Numerical study on performance of hybrid mechanical draft wet cooling tower

被引:11
|
作者
Deng, Weipeng [1 ]
Sun, Fengzhong [1 ]
Chen, Kun [1 ]
Zhang, Xiaoyu [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
Hybrid MCT; Thermal performance; Plume abatement; Water saving rate; Numerical simulation; CROSSWIND; AIR; TEMPERATURE; ABATEMENT; RETROFIT; SYSTEM; PLUME; WATER;
D O I
10.1016/j.ijheatmasstransfer.2022.123574
中图分类号
O414.1 [热力学];
学科分类号
摘要
To explore the operation mechanism of the hybrid mechanical draft wet cooling tower (hybrid MCT), a 3D model of the hybrid MCT is established. The plume, water saving, and cooling capacity of the hybrid MCT are discussed. The ambient dry bulb temperature, relative humidity, circulating water temperature, and circulating water flow rate are taken as the main variables. Results that the ambient dry bulb temperature and circulating water temperature have the larger impact on the plume abatement and water saving rate, and the relative humidity and circulating water flow rate have relatively small impact. As the ratio of circulating water flow rate in the dry part increases, the water saving rate and cooling capacity of hybrid MCT are enhanced. However, when the ratio of circulating water flow rate in the dry part exceeds 0.4, the variation of water saving rate is not obvious. Based on satisfied plume abatement, by adjusting the airflow resistance in the dry part, the water temperature drop of hybrid MCT can be increased by 0.4 degrees C.(c) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Performance investigation of the natural draft wet cooling tower at different wet-bulb temperatures
    Raj, Gaurav
    Chandra, Prakash
    Pathak, Piyush Kumar
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2021, : 5864 - 5872
  • [32] A Numerical Study on the Improving Techniques of the Cooling Performance of a Natural Draft Dry Cooling Tower under Crosswind
    Wang, Weiliang
    Liu, Pei
    Li, Zheng
    Ni, Weidou
    Liu, Jiangmin
    Li, Yongsheng
    PRES15: PROCESS INTEGRATION, MODELLING AND OPTIMISATION FOR ENERGY SAVING AND POLLUTION REDUCTION, 2015, 45 : 1081 - 1086
  • [33] Numerical analysis on performance of mechanical draft wet cooling towers based on the condensation plume module
    Deng, Weipeng
    Sun, Fengzhong
    APPLIED THERMAL ENGINEERING, 2024, 237
  • [34] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, Wanchai
    Kuansathan, Mantheerapol
    APPLIED THERMAL ENGINEERING, 2014, 71 (01) : 83 - 93
  • [35] Comparative evaluation of hybrid (dry/wet) cooling tower performance
    Asvapoositkul, W. (wanchai.asv@kmutt.ac.th), 1600, Elsevier Ltd (71):
  • [36] Evaporative cooling of water in a mechanical draft cooling tower
    Fisenko, SP
    Brin, AA
    Petruchik, AI
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2004, 47 (01) : 165 - 177
  • [37] Thermal optimization of a natural draft wet cooling tower
    Williamson, N.
    Behnia, M.
    Armfield, S. W.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (14) : 1349 - 1361
  • [38] A Comprehensive Approach to an Optimum Design and Simulation Model of a Mechanical Draft Wet Cooling Tower
    Panjeshahi, Mohammad Hassan
    Ataei, Abtin
    Gharaie, Mona
    IRANIAN JOURNAL OF CHEMISTRY & CHEMICAL ENGINEERING-INTERNATIONAL ENGLISH EDITION, 2010, 29 (01): : 21 - 32
  • [39] DYNAMIC MODELING OF MECHANICAL DRAFT COUNTER-FLOW WET COOLING TOWER WITH MODELICA
    Li, Xiao
    Li, Yaoyu
    Seem, John E.
    PROCEEDINGS OF THE ASME DYNAMIC SYSTEMS AND CONTROL CONFERENCE 2010, VOL 2, 2010, : 687 - 694
  • [40] Comparative study on the cooling characteristics of high level water collecting natural draft wet cooling tower and the usual cooling tower
    Zhao, Yuanbin
    Sun, Fengzhong
    Long, Guoqing
    Huang, Xiaofeng
    Huang, Wenqiang
    Lyv, Dongqiang
    ENERGY CONVERSION AND MANAGEMENT, 2016, 116 : 150 - 164