Discharge modes evolution characteristics of metal particle on the spacer surface in AC gas insulated switchgear

被引:0
|
作者
Nie, Jiayi [1 ]
Fan, Xing [1 ]
Pei, Zhehao [1 ]
Ge, Dong [2 ]
Xu, Yuan [3 ]
Xiang, Nianwen [1 ]
Chen, Weijiang [2 ]
机构
[1] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] State Grid Corp China, Beijing 100031, Peoples R China
[3] China Elect Power Res Inst, Beijing 100192, Peoples R China
基金
国家重点研发计划;
关键词
metal particle; micro-discharge; discharge mode; electric field characteristics; FLASHOVER;
D O I
10.1088/1361-6463/ad89cf
中图分类号
O59 [应用物理学];
学科分类号
摘要
Flashover faults on gas insulated switchgear (GIS) insulators induced by metal particles occur frequently. Previous studies have obtained the characteristics of partial discharges (PDs) induced by metal particles on spacer surfaces, but these characteristics cannot explain the detection failure of ultra-high frequency (UHF) online monitoring. To enable further study of the PD characteristics induced by surface metal particles, the space electric field and a very-high-sensitivity pulse current (PC) measurement system were established. The electric field and PC characteristics of a PD induced by metal particle on the spacer surface of a 126 kV GIS were obtained. Two PD modes were found to be induced by surface metal particles. In addition to the typical pulse discharge (TP), there is a micro-discharge group (MG) mode with low apparent charge and long duration. The average apparent charge of the MG mode is approximately one-tenth of that of the TP at 0.4 pC. Its duration may extend to the millisecond level, causing significant distortion of the spatial electric field while hardly producing UHF signals. Moreover, increasing the applied voltage will increase the proportion of the MG within the total discharge, where this proportion can reach more than 90% before flashover, and the proportion of the discharge pulses that generates UHF signals is as low as 1%. The MG generation mechanism is analysed, the ion group stranded on the spacer surface by the TP changes the local electric field at the tip of the metal particle, which reduces the development length and apparent charge of the MG. Low apparent charge is cleared easily by the background electric field and thus the discharge interval is very short. This paper can provide an important basis for revealing the mechanism of GIS spacer surface discharge induced by metal particles and solving the effectiveness of PD monitoring devices.
引用
收藏
页数:10
相关论文
共 50 条
  • [31] Scaling laws of the lifting height of a conductive particle in a gas insulated switchgear
    Wang, Zekun
    Liu, Moubin
    Yang, Xi
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2021, 54 (25)
  • [32] Direct numerical simulations for the motion of charged particle in gas insulated switchgear
    Yang, Li
    Yang, Xi
    Zhu, Lijuan
    Wu, Yezhi
    2021 96TH IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP 2021) / 16TH IEEE NANOTECHNOLOGY MATERIALS AND DEVICES CONFERENCE (IEEE NMDC 2021), 2021, : 470 - 473
  • [33] Motor Behavior and Hazard of Spherical and Linear Particle in Gas Insulated Switchgear
    Zhang L.
    Lu S.
    Li C.
    Wang H.
    Tang Z.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (20): : 4217 - 4225
  • [34] AC breakdown and decomposition products detection characteristics of eco-friendly insulating medium in gas insulated switchgear
    Du, Shuai
    Cheng, Xian
    Ge, Guowei
    Li, Tianyun
    Guo, Longyu
    Liu, Sai
    SCIENTIFIC REPORTS, 2024, 14 (01):
  • [35] Study on the Partial Discharge Characteristics and Development Process in Use of the Multiple Discharge Patterns for the Typical Defects in Gas-Insulated Switchgear
    Yao, Rui
    Si, Gangquan
    Zhang, Yanbin
    Yuan, Yiwei
    Xie, Qian
    CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 2016, 39 (04): : 297 - 310
  • [36] Partial Discharge Detection and Discharge Type Identification of Gas Insulated Switchgear Based on Photoelectric Detection
    Liu, Dayong
    Teng, Guifa
    JOURNAL OF NANOELECTRONICS AND OPTOELECTRONICS, 2019, 14 (11) : 1625 - 1633
  • [37] Detection Method of Partial Discharge on Transformer and Gas-Insulated Switchgear: A Review
    Faizol, Zulbirri
    Zubir, Farid
    Saman, Norhafezaidi Mat
    Ahmad, Mohd Hafizi
    Rahim, Mohamad Kamal A.
    Ayop, Osman
    Jusoh, Muzammil
    Majid, Huda A.
    Yusoff, Zubaida
    APPLIED SCIENCES-BASEL, 2023, 13 (17):
  • [38] Recurrent Neural Network for Partial Discharge Diagnosis in Gas-Insulated Switchgear
    Minh-Tuan Nguyen
    Viet-Hung Nguyen
    Yun, Suk-Jun
    Kim, Yong-Hwa
    ENERGIES, 2018, 11 (05)
  • [40] Health assessment procedures on HVAC Gas Insulated Switchgear Partial Discharge monitoring
    Linn, Thomas
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,