Regenerator performance using freezing concentration for heat source tower heat pump system

被引:5
|
作者
Han, Chong [1 ,2 ]
Yu, Muyang [1 ,2 ]
Hou, Chongchong [1 ,2 ]
Jiang, Huimin [3 ]
Chen, Chuanbao [3 ]
Yao, Yang [1 ,2 ]
Ni, Long [1 ,2 ]
机构
[1] Harbin Inst Technol, Sch Architecture, Harbin 150090, Peoples R China
[2] Minist Ind & Informat Technol, Key Lab Cold Reg Urban & Rural Human Settlement En, Harbin, Peoples R China
[3] Nanjing Wuzhou Refrigerat Grp Co Ltd, Nanjing, Peoples R China
基金
中国国家自然科学基金;
关键词
Heat source tower heat pump; Freeze concentration; Refrigeration; Heat transfer; Freezing process; DESICCANT;
D O I
10.1016/j.applthermaleng.2023.121053
中图分类号
O414.1 [热力学];
学科分类号
摘要
Freeze concentration has a good regeneration effect and is easy for latent heat utilization. The electronic expansion valve opening has a great impact on the icing process. Hence, to investigate variations in the freezing process and gain the optimum regeneration effect, a solution regenerator was tested under different system-side control strategies. The solution volume flow was 5 m3/h and the electronic expansion valve opening degree (OEEV) was from 100% to 50%. For ice-covering growth, ice in low opening degree spent a long time to cover the plate. The area of ice under 100% to 65% OEEV was 1.43 times that under 50% OEEV. Peak velocities from 100% to 50% OEEV all appeared in the early stage of icing development. Moreover, the low opening degree made the ice distribute unevenness. The percentage slope of 100% OEEV was 1.23% and that of 50% OEEV was 3.46%. In addition, decreasing ice thickness uniformity was beneficial to the separation process. The separation ratio from 100% to 50% OEEV was 49.51%, 51.67%, 57.88%, and 74.54%, respectively. Both the low average thickness growth rate and high separation ratio were beneficial to increase the regeneration concentration. The effective specific ice production rate was from 100% to 50% OEEV was 5.99 kg/kWh, 6.18 kg/kWh, 6.94 kg/kWh, and 6.88 kg/kWh, respectively. Results showed that 65% OEEV operation was optimum for the solution regenerator unit using freeze concentration.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Application of a heat pump system using untreated urban sewage as a heat source
    Liu, Zhibin
    Ma, Liangdong
    Zhang, Jili
    Applied Thermal Engineering, 2013, 61 (02) : 747 - 757
  • [32] Alternative refrigerants for the heat pump of a ground source heat pump system
    Sagia, Zoi
    Rakopoulos, Constantinos
    APPLIED THERMAL ENGINEERING, 2016, 100 : 768 - 774
  • [33] A multivariate nonlinear regression prediction model for the performance of cooling tower assisted ground source heat pump system
    Lan, Ting
    Hu, Rong
    Tang, Qi
    Han, Minxia
    Wu, Shuqin
    Liu, Gang
    ENERGY CONVERSION AND MANAGEMENT, 2025, 325
  • [34] Heat storage characteristics and application analysis of heat source tower in soil thermal balance of ground source heat pump
    Hu, Zicheng
    Geng, Shuwen
    Huang, Yufei
    Ge, Fenghua
    Wang, Yuecheng
    ENERGY AND BUILDINGS, 2021, 235
  • [35] Experimental performance evaluation of a novel anti-fouling wastewater source heat pump system with a wastewater tower
    Shen, Chao
    Lei, Zhuoyu
    Lv, Guoquan
    Ni, Long
    Deng, Shiming
    APPLIED ENERGY, 2019, 236 : 690 - 699
  • [36] Performance simulation of multiple heat source solar heat pump water heater system
    Yang, Lei
    Zhang, Xiaosong
    Huagong Xuebao/CIESC Journal, 2009, 60 (09): : 2292 - 2298
  • [37] REQUIREMENT OF HEAT PUMP SYSTEM PERFORMANCE FOR AN ENERGY EFFICIENT SEAWATER-SOURCE HEAT PUMP DISTRICT HEATING SYSTEM
    Shu, Haiwen
    Lin Duanmu
    Li, Xiangli
    Zhu, Yingxin
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1644 - 1651
  • [38] Operating performance simulation of ground source heat pump system
    Wang, Jing-Gang
    Ma, Yi-Tai
    Zhang, Zi-Ping
    Wang, Kan-Hong
    Hou, Li-Quan
    Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2003, 24 (03):
  • [39] Research on performance of the coupled heat and mass transfer in ground source heat pump system
    Gu, Yaxiu
    Ma, Fengfeng
    Wang, Wenke
    8TH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2016, 146 : 522 - 528
  • [40] Study of the performance of an urban original source heat pump system
    Zhao, X. L.
    Fu, L.
    Zhang, S. G.
    Jiang, Y.
    Lai, Z. L.
    ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (04) : 765 - 770