Rapid Building Energy Modeling Using Prototype Model and Automatic Model Calibration for Retrofit Analysis with Uncertainty

被引:4
|
作者
Chen, Yixing [1 ,2 ]
Wei, Wanlei [1 ]
Song, Chengcheng [1 ]
Ren, Zhiyi [1 ]
Deng, Zhang [1 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Peoples R China
[2] Hunan Univ, Key Lab Bldg Safety & Energy Efficiency, Minist Educ, Changsha 410082, Peoples R China
关键词
AutoBPS; shopping mall; model calibration; EnergyPlus; Monte Carlo; uncertainty analysis; CONSUMPTION; SIMULATION; STORAGE; SYSTEMS; CHINA;
D O I
10.3390/buildings13061427
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Building performance simulation can be used for retrofit analysis. However, it is time-consuming to create building energy models for existing buildings. This paper presented and implemented a rapid building energy modeling method for existing buildings by using prototype models and automatic model calibration for retrofit analysis with uncertainty. A shopping mall building located in Changsha, China, was selected as a case study to demonstrate the rapid modeling method. First, a toolkit named AutoBPS-Param was developed to generate building energy models with parameterized geometry data. A baseline EnergyPlus model was generated based on the building's basic information, including vintage, climate zone, total floor area, and percentage of each function type. Next, Monte Carlo sampling was applied to generate 1000 combinations for fourteen parameters. One thousand EnergyPlus models were created by modifying the baseline model with each parameter combination. Moreover, the 1000 simulation results were compared with the measured monthly electricity and natural gas usage data to find 29 calibrated solutions. Finally, the 29 calibrated energy models were used to evaluate the energy-saving potential of three energy conservation measures with uncertainty. The retrofit analysis results indicated that the electrical energy saving percentage of chiller replacement ranged from 1.57% to 13.51%, with an average of 8.27%. The energy-saving rate of lighting system replacement ranged from 1.92% to 11.66%, with an average of 6.43%. The energy-saving rate of window replacement ranges from 0.31% to 1.81%, with an average of 0.55%. The results showed that AutoBPS-Param could rapidly create building energy models for existing buildings and can be used for retrofit analysis after model calibration.
引用
收藏
页数:22
相关论文
共 50 条
  • [31] Calibration and uncertainty analysis of the SWAT model using Genetic Algorithms and Bayesian Model Averaging
    Zhang, Xuesong
    Srinivasan, Raghavan
    Bosch, David
    JOURNAL OF HYDROLOGY, 2009, 374 (3-4) : 307 - 317
  • [32] Optimization Tools for Building Energy Model Calibration
    Lara, Rigoberto Arambula
    Naboni, Emanuele
    Pernigotto, Giovanni
    Cappelletti, Francesca
    Zhang, Yi
    Barzon, Furio
    Gasparella, Andrea
    Romagnoni, Piercarlo
    8TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, SEB-16, 2017, 111 : 1060 - 1069
  • [33] Model calibration for building energy efficiency simulation
    Mustafaraj, Giorgio
    Marini, Dashamir
    Costa, Andrea
    Keane, Marcus
    APPLIED ENERGY, 2014, 130 : 72 - 85
  • [34] BUILDING AND CALIBRATION OF A FAST MODEL OF THE SWAY PROTOTYPE FLOATING WIND TURBINE
    Hao, Koh Jian
    Robertson, Amy N.
    Jonkman, Jason
    Driscoll, Frederick
    Ng, Eddie Y. K.
    2013 INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY RESEARCH AND APPLICATIONS (ICRERA), 2013, : 788 - 793
  • [35] Automatic generation of model for building energy management
    Quoc-Dung Ngo
    Hadj-Said, Yanis
    Ploix, Stephane
    Maulik, Ujjwal
    INTERNATIONAL JOURNAL OF ADVANCED COMPUTER SCIENCE AND APPLICATIONS, 2016, 7 (09) : 442 - 454
  • [36] Groundwater model diagnostic calibration and uncertainty analysis using information theory
    Khorshidi, Mohammad Sadegh
    Izady, Azizallah
    Al-Maktoumi, Ali
    Chen, Mingjie
    Nikoo, Mohammad Reza
    Gandomi, Amir H.
    HYDROLOGICAL SCIENCES JOURNAL, 2024, 69 (07) : 878 - 890
  • [37] Automatic model calibration for coupled HVAC and building dynamics using Modelica and Bayesian optimization
    Martinez-Viol, Victor
    Urbano, Eva M.
    Delgado-Prieto, Miguel
    Romeral, Luis
    BUILDING AND ENVIRONMENT, 2022, 226
  • [38] Automatic model calibration for coupled HVAC and building dynamics using Modelica and Bayesian optimization
    Martinez-Viol, Victor
    Urbano, Eva M.
    Delgado-Prieto, Miguel
    Romeral, Luis
    Building and Environment, 2022, 226
  • [39] Model calibration and uncertainty analysis in signaling networks
    Heinemann, Tim
    Raue, Andreas
    CURRENT OPINION IN BIOTECHNOLOGY, 2016, 39 : 143 - 149
  • [40] Uncertainty-based automatic calibration of HEC-HMS model using sequential uncertainty fitting approach
    Mousavi, S. Jamshid
    Abbaspour, K. C.
    Kamali, B.
    Amini, M.
    Yang, H.
    JOURNAL OF HYDROINFORMATICS, 2012, 14 (02) : 286 - 309