Techno-economic assessment of low-grade geothermal heat-driven ejector refrigeration cycle with a flash chamber and a booster compressor

被引:0
|
作者
Sahana, Chitta [1 ]
De, Sudipta [2 ]
Mondal, Subha [1 ]
机构
[1] Aliah Univ, Dept Mech Engn, Kolkata 700160, India
[2] Jadavpur Univ, Dept Mech Engn, Kolkata 700032, India
关键词
Ejector; Flash chamber; Booster compressor; Low-grade geothermal heat; Mechanical COP; Levelized cooling cost; ORGANIC RANKINE-CYCLE; THERMODYNAMIC ANALYSIS; PERFORMANCE ANALYSIS; COMBINED POWER; SYSTEM; OPTIMIZATION; EFFICIENCIES; WORKING; ENERGY; WATER;
D O I
10.1007/s10098-023-02662-5
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present study, an ejector refrigeration cycle with a flash chamber (FC) and a booster compressor is proposed to produce a 300-kW refrigeration effect for evaporator temperature varying between - 10 and 0 degrees C. R600a and R1234yf are considered as the working fluids. Readily available geothermal water at 95 degrees C is considered as the heat source. Thermodynamic and economic analyses are conducted by comparing with a vapour compression refrigeration cycle (VCRC) with a FC. It is observed that there exist optimum combinations of booster compressor pressure ratio and flash pressure ratio corresponding to the maximum mechanical COP and minimum levelized cooling cost (LCC). Both the proposed ejector refrigeration cycle and the VCRC yield better economic performance with R600a. For zero-carbon pricing and the specified range of evaporator temperature, the achievable LCC reduction with the R600a-based proposed cycle varies between 11.99 and 13.98%. The corresponding range of the achievable LCC reduction is 15.02-26.20% for a carbon price of $ 75/ton of CO2. If the geothermal water flow rate is restricted to 15 kg/s, the achievable range of LCC reductions for an R600a-based system will be 7.48-10.40% if the carbon pricing is ignored. For a reasonable carbon price, the proposed geothermal heat-driven cycle with each considered working fluid yields a much lower LCC compared to that of the conventional cycle as the annual carbon foot print of the presented cycle is much lower.
引用
收藏
页码:1089 / 1106
页数:18
相关论文
共 44 条
  • [41] An efficient low-grade thermal energy dual-driven elastocaloric cooling system: Thermodynamic cycle analysis, economic and sustainability assessment
    Dong, Xingkun
    Jiang, Xiangjun
    Li, Peng
    Energy Conversion and Management, 2025, 324
  • [42] Techno-economic assessment of Joule-Brayton cycle architectures for heat to power conversion from high-grade heat sources using CO2 in the supercritical state
    Marchionni, Matteo
    Bianchi, Giuseppe
    Tassou, Savvas A.
    ENERGY, 2018, 148 : 1140 - 1152
  • [43] Thermodynamic and economic analysis and multi-objective optimization of a novel transcritical CO2 Rankine cycle with an ejector driven by low grade heat source
    Xia, Jiaxi
    Wang, Jiangfeng
    Zhou, Kehan
    Zhao, Pan
    Dai, Yiping
    ENERGY, 2018, 161 : 337 - 351
  • [44] Comparative study on two low-grade heat driven absorption-compression refrigeration cycles based on energy, exergy, economic and environmental (4E) analyses
    Xu, Yingjie
    Jiang, Ning
    Pan, Fan
    Wang, Qin
    Gao, Zengliang
    Chen, Guangming
    ENERGY CONVERSION AND MANAGEMENT, 2017, 133 : 535 - 547