Computation of electromagnetic forces in the windings of amorphous core transformers

被引:2
|
作者
Thanh, Bao Doan [1 ]
Tung, Doan Duc [1 ]
Le, Tuan-Ho [1 ]
机构
[1] Quy Nhon Univ, Fac Engn & Technol, Quy Nhon, Binh Dinh Provi, Vietnam
关键词
amorphous transformer; electromagnetic force; leakage flux; magnetic vector potential formulation; short-circuit current; FIELD;
D O I
10.24425/aee.2023.145423
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electromagnetic forces generated by the short circuit current and leakage flux in low-and high-voltage windings of distribution transformers as well as amorphous core transformers will cause the translation, destruction, and explosion of the windings. Thus, the investigation of these forces plays a significant role for researchers and manufacturers. Many authors have recently used the finite element method to analyze electromagnetic forces. In this paper, an analytic model is first developed for magnetic vector potential formulations to compute the electromagnetic forces (i.e., axial and radial forces) acting on the low-and high-voltage windings of an amorphous core transformer. The finite element technique is then presented to validate the results obtained from the analytical model. The developed model is applied to an actual problem.