Experimental Performance of Moderate and High Temperature Heat Pump Charged with Refrigerant Mixture BY-3

被引:0
|
作者
陈成敏 [1 ]
张于峰 [1 ]
邓娜 [1 ]
马洪亭 [1 ]
张彦所 [1 ]
马丽筠 [1 ]
胡晓微 [1 ]
机构
[1] School of Environmental Science and Engineering,Tianjin University
关键词
moderate and high temperature heat pump; refrigerant mixture; single-stage; compression heat pump system; coefficient of performance;
D O I
暂无
中图分类号
TB64 [制冷材料];
学科分类号
0805 ;
摘要
Theoretical and experimental analysis of a new refrigerant mixture BY-3 was conducted based on a single-stage vapor compression refrigeration system. The water-water heat pump system used BY-3 to produce hot water when the low temperature was 20 ℃. The following results were obtained: the highest temperature at the condenser outlet reached about 85 ℃; when the difference between the water temperatures at the condenser outlet and the evaporator inlet was less than 40 ℃, the coefficient of performance (COP) was larger than 4; when the difference reached 55 ℃, the COP still kept 3; the discharge temperature of BY-3 was lower than 100 ℃, and the refrigerant vapor pressure kept lower than 1.8 MPa. When the water temperature at the condenser outlet reached over 85 ℃, nearly a 5 ℃ superheating temperature was maintained.
引用
收藏
页码:386 / 390
页数:5
相关论文
共 50 条
  • [1] Experimental performance of moderate and high temperature heat pump charged with refrigerant mixture BY-3
    Chen C.
    Zhang Y.
    Deng N.
    Ma H.
    Zhang Y.
    Ma L.
    Hu X.
    Transactions of Tianjin University, 2011, 17 (5) : 386 - 390
  • [2] Experimental Performance of Moderate and High Temperature Heat Pump Charged with Refrigerant Mixture BY-3
    陈成敏
    张于峰
    邓娜
    马洪亭
    张彦所
    马丽筠
    胡晓微
    Transactions of Tianjin University, 2011, 17 (05) : 386 - 390
  • [3] Experimental performance of high temperature heat pump with near-azeotropic refrigerant mixture
    Yu Xiaohui
    Zhang Yufeng
    Deng Na
    Chen Chengmin
    Ma Lijun
    Dong Lipin
    Zhang Yan
    ENERGY AND BUILDINGS, 2014, 78 : 43 - 49
  • [4] Experimental investigation on the performance of a very high temperature heat pump with water refrigerant
    Wu, Di
    Jiang, Jiatong
    Hu, Bin
    Wang, R. Z.
    ENERGY, 2020, 190
  • [5] Experimental Study on Compression/Absorption High-Temperature Hybrid Heat Pump with Natural Refrigerant Mixture
    Kim, Jiyoung
    Park, Seong-Ryong
    Baik, Young-Jin
    Chang, Ki-Chang
    Ra, Ho Sang
    Kim, Minsung
    Kim, Yongchan
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2011, 35 (12) : 1367 - 1373
  • [6] Performance analysis of a cascade high temperature heat pump using R245fa and BY-3 as working fluid
    Ma, Xuelian
    Zhang, Yufeng
    Fang, Lei
    Yu, Xiaohui
    Li, Xiaoqiong
    Sheng, Ying
    Zhang, Yan
    APPLIED THERMAL ENGINEERING, 2018, 140 : 466 - 475
  • [7] Experimental investigation of a heat pump tumble dryer with a zeotropic refrigerant mixture
    Cop, Melanie
    Barta, Riley B.
    Thomas, Christiane
    Hesse, Ullrich
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 158 : 190 - 201
  • [8] Experimental Performance Comparison of High-Glide Hydrocarbon and Synthetic Refrigerant Mixtures in a High-Temperature Heat Pump
    Brendel, Leon P. M.
    Bernal, Silvan N.
    Arpagaus, Cordin
    Roskosch, Dennis
    Bardow, Andre
    Bertsch, Stefan S.
    ENERGIES, 2024, 17 (08)
  • [9] Experimental Investigation of Performance of R134a/R152a Refrigerant Mixture in Heat Pump
    Boran, Kurtulus
    Menlik, Tayfun
    Alpsoy, Halil
    JOURNAL OF POLYTECHNIC-POLITEKNIK DERGISI, 2015, 18 (04): : 251 - 256
  • [10] WATER VAPOUR AS REFRIGERANT FOR A NEW HIGH TEMPERATURE HEAT PUMP
    Chamoun, M.
    Rulliere, R.
    Haberschill, P.
    Berail, J. F.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 376 - +