Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170

被引:9
|
作者
Tan, Haihui [1 ]
Xu, Lingfei [2 ]
Yang, Linlin [2 ]
Bai, Minkai [3 ]
Liu, Zhan [3 ,4 ]
机构
[1] Univ Elect Sci & Technol China, Zhongshan Inst, Sch Mech & Elect Engn, Zhongshan 528400, Peoples R China
[2] Zhongshan Candor Elect Appliances Co Ltd, Zhongshan 528427, Peoples R China
[3] China Univ Min & Technol, Dept Bldg Environm & Energy Engn, Sch Mech & Civil Engn, Xuzhou 221116, Jiangsu, Peoples R China
[4] Lund Univ, Dept Energy Sci, Fac Engn, S-22100 Lund, Sweden
关键词
Cascade refrigeration system; Natural refrigerants R290-R170; Ultralow-temperature; Experimental measure; THERMODYNAMIC ANALYSIS; SYSTEM; ENERGY; OPTIMIZATION;
D O I
10.1007/s11356-022-24310-z
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present study, the operation performance of an ultralow-temperature cascade refrigeration freezer is experimentally researched. The natural refrigerants R290-R170 are adopted as high-temperature and low-temperature fluids. The experimental test is conducted in a type laboratory with a dry bulb temperature of 32.0 degrees C and a wet bulb temperature of 26.5 degrees C. Different state monitors are set to display the system operation performance, and several temperature monitors are arranged to study the pull-down performance and temperature variations in the freezer. Based on the established experimental rig, three freezing temperatures, including - 40 degrees C, - 80 degrees C, and - 86 degrees C, are measured and compared. The results show that it takes about 240 min for the freezer to be pulled down to - 80 degrees C. During the pull-down period, different monitors all experience rapid temperature drop, and the power consumption reduces from 1461.4 W to 997.5 W. Once the target temperature is achieved, the freezer comes into periodic start-stop operation. With the set temperature ranging from - 40 degrees C to - 86 degrees C, the inlet temperature of two compressors gradually decreases, while the discharge temperature has an increase trend. The cooling effect of the pre-cooled condenser reduces with the freezing temperature, while the long connection pipe has opposite variation profile. Moreover, it is observed that for different freezing temperatures, most of the space in the freezer can be cooled down to the target temperature. It is confirmed that the present ultralow-temperature freezer can be used for the storage and transportation of COVID-19 vaccines. However, it is also found that the cascade refrigeration system is not suitable for high freezing temperature, due to high power consumption and extensive start-stop switch of refrigeration system.
引用
收藏
页码:29790 / 29806
页数:17
相关论文
共 40 条
  • [31] Performance comparison of ultra-low temperature cascade refrigeration cycles using R717/R170, R717/R41 and R717/R1150 to replace R404A/R23
    Chen, Muqing
    Yang, Qichao
    Shi, Benlin
    Chen, Xiaonan
    Chi, Weikai
    Liu, Guangbin
    Zhao, Yuanyang
    Li, Liansheng
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 44
  • [32] Theoretical investigation on the performance of R600/R170/R14/R50 four stage regenerator-enhanced auto cascade refrigeration system
    He, Yongning
    Wang, Su'ao
    Cao, Wenliang
    Wu, Huihong
    Wu, Xuehong
    Xing, Linfen
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2025, 174 : 14 - 22
  • [33] Investigation of environmentally friendly new generation refrigerant R471A instead of R404A in low and medium temperature commercial refrigeration system
    Yildirim, Ragip
    Sahin, Arzu Sencan
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2024, 149 (12) : 6307 - 6317
  • [34] Energy assessment and environmental impact analysis of an R134a/R744 cascade refrigeration plant upgraded with the low-GWP refrigerants R152a, R1234ze(E), propane (R290) and propylene (R1270)
    Sanchez, D.
    Cabello, R.
    Llopis, R.
    Catalan-Gil, J.
    Nebot-Andres, L.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 321 - 334
  • [35] Thermodynamic analysis of auto-cascade refrigeration cycles, with and without ejector, for ultra low temperature freezing using a mixture of refrigerants R600a and R1150
    Angel Rodriguez-Jara, Enrique
    Jose Sanchez-de-la-Flor, Francisco
    Antonio Exposito-Carrillo, Jose
    Manuel Salmeron-Lissen, Jose
    APPLIED THERMAL ENGINEERING, 2022, 200
  • [36] Energy, exergy and economical analysis of N2O based cascade refrigeration system for ultralow temperature cooling applications using different eco-friendly refrigerants in high temperature cycle
    Kumar, Sachin
    Gahlot, Pardeep
    Kumar, Suresh
    RESULTS IN ENGINEERING, 2024, 22
  • [37] Theoretical analysis of three CO2/C3H8 (R744-R290) cascade refrigeration systems with precooling processes in low-temperature circuits
    Li, Ruishen
    Ye, Fen
    Zhang, Jili
    Wang, Meng
    Li, Kun
    APPLIED THERMAL ENGINEERING, 2023, 234
  • [38] Thermodynamic Analysis of Comprehensive Performance of Carbon Dioxide(R744) and Its Mixture With Ethane(R170) Used in Refrigeration and Heating System at Low Evaporation Temperature
    Sun, Dahan
    Liu, Zhongyan
    Zhang, Hao
    Zhang, Xin
    Qin, Jiang
    ASME Open Journal of Engineering, 2024, 3
  • [39] An investigation to identify the performance of cascade refrigeration system by adopting high-temperature circuit refrigerant R1233zd(E) over R161
    Patel V.K.
    Raja B.D.
    Prajapati P.
    Parmar L.
    Jouhara H.
    International Journal of Thermofluids, 2023, 17
  • [40] Thermodynamic performance of the fractionated auto-cascade refrigeration cycle coupled with two-phase ejector using R1150/R600a at-80 °C temperature level
    Tan, Yingying
    Li, Xiuzhen
    Wang, Lin
    Huang, Lisheng
    Xiao, Yi
    Wang, Zhanwei
    Li, Shaoqiang
    ENERGY, 2023, 281