Insulation evaluation of MV underground cable with partial discharge and dielectric dissipation factor measurements

被引:7
|
作者
Arikan, Oktay [1 ]
Uydur, Cihat Cagdas [2 ]
Kumru, Celal Fadil [3 ]
机构
[1] Yildiz Tech Univ, Dept Elect Engn, Istanbul, Turkiye
[2] Trakya Univ, Tech Sci Vocat Sch, Edirne, Turkiye
[3] Suleyman Demirel Univ, Dept Elect Elect Engn, Isparta, Turkiye
关键词
Diagnosis procedure; Dissipation factor; Electrical stresses; Partial discharge; Operation of XLPE cable; LOW-FREQUENCY; KV XLPE; VOLTAGE; VLF;
D O I
10.1016/j.epsr.2023.109338
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As it is known overvoltage and impulse voltage are the most common stresses that cables are exposed to in practice. Since the occurrence frequency, duration and amplitude of these two stresses are different, their deteriorating effects on the cable insulation also differ. At this point, it is necessary to know how sensitively the preferred dielectric diagnosis method can detect the deteriorations on cable insulation. Since it is not technically possible to detect all isolation errors with a single preferred diagnostic method, the methods must be used together in a certain procedure. In this study, 12/20.8 kV, XLPE insulated Cable Samples were artificially aged using 50 aging cycles of overvoltage (36 kV and 60 kV) and 50 kV, standard positive impulse voltage. After each aging cycle, dielectric performance of cable insulation was measured using partial discharge (PD) and dielectric dissipation factor (DDF) methods. The accuracy of dielectric diagnosis methods due to overvoltage and impulse voltage are analyzed and discussed based on the measurement results. In order to analyze dielectric diagnostic performances of the methods, both individual trends and the correlation between PD and DDF parameters during overvoltage and impulse voltage aging processes were shared. As a result, it was found that diagnostic perfor-mances of PD and DDF methods differ according to the amplitude and waveform of the applied electrical stress. Therefore, a dielectric diagnosis procedure for MV cables including both PD and DDF methods to improve diagnostic process in field applications was proposed. In this context, the use of the proposed diagnosis procedure will contribute to the evaluation of the findings resulting from the diagnostic methods during the operation of MV cables.
引用
收藏
页数:12
相关论文
共 50 条
  • [21] Methods of Characterisation of DC Partial Discharge in Polymeric Cable Insulation
    Morris, Euan A.
    Siew, W. H.
    Given, Martin J.
    [J]. 2018 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP), 2018, : 494 - 497
  • [22] Localization of partial discharge sources along HV and MV cable routes
    Puletti, F.
    Olivieri, M.
    Cavallini, A.
    Montanari, G. C.
    [J]. IPEC: 2005 International Power Engineering Conference, Vols 1 and 2, 2005, : 194 - 199
  • [23] Multi-end Partial Discharge Location Algorithm based on Trimmed Mean Data Filtering Technique for MV Underground Cable
    Yii, C. C.
    Rohani, M. N. K. H.
    Isa, M.
    Hassan, S. I. S.
    Ismail, B.
    Hussin, N.
    [J]. 2015 IEEE STUDENT CONFERENCE ON RESEARCH AND DEVELOPMENT (SCORED), 2015, : 345 - 350
  • [24] Cable Insulation Fault Identification Using Partial Discharge Patterns Analysis
    Abu-Rub, Omar H.
    Khan, Qasim
    Refaat, Shady S.
    Nounou, Hazem
    [J]. IEEE CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, 2022, 45 (01): : 31 - 41
  • [25] A COMPARISON OF AC AND DC PARTIAL DISCHARGE ACTIVITY IN POLYMERIC CABLE INSULATION
    Morris, E. A.
    Siew, W. H.
    [J]. 2017 IEEE 21ST INTERNATIONAL CONFERENCE ON PULSED POWER (PPC), 2017,
  • [26] Experimental Studies on the Partial Discharge of Insulation for High Tc Superconducting Cable
    Liwei Jing
    Yuping Teng
    Jingye Zhang
    Dong Zhang
    Qingquan Qiu
    Wenju Sang
    Guomin Zhang
    Liye Xiao
    [J]. Journal of Superconductivity and Novel Magnetism, 2020, 33 : 2615 - 2620
  • [27] On-line partial discharge monitoring for assessment of power cable insulation
    Blackburn, TR
    Phung, BT
    Hao, Z
    [J]. PROCEEDINGS OF THE 2005 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, VOLS, 1-3, 2005, : 865 - 868
  • [28] An Interpretation Approach for in Field Measured Dissipation Factor Values of MV Cable Lines
    Freitag, Christian
    Mladenovic, Ivana
    Weindl, Christian
    [J]. PROCEEDINGS OF THE 2013 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2013), VOLS 1 AND 2, 2013, : 96 - 99
  • [29] Modeling and Investigation of Insulation Defects by Partial Discharge in HV XLPE Cable
    Kalla, Ujjwal Kumar
    Adhikari, Neha
    Rustagi, Ashish
    [J]. 2018 8TH IEEE INDIA INTERNATIONAL CONFERENCE ON POWER ELECTRONICS (IICPE), 2018,
  • [30] Partial discharge on-line measures in cable's EPR insulation
    Candela, R
    Sanseverino, ER
    Romano, P
    [J]. 2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 470 - 473