Insulation evaluation of MV underground cable with partial discharge and dielectric dissipation factor measurements

被引:7
|
作者
Arikan, Oktay [1 ]
Uydur, Cihat Cagdas [2 ]
Kumru, Celal Fadil [3 ]
机构
[1] Yildiz Tech Univ, Dept Elect Engn, Istanbul, Turkiye
[2] Trakya Univ, Tech Sci Vocat Sch, Edirne, Turkiye
[3] Suleyman Demirel Univ, Dept Elect Elect Engn, Isparta, Turkiye
关键词
Diagnosis procedure; Dissipation factor; Electrical stresses; Partial discharge; Operation of XLPE cable; LOW-FREQUENCY; KV XLPE; VOLTAGE; VLF;
D O I
10.1016/j.epsr.2023.109338
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As it is known overvoltage and impulse voltage are the most common stresses that cables are exposed to in practice. Since the occurrence frequency, duration and amplitude of these two stresses are different, their deteriorating effects on the cable insulation also differ. At this point, it is necessary to know how sensitively the preferred dielectric diagnosis method can detect the deteriorations on cable insulation. Since it is not technically possible to detect all isolation errors with a single preferred diagnostic method, the methods must be used together in a certain procedure. In this study, 12/20.8 kV, XLPE insulated Cable Samples were artificially aged using 50 aging cycles of overvoltage (36 kV and 60 kV) and 50 kV, standard positive impulse voltage. After each aging cycle, dielectric performance of cable insulation was measured using partial discharge (PD) and dielectric dissipation factor (DDF) methods. The accuracy of dielectric diagnosis methods due to overvoltage and impulse voltage are analyzed and discussed based on the measurement results. In order to analyze dielectric diagnostic performances of the methods, both individual trends and the correlation between PD and DDF parameters during overvoltage and impulse voltage aging processes were shared. As a result, it was found that diagnostic perfor-mances of PD and DDF methods differ according to the amplitude and waveform of the applied electrical stress. Therefore, a dielectric diagnosis procedure for MV cables including both PD and DDF methods to improve diagnostic process in field applications was proposed. In this context, the use of the proposed diagnosis procedure will contribute to the evaluation of the findings resulting from the diagnostic methods during the operation of MV cables.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Experience with partial discharge, dissipation factor and recovery voltage measurements for the evaluation of insulation systems of high voltage rotating machines
    Farahani, M
    Borsi, H
    Gockenbach, E
    [J]. 2002 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2002, : 454 - 457
  • [2] Frequency Dielectric Spectroscopy and Dissipation Factor Measurements during Thermal Cycles on Different Types of MV Cable Joints
    Borghetto, Johnny
    Pirovano, Giovanni
    Tornelli, Carlo
    Contin, Alfredo
    [J]. 2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 441 - 446
  • [3] Diagnostic Accuracy and Technical Considerations for MV Cable Field Partial Discharge Measurements
    Banerjee, Sarajit
    Drapeau, Jean-Francois
    [J]. 2022 9TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2022, : 24 - 33
  • [4] Comparison of parametric Partial Discharge and Dissipation Factor Characteristics of MV PILC Cables
    Mladenovic, I.
    Weindl, Ch.
    Freitag, Ch.
    [J]. CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 319 - 322
  • [5] Impact of partial discharges on MV cable dissipation factor varying supply frequency and waveshape
    Seri, P.
    Berardi, G.
    Albertini, M.
    Bononi, S. Franchi
    Haney, J.
    Tonyali, K.
    Montanari, G. C.
    [J]. 2022 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP 2022), 2022, : 316 - 319
  • [6] Faults Evaluation of MV Underground Cable Joints
    Calcara, Luigi
    D'Orazio, Luigi
    Della Corte, Maurizio
    Di Filippo, Guglielmo
    Pastore, Alessio
    Ricci, Davide
    Pompili, Massimo
    [J]. 2019 AEIT INTERNATIONAL ANNUAL CONFERENCE (AEIT), 111TH EDITION, 2019,
  • [7] Investigating the progression of insulation degradation in power cable based on partial discharge measurements
    Hassan, Waqar
    Shafiq, Muhammad
    Hussain, Ghulam Amjad
    Choudhary, Maninder
    Palu, Ivo
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2023, 221
  • [8] Analysis of Partial Discharge in Underground Cable Joints
    Rajalakshmi, B.
    Kalaivani, L.
    [J]. 2015 INTERNATIONAL CONFERENCE ON INNOVATIONS IN INFORMATION, EMBEDDED AND COMMUNICATION SYSTEMS (ICIIECS), 2015,
  • [9] Dielectric and Partial Discharge Investigations on Aged Medium Voltage Underground Power Cables Dielectric integrity of MV underground cables: An experimental approach
    Arumugam, Saravanakumar
    Bogaczyk, Marc
    Gorchakov, Sergey
    Kozakov, Ruslan
    Weltmann, Klaus-Dieter
    [J]. 2015 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2015, : 306 - 310
  • [10] Dielectric Dissipation factor measurements on stator insulation - results from a global survey
    Krieg-Wezelenburg, M. G.
    [J]. 2020 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2020, : 269 - 273