Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170

被引:7
|
作者
Tan, Haihui [1 ]
Xu, Lingfei [2 ]
Yang, Linlin [2 ]
Bai, Minkai [3 ]
Liu, Zhan [3 ,4 ]
机构
[1] Univ Elect Sci & Technol China, Zhongshan Inst, Sch Mech & Elect Engn, Zhongshan 528400, Peoples R China
[2] Zhongshan Candor Elect Appliances Co Ltd, Zhongshan 528427, Peoples R China
[3] China Univ Min & Technol, Dept Bldg Environm & Energy Engn, Sch Mech & Civil Engn, Xuzhou 221116, Jiangsu, Peoples R China
[4] Lund Univ, Dept Energy Sci, Fac Engn, S-22100 Lund, Sweden
关键词
Cascade refrigeration system; Natural refrigerants R290-R170; Ultralow-temperature; Experimental measure; THERMODYNAMIC ANALYSIS; SYSTEM; ENERGY; OPTIMIZATION;
D O I
10.1007/s11356-022-24310-z
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present study, the operation performance of an ultralow-temperature cascade refrigeration freezer is experimentally researched. The natural refrigerants R290-R170 are adopted as high-temperature and low-temperature fluids. The experimental test is conducted in a type laboratory with a dry bulb temperature of 32.0 degrees C and a wet bulb temperature of 26.5 degrees C. Different state monitors are set to display the system operation performance, and several temperature monitors are arranged to study the pull-down performance and temperature variations in the freezer. Based on the established experimental rig, three freezing temperatures, including - 40 degrees C, - 80 degrees C, and - 86 degrees C, are measured and compared. The results show that it takes about 240 min for the freezer to be pulled down to - 80 degrees C. During the pull-down period, different monitors all experience rapid temperature drop, and the power consumption reduces from 1461.4 W to 997.5 W. Once the target temperature is achieved, the freezer comes into periodic start-stop operation. With the set temperature ranging from - 40 degrees C to - 86 degrees C, the inlet temperature of two compressors gradually decreases, while the discharge temperature has an increase trend. The cooling effect of the pre-cooled condenser reduces with the freezing temperature, while the long connection pipe has opposite variation profile. Moreover, it is observed that for different freezing temperatures, most of the space in the freezer can be cooled down to the target temperature. It is confirmed that the present ultralow-temperature freezer can be used for the storage and transportation of COVID-19 vaccines. However, it is also found that the cascade refrigeration system is not suitable for high freezing temperature, due to high power consumption and extensive start-stop switch of refrigeration system.
引用
收藏
页码:29790 / 29806
页数:17
相关论文
共 33 条
  • [1] Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170
    Haihui Tan
    Lingfei Xu
    Linlin Yang
    Minkai Bai
    Zhan Liu
    [J]. Environmental Science and Pollution Research, 2023, 30 : 29790 - 29806
  • [2] An ultralow-temperature cascade refrigeration unit with natural refrigerant pair R290-R170: Performance evaluation under different ambient and freezing temperatures
    Liu, Zhan
    Ji, Shenrui
    Tan, Haihui
    Yang, Danan
    Cao, Zhen
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2023, 46
  • [3] Experimental study on a -86 °C cascade refrigeration unit with environmental-friendly refrigerants R290-R170
    Zhan Liu
    Kaifeng Yuan
    Yunzhi Ling
    Haihui Tan
    Shuo Yang
    [J]. Environmental Science and Pollution Research, 2023, 30 : 97339 - 97352
  • [4] Experimental study on a-86 °C cascade refrigeration unit with environmental-friendly refrigerants R290-R170
    Liu, Zhan
    Yuan, Kaifeng
    Ling, Yunzhi
    Tan, Haihui
    Yang, Shuo
    [J]. ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2023, 30 (43) : 97339 - 97352
  • [5] Experimental test on the performance of a -80 °C cascade refrigeration unit using refrigerants R290-R170 for COVID-19 vaccines storage
    Liu, Zhan
    Bai, Minkai
    Tan, Haihui
    Ling, Yunzhi
    Cao, Zhen
    [J]. JOURNAL OF BUILDING ENGINEERING, 2023, 63
  • [6] Cascade refrigeration system with environment friendly refrigerants as R290 and ammonia
    Raibhole, V.N.
    Kamble, D.A.
    [J]. International Journal of Environmental Engineering, 2022, 11 (04): : 261 - 276
  • [7] Performance evaluation of an ejector subcooling refrigeration cycle with zeotropic mixture R290/R170 for low-temperature freezer applications
    Liu, Ye
    Yu, Jianlin
    [J]. APPLIED THERMAL ENGINEERING, 2019, 161
  • [8] Performance of R170 mixtures as refrigerants for refrigeration at-80 °C temperature range
    Gong, Maoqiong
    Sun, Zhaohu
    Wu, Jianfeng
    Zhang, Yu
    Meng, Chong
    Zhou, Yuan
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (05): : 892 - 900
  • [9] Investigation of R290/R170 substituting R22/R23 in cascade refrigeration cycle
    Xie, Y. B.
    Liu, Ch T.
    Lun, L. Y.
    Zhang, X. D.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 509 - 513
  • [10] Experimental research on a Joule-Thomson refrigeration cycle with mixture R170/R290 for 60 °C low-temperature freezer
    Bai, Tao
    Li, Dawei
    Xie, Hongxu
    Yan, Gang
    Yu, Jianlin
    [J]. APPLIED THERMAL ENGINEERING, 2021, 186