Reliability improvement of gas discharge tube by suppressing the formation of short-circuit pathways

被引:0
|
作者
程凌云 [1 ]
向念文 [1 ,2 ]
李科杰 [1 ]
陈维江 [3 ]
边凯 [3 ]
阳晋 [4 ]
徐宗奇 [4 ]
韩聪颖 [4 ]
古宏阳 [1 ]
杨纯 [1 ]
机构
[1] Heifei University of Technology
[2] Institute of Energy, Hefei Comprehensive National Science Center
[3] State Grid Corporation of China
[4] Beijing National Railway Research & Design Institute of Signal & Communication Group Co., Ltd.
基金
中国国家自然科学基金;
关键词
D O I
暂无
中图分类号
TN13 [气体放电器件、离子管];
学科分类号
080901 ;
摘要
After cumulative discharge of gas discharge tube(GDT), it is easy to form a short circuit pathway between the two electrodes, which increases the failure risk and causes severe influences on the protected object. To reduce the failure risk of GDT and improve cumulative discharge times before failure, this work aims to suppress the formation of two short-circuit pathways by optimizing the tube wall structure, the electrode materials and the electrode structure. A total of five improved GDT samples are designed by focusing on the insulation resistance change that occurs after the improvement; then, by combining these designs with the microscopic morphology changes inside the cavity and the differences in deposition composition, the reasons for the differences in the GDT failure risk are also analyzed. The experimental results show that compared with GDT of traditional structure and material, the method of adding grooves at both ends of the tube wall can effectively block the deposition pathway of the tube wall, and the cumulative discharge time before device failure is increased by 149%. On this basis, when the iron-nickel electrode is replaced with a tungsten-copper electrode, the difference in the electrode’s surface splash characteristics further extends the discharge time before failure by 183%. In addition, when compared with the traditional electrode structure, the method of adding an annular structure at the electrode edge to block the splashing pathway for the particles on the electrode surface shows no positive effect, and the cumulative discharge time before the failure of the two structures is reduced by 22.8% and 49.7%, respectively. Among these improved structures, the samples with grooves at both ends of the tube wall and tungsten-copper as their electrode material have the lowest failure risk.
引用
收藏
页码:157 / 170
页数:14
相关论文
共 50 条
  • [31] Performance and Short-Circuit Reliability of SiC MOSFETs With Enhanced JFET Doping Design
    Lin, Chaobiao
    Ren, Na
    Xu, Hongyi
    Sheng, Kuang
    IEEE TRANSACTIONS ON ELECTRON DEVICES, 2023, 70 (05) : 2395 - 2402
  • [32] STUDY OF STRUCTURE OF A PRIMARY DISTRIBUTION NETWORK AS RELATED TO RELIABILITY AND SHORT-CIRCUIT LEVELS
    COMELLINI, E
    SALVADERI, L
    REGGIANI, F
    PARIS, L
    NOFERI, PL
    ELETTROTECNICA, 1972, 59 (07): : 793 - +
  • [33] Improving reliability in electric drive systems during IGBT short-circuit fault
    Naghavi, Maryam
    Ghanbari, Mahmood
    Ebrahimi, Reza
    Jannati, Mohammad
    IET POWER ELECTRONICS, 2021, 14 (04) : 888 - 899
  • [34] Investigation of Idle Running and Short-Circuit Performance Improvement for an Asynchronous Traction Motor
    Raluca-Cristina, Nicolae
    Ion, Vlad
    Marian-Stefan, Nicolae
    Sorin, Enache
    2019 INTERNATIONAL CONFERENCE ON ELECTROMECHANICAL AND ENERGY SYSTEMS (SIELMEN), 2019,
  • [35] A 50:1 Bandwidth Tightly Coupled Dipole Array With Short-Circuit Resonance Suppressing Surface
    Feng, Yuhao
    Chen, Yikai
    Zhu, Manyun
    IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS II-EXPRESS BRIEFS, 2024, 71 (07) : 3323 - 3327
  • [36] Breakdown voltage reliability improvement in gas-discharge tube surge protectors employing graphite field emitters
    Zumer, Marko
    Zajec, Bojan
    Rozman, Robert
    Nemanic, Vincenc
    JOURNAL OF APPLIED PHYSICS, 2012, 111 (08)
  • [37] PROBABILISTIC SHORT-CIRCUIT UPRATING OF STATION STRAIN BUS SYSTEM - RELIABILITY AND OPERATING CONSIDERATIONS
    RAMANI, N
    WANG, L
    TANAKA, WH
    MACEDO, FX
    IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (04) : 137 - 141
  • [38] Analysis of power transformers reliability with regard to the influences of short-circuit currents effects and overcurrents
    Gutten, Miroslav
    Kucera, Stanislav
    Kucera, Matej
    Sebok, Milan
    PRZEGLAD ELEKTROTECHNICZNY, 2009, 85 (07): : 62 - 64
  • [39] Improving reliability and short-circuit protection of power lines for road lighting (interchange of experience)
    Galimova, Akilya A. (akilya@mail.ru), 2017, LLC Editorial of Journal Light Technik (25):
  • [40] IMPROVING RELIABILITY AND SHORT-CIRCUIT PROTECTION OF POWER LINES FOR ROAD LIGHTING (INTERCHANGE OF EXPERIENCE)
    Galimova, Akilya A.
    LIGHT & ENGINEERING, 2017, 25 (04): : 145 - 148