Floor response spectra and seismic design method of electrical equipment installed on floor in indoor substation

被引:5
|
作者
Zhu, Wang [1 ]
Wu, Minger [1 ,2 ]
Xie, Qiang [1 ,2 ,3 ]
Xu, Junxin [1 ]
机构
[1] Tongji Univ, Dept Struct Engn, Shanghai 200092, Peoples R China
[2] Tongji Univ, Key Lab Performance Evolut & Control Engn Struct, Minist Educ, Shanghai 200092, Peoples R China
[3] Tongji Univ, Dept Struct Engn, Singping Rd 1239, Shanghai 200092, Peoples R China
基金
中国国家自然科学基金;
关键词
Indoor substation; Electrical equipment; Floor response spectra; Amplification factor; Seismic design method;
D O I
10.1016/j.soildyn.2023.108138
中图分类号
P5 [地质学];
学科分类号
0709 ; 081803 ;
摘要
Electrical equipment installed on floors is a typical type of nonstructural component in indoor substations, which could be subjected to earthquake loading during seismic events. To investigate the seismic design method of floor electrical equipment in indoor substations, simulation models of four whole-indoor substations comprising main control buildings and their floor electrical equipment were established. Seismic response spectrum analyses of main-attachment structures were performed with a high number of ground motions as inputs. Using mathematical statistics and data fitting methods, this research suggested the calculation formula of amplification factor of floor acceleration response spectrum. Specifically, when the periodic ratio of electrical equipment to main control building is in the range of 0.9-1.1, the system would produce a strong resonance-like effect with a peak spectral amplification factor. The floor response spectrum for seismic design was influenced by four factors: equipment importance category, floor position, damping ratio of electrical equipment, and torsion effect of main control building. Following that, a seismic design method especially applicable for electrical equipment installed on floor in indoor substation, which combines amplification factor and calculation method of seismic action indicated in the relevant specification, was presented. Lastly, a typical 220 kV whole-indoor substation was taken as an example to validate the accuracy of the design method highlighted in this article.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Anti-seismic Design Method for Floor Electrical Equipment in Whole-indoor Substation
    Xie Q.
    Bian X.
    Xu J.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (06): : 2155 - 2163
  • [2] FLOOR RESPONSE SPECTRA FOR EQUIPMENT
    OROURKE, MJ
    KOUNTOURIS, G
    JOURNAL OF THE ENGINEERING MECHANICS DIVISION-ASCE, 1979, 105 (05): : 907 - 911
  • [3] Floor response spectra for beyond design basis seismic demand
    Jha, Somnath
    Roshan, A. D.
    Bishnoi, L. R.
    NUCLEAR ENGINEERING AND DESIGN, 2017, 323 : 259 - 268
  • [4] Design floor spectra for nonstructural components and equipment in buildings
    Tsinghua Univ, Beijing, China
    Qinghua Daxue Xuebao, 6 (82-86):
  • [5] Towards improved floor spectra estimates for seismic design
    Sullivan, Timothy J.
    Calvi, Paolo M.
    Nascimbene, Roberto
    EARTHQUAKES AND STRUCTURES, 2013, 4 (01) : 109 - 132
  • [6] GENERATION OF SEISMIC FLOOR SPECTRA
    SINGH, MP
    JOURNAL OF THE ENGINEERING MECHANICS DIVISION-ASCE, 1975, 101 (05): : 593 - 607
  • [7] Seismic response of electrical substation equipment interconnected by flexible conductors
    Filiatrault, A
    Stearns, C
    JOURNAL OF STRUCTURAL ENGINEERING-ASCE, 2004, 130 (05): : 769 - 778
  • [8] Numerical modeling for the seismic response of interconnected electrical substation equipment
    Ahmet Güllü
    Innovative Infrastructure Solutions, 2023, 8
  • [9] Numerical modeling for the seismic response of interconnected electrical substation equipment
    Gullu, Ahmet
    INNOVATIVE INFRASTRUCTURE SOLUTIONS, 2023, 8 (01)
  • [10] Seismic response of nonstructural components in case of nonlinear structures based on floor response spectra method
    Oropeza, Marcelo
    Favez, Pascale
    Lestuzzi, Pierino
    BULLETIN OF EARTHQUAKE ENGINEERING, 2010, 8 (02) : 387 - 400