Wideband Synchronous Measurement-Based Detection and Location of High Impedance Fault for Resonant Distribution Systems With Integration of DERs

被引:13
|
作者
Wei, Mingjie [1 ]
Shi, Fang [1 ]
Zhang, Hengxu [1 ]
Chen, Weijiang [2 ]
机构
[1] Shandong Univ, Key Lab Power Syst Intelligent Dispatch & Control, Minist Educ, Jinan 250061, Peoples R China
[2] State Grid Corp China, Beijing 100031, Peoples R China
关键词
Harmonic analysis; Circuit faults; Resistance; Impedance; Feature extraction; Transformers; Wideband; DER; resonant distribution system; high impedance fault; fault detection; fault location; nonlinearity; DISTRIBUTION NETWORKS; SINGLE-PHASE; ADMITTANCE;
D O I
10.1109/TSG.2022.3199781
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The increasing integration of distributed energy resources (DERs) into the distribution system has caused interference with the signals stimulated by high impedance faults (HIFs). Many existing HIF detection or location methods that are only based on the superficial nonlinearity features of signals rather than the deep laws, will become invalid. This paper proposes a detection and location scheme for HIFs by theoretically analyzing the relationships between signals and systems. By establishing the equivalent circuit of a resonant distribution system, an online method to calculate the kernel system parameters is proposed, based on which an adaptive criterion for HIF detection is provided. In this way, the ability to detect HIF is adequately exploited and independent of DER influences. The method is able to detect HIF over 8.5 k Omega under common operating conditions. Furthermore, the nonlinearity of HIF is analyzed by deriving laws about how wideband signals distribute in the system. The 3rd harmonic component of zero-sequence signals is proved to be superior in HIF location in terms of signal content and discrimination, which is also demonstrated to be valid under the influence of DER harmonic injection. On this basis, a HIF location method utilizing the 3rd harmonic zero-sequence signals is proposed. The effectiveness of the method and its robustness to the DER interference are validated by simulated and field HIFs in 10kV systems.
引用
收藏
页码:1117 / 1134
页数:18
相关论文
共 50 条
  • [31] PSD based high impedance fault detection and classification in distribution system
    Roy, Subhamita
    Debnath, Sudipta
    MEASUREMENT, 2021, 169
  • [32] Impedance-Based Fault Location Technique for Distribution Systems in Presence of Distributed Generation
    Abo-Shady, F. M.
    Alaam, M. A.
    Azmy, Ahmed M.
    2013 IEEE INTERNATIONAL CONFERENCE ON SMART ENERGY GRID ENGINEERING (SEGE), 2013,
  • [33] Fault location algorithm for distribution systems with distributed generation based on impedance and metaheuristic methods
    Pessoa, Andre Luis da Silva
    Oleskovicz, Mario
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 225
  • [34] Extended Impedance-Based Fault Location Formulation for Unbalanced Underground Distribution Systems
    Filomena, Andre D.
    Resener, Mariana
    Salim, Rodrigo H.
    Bretas, Arturo S.
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 4217 - 4224
  • [35] High-impedance Fault Detection Method Based on Feature Extraction and Synchronous Data Divergence Discrimination in Distribution Networks
    Liu, Yang
    Zhao, Yanlei
    Wang, Lei
    Fang, Chen
    Xie, Bangpeng
    Cui, Laixi
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2023, 11 (04) : 1235 - 1246
  • [36] High-impedance Fault Detection Method Based on Feature Extraction and Synchronous Data Divergence Discrimination in Distribution Networks
    Yang Liu
    Yanlei Zhao
    Lei Wang
    Chen Fang
    Bangpeng Xie
    Laixi Cui
    JournalofModernPowerSystemsandCleanEnergy, 2023, 11 (04) : 1235 - 1246
  • [37] Analysis of Signal Processing Techniques for High Impedance Fault Detection in Distribution Systems
    Lopes, Gabriela Nunes
    Lacerda, Vinicius Albernaz
    Vieira, Jose Carlos Melo
    Coury, Denis Vinicius
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (06) : 3438 - 3447
  • [38] Fire hazard mitigation in distribution systems through high impedance fault detection
    Gashteroodkhani O.A.
    Majidi M.
    Etezadi-Amoli M.
    Electric Power Systems Research, 2021, 192
  • [39] A Novel High Impedance Fault Detection Technique in Distribution Systems With Distributed Generators
    Nayak, Paresh Kumar
    Sarwagya, Kumari
    Biswal, Tapaswini
    2016 NATIONAL POWER SYSTEMS CONFERENCE (NPSC), 2016,
  • [40] Detection of High Impedance Fault in Power Distribution Systems Using Mathematical Morphology
    Gautam, Suresh
    Brahma, Sukumar M.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1226 - 1234