Tian
    Strunz, Kai
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 146
  • [38] Influence of centralized and distributed thermal energy storage on district heating network design
    Jebamalai, Joseph Maria
    Marlein, Kurt
    Laverge, Jelle
    ENERGY, 2020, 202
  • [39] Thermal design and optimization of high-temperature heat pump integrated with district heating benchmarked in Denmark for process heat supply
    Sadeghi, Mohsen
    Petersen, Tage
    Yang, Zhenyu
    Zuhlsdorf, Benjamin
    Madsen, Kim Stenholdt
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 159 : 356 - 370
  • [40] Energy Saving Control of District Heating System Based on MATLAB
    Sun, Yu
    Liu, Yadan
    Su, Hui
    Tao, Xiaoxia
    MATHEMATICAL PROBLEMS IN ENGINEERING, 2022, 2022