An Enhanced Parameter-Free Fault Locator for Untransposed Line With Unsynchronized Terminals

被引:1
|
作者
Kalita, Kaustav [1 ,2 ]
Anand, Shubham [3 ]
Parida, S. K. [3 ]
机构
[1] Power Grid Corp India Ltd, Gurgaon 122001, India
[2] Indian Inst Technol, Patna 801106, Bihar, India
[3] Indian Inst Technol, Dept Elect Engn, Patna 801106, Bihar, India
关键词
Fault location; untransposed configuration; two-terminal line; unsynchronized measurements; impedance and admittance matrix;
D O I
10.1109/TPWRD.2023.3295998
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This letter presents a novel fault location algorithm for single circuit untransposed line, which is independent of transmission line parameters and unsynchronized measurement. The novelty of proposed algorithm is that it considers asymmetry in untransposed line while considering unequal angles of synchronism mismatch in pre-fault and fault conditions. Thus, in contrast to existing techniques the proposed algorithm can be applied to conductor configuration other than delta/flat configuration of untransposed line. Simulation results using EMTP-RV platform along with those obtained using field data are presented. The test results verify the accuracy and validity of the proposed method.
引用
收藏
页码:3733 / 3736
页数:4
相关论文
共 38 条
  • [11] Transmission Line Parameter-Free Fault Location Results Using Field Data
    Fan, Wen
    Liao, Yuan
    2018 IEEE POWER AND ENERGY CONFERENCE AT ILLINOIS (PECI), 2018,
  • [12] Parameter-Less Fault Locator for Double-Circuit Transmission Line Using Two-Terminal Unsynchronized Measurements
    Saber, Ahmed
    Zeineldin, H. H.
    El-Saadany, Ehab F.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (05) : 2616 - 2629
  • [13] A Non-Iterative Fault Location Algorithm for Transposed/Untransposed Transmission Line Immune to Unsynchronized Measurements
    Kalita, Kaustav
    Anand, Shubham
    Parida, S. K.
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2023, 59 (01) : 422 - 433
  • [14] Unsynchronized fault location based on distributed parameter line model
    Liao, Yuan
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2007, 35 (09) : 1061 - 1077
  • [15] CANNYLINES: A PARAMETER-FREE LINE SEGMENT DETECTOR
    Lu, Xiaohu
    Yao, Jian
    Li, Kai
    Li, Li
    2015 IEEE INTERNATIONAL CONFERENCE ON IMAGE PROCESSING (ICIP), 2015, : 507 - 511
  • [16] Parameter-Free On-line Deep Learning
    Wawrzynski, Pawel
    AUTOMATION 2017: INNOVATIONS IN AUTOMATION, ROBOTICS AND MEASUREMENT TECHNIQUES, 2017, 550 : 543 - 553
  • [17] Distributed Parameter Based Setting-Free Fault Locator for Double-Circuit Line Using Fault Data
    Kalita, Kaustav
    Anand, Shubham
    Parida, S. K.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (04) : 2981 - 2984
  • [18] Parameter-free fault location for transmission lines based on optimisation
    Davoudi, Masoud
    Sadeh, Javad
    Kamyab, Ebadollah
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (11) : 1061 - 1068
  • [19] A new parameter-free fault location approach for power distribution systems
    Hamdouche, Tarek
    Boushaki, Saida Ishak
    Bendjeghaba, Omar
    Brakta, Noureddine
    COMPUTERS & ELECTRICAL ENGINEERING, 2023, 111
  • [20] A Closed Form Solution for Line Parameter-Less Fault Location With Unsynchronized Measurements
    Kalita, Kaustav
    Anand, Shubham
    Parida, S. K.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1997 - 2006