A numerical study on performance efficiency of a low-temperature horizontal ground-source heat pump system

被引:4
|
作者
Gao, Wu [1 ]
Masum, Shakil [1 ]
Qadrdan, Meysam [1 ]
Thomas, Hywel Rhys [1 ]
机构
[1] Cardiff Univ, Sch Engn, Queens Bldg, Cardiff CF24 3AA, Wales
基金
英国工程与自然科学研究理事会;
关键词
Horizontal ground -source heat pump system; Performance efficiency; Ground temperature; Fluid temperature; Coefficient of performance; District heating and cooling network; COUPLED HEAT; THERMAL PERFORMANCE; NEURAL-NETWORKS; ENERGY-BALANCE; SIMULATION; EXCHANGER; SURFACE; MODEL; FIELD; CONDUCTIVITY;
D O I
10.1016/j.enbuild.2023.113137
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Exploitation of shallow ground and its low-grade heat potential is fundamental to designing 5th generation district heating and cooling (DHC) networks. Horizontal ground-source heat pump (HGSHP) systems are a common way to utilize shallow geothermal energy. Realistic estimation and prediction of performance of a HGSHP system and shallow ground thermal behaviour should consider the whole system including building heating and cooling load, heat pump and ground heat exchanger, and the ground. This should be accompanied by realistic atmospheric and ground conditions. In this paper, a three-dimensional coupled thermal-hydraulic model with realistic boundary conditions adopting a whole system approach is presented. Dynamic heat pump coefficient of performance (COP) that depends on seasonal variation of heating/cooling demand and ground conditions are also considered. Model validations are conducted against experimental and analytical results in literatures. The model is applied for evaluating a HGSHP system to support development of a 5th generation DHC network on a potential site in the UK. Several influencing factors, such as ground moisture transfer, building thermal load mode, buried depth of ground loops, and initial ground temperature profile are studied to assess performance efficiency of the HGSHP system and evolution of ground thermal behaviour in response to heat extraction or rejection into the ground. The results show that 5% of the monthly total heat demand of the site could be met by the designed HGSHP system, consisting of 200 U-shaped ground loops buried at the depth of 3 m and pure water as the heat carrier. Overlooking the ground moisture transfer or hyperbolizing the ground saturation would overestimate the load-carrying capacity of the HGSHP system. The HGSHP system is more efficient with a higher heat pump COP under the heating and cooling mode than under the heating-only mode. Predicted performance of the HGSHP system improves with buried depth of the ground loops. The results also show that a 1 celcius increase in the undisturbed ground temperature could suffice up to 8% of the monthly total heat demand of the site.
引用
收藏
页数:19
相关论文
共 50 条
  • [1] Experimental thermal performance evaluation of a horizontal ground-source heat pump system
    Inalli, M
    Esen, H
    [J]. APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) : 2219 - 2232
  • [2] Performance prediction of a hybrid solar ground-source heat pump system
    Wang, Enyu
    Fung, Alan S.
    Qi, Chengying
    Leong, Wey H.
    [J]. ENERGY AND BUILDINGS, 2012, 47 : 600 - 611
  • [3] Exergetic performance assessment of a ground-source heat pump drying system
    Kuzgunkaya, Ebru Hancioglu
    Hepbasli, Arif
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2007, 31 (08) : 760 - 777
  • [4] Theoretical study on the performance of an integrated ground-source heat pump system in a whole year
    Fan, Rui
    Jiang, Yiqiang
    Yao, Yang
    Ma, Zuiliang
    [J]. ENERGY, 2008, 33 (11) : 1671 - 1679
  • [5] A numerical study on heat transfer performances of horizontal ground heat exchangers in ground-source heat pumps
    Zou, Hang
    Pei, Peng
    Wang, Chen
    Hao, Dingyi
    [J]. PLOS ONE, 2021, 16 (05):
  • [6] IMPACT OF THE GROUND-SOURCE HEAT PUMP RUNNING TIME DURATION ON THE SYSTEM EFFICIENCY
    Soldo, V.
    Rusevljan, M.
    Grozdek, M.
    Curko, T.
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 3649 - 3655
  • [7] Study on Hybrid Solar Energy and Ground-Source Heat Pump System
    Liu Yi
    Li Bing-xi
    Zhou Yi
    Fu Zhong-bin
    Xu Xin-hai
    [J]. ICEET: 2009 INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT TECHNOLOGY, VOL 1, PROCEEDINGS, 2009, : 845 - 848
  • [8] Energy performances of a ground-source heat pump system
    Minea, V
    [J]. RESEARCH, DESIGN AND CONSTRUCTION OF REFRIGERATION AND AIR CONDITIONING EQUIPMENTS IN EASTERN EUROPEAN COUNTRIES, 1996, : 116 - 125
  • [9] Heat transfer characteristics and Loading Performance of ground-source heat pump system pile
    Zhang, Mengyu
    Zhou, Wanqing
    Gao, Fengqi
    [J]. RESEARCH ON MECHANICAL ENGINEERING, CIVIL ENGINEERING AND MATERIAL ENGINEERING, 2014, 454 : 190 - 193
  • [10] Thermal performance analysis of ground source heat pump system for low-temperature waste heat recovery storage
    Wang, Songqing
    Qu, Rongyan
    Zhang, Xuedan
    Li, Yitong
    Chen, Jingya
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2022, 35