A Novel Method to Estimate the System Damping After Generator Tripping

被引:0
|
作者
Bin, Zi-Jun [1 ]
Liu, Yun [2 ]
Hao, Si-Peng [2 ]
Zhu, Xin-Yao [1 ]
Kong, Xiang-Ping [1 ]
Wang, Ming-Shen [1 ]
机构
[1] State Grid Jiangsu Elect Power Co Ltd, Elect Power Res Inst, Nanjing, Peoples R China
[2] Nanjing Inst Technol, Sch Elect Power Engn, Nanjing, Peoples R China
关键词
Generator tripping; System damping; Virtual equilibrium point; Inertia equivalence; Dynamic stability; PREDICTION;
D O I
10.1007/s42835-022-01261-6
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Generator tripping strategies are generally decided by offline transient stability analysis. However, traditional methods can hardly ensure dynamic stability after GT. Simulation tests show that GT strategies change the topology and the state variables of a power system, which may weaken the system damping after GT. In order to estimate the system damping, this paper proposes a time-varying linearized model under unsteady states based on the virtual equilibrium point (VEP) theory. Then, the changes in dynamic characteristics caused by GT can be represented by the eigenvalues at VEPs before and after GT. An inertia equivalence system is mathematically formulated to analyze the effects of generator inertia, damping ratio, and controllers. Two indices are designed to estimate the system damping changes. Based on the indices, a framework is proposed to improve the current GT strategy decision-making system. The sensitivity analysis and the fault scanning verify the effectiveness and robustness of the proposed method and indices.
引用
收藏
页码:843 / 855
页数:13
相关论文
共 50 条
  • [21] Generator damping evaluation method based on oscillation energy consumption
    Zhu H.
    Ye H.
    Gao L.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (24): : 41 - 50
  • [22] Design Method for Improving Damping Characteristics of Virtual Synchronous Generator
    Ma Y.
    Yang H.
    Qu Z.
    Xin H.
    Han J.
    Yang, Huan (yanghuan@zju.edu.cn), 1600, Power System Technology Press (45): : 269 - 275
  • [23] Real-time power system generator tripping control based on deep reinforcement learning
    Lin, Bilin
    Wang, Huaiyuan
    Zhang, Yang
    Wen, Buying
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 141
  • [24] Novel control method of PAPF for resonance damping and harmonics compensation in power system
    School of Electrical Engineer, Xi'an Jiaotong University, Xi'an 710049, China
    Zhongguo Dianji Gongcheng Xuebao, 2008, 27 (70-77):
  • [25] A Novel Control Method of PAPF for Harmonics Compensation and Resonance Damping in Power System
    Wu Longhui
    Zhuo Fang
    Zhang Pengbo
    Li Hui
    Wang Zhaoan
    2008 IEEE POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-10, 2008, : 2023 - 2029
  • [26] Behavior Analysis of the Nonuniform Damping and Screening System in the HTS Generator
    Zhang, Wenfeng
    Xia, Dong
    Zhang, Dong
    IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (11)
  • [27] A Novel Method for Azimuth Estimate of Ultra Short Base Line Positioning System
    Zhang, Jucheng
    Sun, Dajun
    Han, Yunfeng
    MEASUREMENT TECHNOLOGY AND ENGINEERING RESEARCHES IN INDUSTRY, PTS 1-3, 2013, 333-335 : 343 - 347
  • [28] Strategy of emergency generator tripping control for transient stability after a large capacity HVDC blocking fault
    Xiang Y.
    Wang T.
    Li C.
    Wang Z.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2021, 49 (15): : 84 - 92
  • [29] A method research based on acceleration unbalance power fast estimation of generator tripping sensitive spot search
    Liu Ying
    Xu Wei-ting
    Tang Quan
    Feng Han
    PROCEEDINGS OF THE 2015 4TH NATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS AND COMPUTER ENGINEERING ( NCEECE 2015), 2016, 47 : 773 - 780
  • [30] A NOVEL METHOD TO ESTIMATE THE RFI ENVIRONMENT
    Chen, David D.
    Ruf, Chris
    2014 IEEE INTERNATIONAL GEOSCIENCE AND REMOTE SENSING SYMPOSIUM (IGARSS), 2014,