Study on air-side performance of air-cooled heat exchangers under large air velocity and wet conditions

被引:1
|
作者
Wei, Wenjian [1 ,2 ]
Xu, Guoliang [1 ]
Wang, Yanfeng [2 ]
Ding, Ergang [2 ]
机构
[1] Zhejiang Univ Water Resources & Elect Power, Inst Adv Heat Transfer & Energy Applicat, Hangzhou 310018, Zhejiang, Peoples R China
[2] Zhejiang DunAn Themal Tech Co Ltd, Zhuji 311835, Zhejiang, Peoples R China
关键词
Heat transfer; Carryover; High humidity; Fin -and -tube heat exchanger; Microchannel heat exchanger; CONDENSATE DRAINAGE BEHAVIOR; MASS-TRANSFER; FIN; SURFACE;
D O I
10.1016/j.tsep.2024.102389
中图分类号
O414.1 [热力学];
学科分类号
摘要
Humidity condensation and carryover from air-cooled heat exchanger affects human comfort and equipment security in the working environment. Surface treatment with a hydrophilic coating is an effective water drainage and carryover resistance solution. In present study, the condensation carryover and air-side performances of a fin-and-tube heat exchanger (FTHX) and microchannel heat exchanger (MCHX) with different fin pitches and surface treatments were experimentally investigated under large air velocities and different inlet humidity conditions. Hydrophilic treatment of FTHX improved heat transfer and condensation drainage, and reduced air pressure loss. In contrast, with MCHX, hydrophilic treatment did not improve heat transfer and rather increased the air pressure loss. For FTHX, the results showed that, compared with the bare fin, the hydrophilic surface treated fin enhanced the Colburn j factor by 20-60 and 10-40% at inlet air dry/wet bulb temperature of 26.7/ 19.4(degrees)C (normal humidity condition) and 26.7/23.9(degrees)C (high humidity condition), respectively. The air friction factor f was reduced by namely by 10-40 and 20-40% under normal- and high-humidity conditions, respectively. Condensing water flowed or retained over the fin surface in film, which suppressed the formation of a water bridge among fins, improved water carry-over, and increased the critical air velocity by 50%. However, water film formation over the MCHX enlarged the water stagnant around the fin corner, which increased the air resistance by 5-10%, and increased the probability of the continuous water bridge formation and carryover.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] ASSESSING AIR-SIDE PERFORMANCE OF AIR-COOLED HEAT EXCHANGERS.
    Berryman, Bob
    Russell, Charles
    Process Engineering (London), 1986, 67 (04):
  • [2] ENHANCEMENT OF AIR-SIDE HEAT TRANSFER IN AIR-COOLED HEAT EXCHANGERS USING DIMPLED FINS
    Vu, Tung X.
    Dhir, Vijay K.
    JOURNAL OF ENHANCED HEAT TRANSFER, 2021, 28 (01) : 63 - 84
  • [3] Improving air-side heat transfer performance in air-cooled power plant condensers
    Lin, Jennifer
    Mahvi, Allison J.
    Kunke, Taylor S.
    Garimella, Srinivas
    APPLIED THERMAL ENGINEERING, 2020, 170
  • [4] AIR-SIDE HEAT TRANSFER ENHANCEMENT AND PUMPING POWER PENALTY IN AIR-COOLED HEAT EXCHANGERS WITH DIMPLED FINS
    Vu, Tung X.
    Mohanta, Lokanath
    Dhir, Vijay K.
    PROCEEDINGS OF THE ASME SUMMER HEAT TRANSFER CONFERENCE, 2017, VOL 1, 2017,
  • [5] Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions
    Kim, MH
    Bullard, CW
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (07): : 924 - 934
  • [6] Air-cooled Heat Exchangers
    S Afr Mech Eng, 10 (35):
  • [7] Parametric study of the air-side performance of slit fin-and-tube heat exchangers in wet conditions
    Wang, CC
    Lee, WS
    Sheu, WJ
    Chang, YJ
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2001, 215 (09) : 1111 - 1121
  • [8] AIR-COOLED HEAT EXCHANGERS.
    Zanker, Adam
    Machine Design, 1979, 51 (28) : 158 - 166
  • [9] QUIETER AIR-COOLED HEAT EXCHANGERS
    DRYDEN, SL
    JUDD, SH
    AMERICAN INDUSTRIAL HYGIENE ASSOCIATION JOURNAL, 1970, 31 (02): : 9 - &
  • [10] Air-side performance evaluation of three types of heat exchangers in dry, wet and periodic frosting conditions
    Zhang, Ping
    Hrnjak, P. S.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05): : 911 - 921