Study on Short-circuit current interruption characteristics of Double-break fast vacuum circuit breaker within the minimum arcing time

被引:2
|
作者
Guan, Chen [1 ]
Ding, Jiangang [1 ]
Yao, Xiaofei [1 ]
Zheng, Jiaming [1 ]
Mu, Shengquan [1 ]
Liu, Zhiyuan [1 ]
Wang, Jianhua [1 ]
Geng, Yingsan [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Fast vacuum circuit breaker; Controlled switching technology; Minimum arcing time; Double break; Short-circuit current interruption; VOLTAGE DISTRIBUTION; SERIES; MECHANISM; RECOVERY; GAPS;
D O I
10.1016/j.ijepes.2022.108865
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
It is significant for circuit breakers to expel a short-circuit fault in a short time for the new power grid with high proportional photovoltaic or wind power plants to achieve high transient operating stability. Compared with a traditional circuit breaker, a fast vacuum circuit breaker (FVCB), operated by an electromagnetic repulsion actuator, has an extremely shorter opening time and lower deviation in their opening times. This potentially contributes the FVCBs to interrupting a short-circuit fault current in the first half-wave when introducing a controlled switching technology. Meanwhile, it is beneficial to improve the short-circuit current breaking capacity of the FVCBs by adopting series-connected double-break circuit breaker technologies. This paper aims to explore short-circuit current interruption characteristics of a double-break FVCB within the minimum arcing time. We performed a series of short-circuit current interruption tests in a Weil synthetic test circuit. Two seriesconnected FVCBs and independent single-break FVCBs were used. Three different kinds of opening velocities were adopted for each of the FVCBs. Results showed that the increase in opening velocity resulted in both a decrease in the minimum arcing time and the critical arc extinguishing contact gap, whether for the single-break or the double-break interruption tests. The ratio of the shared voltage on each of the series-connected FVCBs was about 54 (for the break on the high-voltage side) and 9 (for the break on the low-voltage side). Taking the break with a shorter opening time as a break in the high-voltage side could reduce the minimum arcing time and the critical arc extinguishing contact gap. At the same opening velocity, the sum of the critical arc extinguishing contact gap of the two breaks in double-break interruption tests was significantly higher than twice the critical arc extinguishing contact gap in the single-break interruption tests. This could be caused by the fact that in double-break interruption tests, after the breakdown of one break, even if the break restored insulation, could not share the transient recovery voltage (TRV) before the break broke down. In addition, the sudden drop of TRV without breakdown occurred for the break on the high-voltage side might correlate with the micro-discharge of the vacuum gap. The interaction of the charged particles with the electrode surface would be responsible for the formation and evolution of the micro-discharge in some successful interruption cases.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Interruption Capability of a Fast Vacuum Circuit Breaker with a Short Arcing Time
    Zhang, Bojian
    Tan, Yaxiong
    Ren, Li
    Wang, Jianhua
    Geng, Yingsan
    Liu, Zhiyuan
    Yanabu, Satoru
    2016 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 2, 2016,
  • [2] Interruption characteristics of double-break vacuum circuit breakers
    Ide, Naotaka
    Tanaka, Osamu
    Yanabu, Satoru
    Kaneko, Shuhei
    Okabe, Shigemitsu
    Matsui, Yoshihiko
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (04) : 1065 - 1072
  • [3] Dependence of Short Circuit Breaking Current on its Minimum Arcing Times of a Fast Vacuum Circuit Breaker
    Guan, Chen
    Yao, Xiaofei
    Wang, Weidong
    Zhang, Ran
    Zhang, Luyang
    Zhang, Jun
    Chen, Xinggui
    Wang, Jianhua
    Liu, Zhiyuan
    Geng, Yingsan
    29TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2020), 2021, : 371 - 374
  • [4] Experimental Investigation on the Matching Characteristics of Vacuum Circuit Breaker with Double-break
    Ge, Guowei
    Liao, Minfu
    Duan, Xiongying
    Wang, Shanjun
    Cheng, Xian
    Zou, Jiyan
    PROCEEDINGS OF THE 2014 26TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV-2014), 2014, : 493 - 496
  • [5] Capacitive making of vacuum circuit breakers: Double-break vacuum circuit breaker is superior to single-break vacuum circuit breaker
    Geng, Yun
    Zhang, Jun
    Yao, Xiaofei
    Fan, Jun
    Jin, Qingbin
    Geng, Yingsan
    Liu, Zhiyuan
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 204
  • [6] Experimental Investigation Into the Synergy of Vacuum Circuit Breaker With Double-Break
    Ge, Guowei
    Liao, Minfu
    Duan, Xiongying
    Cheng, Xian
    Zhao, Yan
    Liu, Zhiheng
    Zou, Jiyan
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2016, 44 (01) : 79 - 84
  • [7] Design of a 126 kV Double-break Fast Vacuum Circuit Breaker for Controlled Switching
    Zhang, Bojian
    Ai, Shaogui
    Du, Wei
    Yao, Xiaofei
    Zhang, Ran
    Wang, Jianhua
    Liu, Zhiyuan
    Geng, Yingsan
    Yanabu, Satoru
    2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 103 - 106
  • [8] Controlled Fast Vacuum Breaking of an AC Short-Circuit Current in a Short-arcing Time
    Yao, Xiaofei
    Guan, Chen
    Ding, Jian'gang
    Ai, Shaogui
    Ma, Kui
    Wang, Jianhua
    Geng, Yingsan
    Liu, Zhiyuan
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (08)
  • [9] A Relationship Between Minimum Arcing Interrupting Capability and Opening Velocity of Vacuum Interrupters in Short-Circuit Current Interruption
    Zhang, Bojian
    Ren, Li
    Ding, Jian'gang
    Wang, Jianhua
    Liu, Zhiyuan
    Geng, Yingsan
    Yanabu, Satoru
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (06) : 2822 - 2828
  • [10] Effect of Arcing Time on Voltage Distribution of Double-Break Vacuum Circuit Breaker During the Transient Recovery Voltage Rising Phase
    Zhang, Hao
    Liao, Minfu
    Fu, Yifan
    Chen, Zhanqing
    Dong, Huaqing
    Zou, Jiyan
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (04) : 1357 - 1362