Effect of stagnation period and flow rate on soluble and particulate Pb leaching in copper pipe water distribution systems

被引:0
|
作者
Chang, Lu [1 ]
Lee, Joseph H. W. [2 ]
机构
[1] Beijing Normal Univ, Sch Environm, State Key Lab Water Environm Simulat, Beijing 100875, Peoples R China
[2] Macau Univ Sci & Technol, Macao Environm Res Inst, Taipa, Macao, Peoples R China
关键词
Lead in drinking water; Copper water distribution system; Particulates contaminants; Sequential sampling; Stagnation time; Flow rate; DRINKING-WATER; LEAD RELEASE; CORROSION; EXPOSURE; BUILDINGS; PARTICLES; CHEMISTRY;
D O I
10.1016/j.jher.2023.06.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Extremely high lead level in tap water caused by particulates has attracted increasing attention in recent years. Despite extensive research on the role of particulate Pb in water supply systems with lead service lines, little information is available on the role of particulate Pb in copper (Cu) water distribution systems. In this study, the dissolved, colloidal, and particulate lead and copper concentrations in representative prototype copper pipe water distribution systems with leaded solder joints and brass fixtures are measured. The effects of flow rate and stagnation time on metal fractionation are investigated. For each experimental scenario, all the water that stagnated inside the system is sampled to have a comprehensive understanding of lead contamination. Sampled at flow rates of 200-250 mL/s, the soluble lead and copper make up 60-96 % of the total concentration in the samples after hours of stagnation. More than half of the Pb and Cu particles are larger than 0.8 & mu;m. Higher flow rates result in substantial increases in particulate metal concentrations but have no apparent effect on dissolved metals. The soluble and particulate copper concentrations (. 100-250 & mu;g/L) both increase with stagnation time. For the case of Pb, while the particulate concentration increases (up to . 40 & mu;g/L after 12 h), the soluble concentration does not change significantly beyond 4 h; this can be attributed to the different solubilities of Pb (. 20 & mu;g/L) and Cu (. 200 & mu;g/L) in tap water. The results also show that particulates suspended by clean "once through" water (without prior stagnation) can lead to high levels of Pb contamination (> 10 & mu;g/L).
引用
收藏
页码:1 / 9
页数:9
相关论文
共 39 条
  • [1] Effects of pipeline geometry, sample volume, and flow rate on pb monitoring outcomes in copper pipe drinking water supply systems
    Chang, Lu
    WATER RESEARCH, 2022, 222
  • [2] Effect of irrigation rate and air flow rate on temperature distribution of secondary copper sulfide during bio-heap leaching process
    Li, Hong-Xu
    Li, An
    Wu, Ai-Xiang
    Qiu, Guan-Zhou
    Zhongguo Youse Jinshu Xuebao/Chinese Journal of Nonferrous Metals, 2010, 20 (07): : 1424 - 1432
  • [3] Flow-induced failure mechanisms of copper pipe in potable water systems
    Roy, Siddhartha
    Coyne, Jeffrey M.
    Novak, Julia A.
    Edwards, Marc A.
    CORROSION REVIEWS, 2018, 36 (05) : 449 - 481
  • [4] Unsteady state flow and stagnation in distribution systems affect the biological stability of drinking water
    Manuel, C. M.
    Nunes, O. C.
    Melo, L. F.
    BIOFOULING, 2010, 26 (02) : 129 - 139
  • [5] Effect of flow fluctuation on water pollution in drinking water distribution systems
    Xin, Changchun
    Khu, Soon-Thiam
    Wang, Tianzhi
    Zuo, Xin
    Zhang, Ying
    ENVIRONMENTAL RESEARCH, 2024, 246
  • [6] Effect of Flow Rate and Lead/Copper Pipe Sequence on Lead Release from Service Lines
    Cartier, Clement
    Arnold, Roger B., Jr.
    Triantafyllidou, Simoni
    Prevost, Michele
    Edwards, Marc
    WATER RESEARCH, 2012, 46 (13) : 4142 - 4152
  • [7] Analysis of the damping effect of leakage in water pipe systems for different flow conditions
    Melo, N.
    Ramos, H. M.
    INTEGRATING WATER SYSTEMS, 2010, : 563 - +
  • [8] Effect of Pipe Size and Location on Water-Main Head Loss in Water Distribution Systems
    Hashemi, Saeed
    Filion, Yves
    Speight, Vanessa
    Long, Andrew
    JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2020, 146 (06)
  • [9] Prediction of lead leaching from galvanic corrosion of lead-containing components in copper pipe drinking water supply systems
    Chang, Lu
    Lee, Joseph H. W.
    Fung, Y. S.
    JOURNAL OF HAZARDOUS MATERIALS, 2022, 436
  • [10] Effect of Particle Concentration and Pipe Materials on the Formation of Biofilms in Drinking Water Distribution Systems
    Zhao, Zhiling
    Zhang, Yongji
    Wang, Lu
    Shi, Wenhang
    WATER, 2022, 14 (02)