Power Grid Primary Frequency Control Strategy Based on Fuzzy Adaptive and State-of-Charge Self-Recovery of Flywheel-Battery Hybrid Energy Storage System

被引:0
|
作者
Wen, Shaobo [1 ,2 ]
Gong, Yipeng [1 ]
Zhao, Zhendong [1 ]
Mu, Xiufeng [3 ]
Zhao, Sufang [1 ]
机构
[1] Nanjing Inst Technol, Sch Traff Engn, Nanjing 211167, Peoples R China
[2] Jiangsu Collaborat Innovat Ctr, Smart Distribut Network, Nanjing 211167, Jiangsu, Peoples R China
[3] Nanjing Inst Technol, Sch Commun & Artificial Intelligence, Sch Integrated Circuits, Nanjing 211167, Peoples R China
关键词
flywheel-battery hybrid energy storage; primary frequency control; fuzzy control; SOC self-recovery;
D O I
10.3390/en18061536
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The integration of new renewable energy sources, such as wind and solar power, is characterized by strong randomness and volatility, which increases the risk of power grid system frequency fluctuations exceeding limits. Traditional thermal power units are unable to frequently respond to frequency regulation signals, necessitating the incorporation of energy storage technologies for primary frequency control. This paper presents a primary frequency control strategy for a flywheel-battery hybrid energy storage system (HESS) based on fuzzy adaptation and state-of-charge (SOC) self-recovery. First, a frequency response system model for primary frequency regulation in flywheel-battery hybrid energy storage was formulated. The frequency regulation command is divided into high-frequency and low-frequency components, which are allocated to the flywheel and the battery, respectively. Fuzzy control and regression functions were employed to adjust and constrain the frequency deviation, frequency deviation rate, and SOC. Subsequently, considering the SOC and frequency deviation of each energy storage component, a SOC self-recovery strategy was proposed. Finally, a simulation analysis was performed using a system benchmark capacity of 600 MW. Under step load disturbance conditions, the proposed strategy reduces the maximum frequency deviation by 10.52% and the steady-state frequency deviation by 8.35% compared with traditional methods. Under random load disturbance conditions, the root mean square (RMS) value of frequency deviation is reduced by 7.34%, and the peak-to-valley difference of frequency decreases by 6.74%. Compared to energy storage without SOC self-recovery, the RMS values of SOC for flywheel storage and battery storage are reduced by 8.79% and 16.68%, respectively. The results demonstrate that the proposed control strategy effectively improves the system's frequency regulation performance, reduces energy storage output fluctuations, and enhances the SOC self-recovery effect of the HESS.
引用
收藏
页数:23
相关论文
共 50 条
  • [21] State of Energy Recovery of Battery Energy Storage System With Primary Frequency Control for Battery Aging Mitigation
    Liu, Tianqi
    Liu, Yiheng
    Peng, Qiao
    Meng, Jinhao
    Gao, Fei
    IEEE TRANSACTIONS ON TRANSPORTATION ELECTRIFICATION, 2025, 11 (02): : 5276 - 5287
  • [22] Primary Frequency Regulation Strategy with Energy Storage System Based on Weight Factors and State of Charge Recovery
    Li J.
    Hou T.
    Mu G.
    Yan G.
    Li C.
    Hu D.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (19): : 63 - 72
  • [23] Comprehensive control method of energy storage system to participate in primary frequency regulation with adaptive state of charge recovery
    Zhu, Zhenshan
    Ye, Chengtao
    Wu, Shiyu
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2021, 31 (12):
  • [24] RESEARCH ON FREQUENCY MODULATION CONTROL STRATEGY OF AUXILIARY POWER GRID IN BATTERY ENERGY STORAGE SYSTEM
    Li J.
    Qu S.
    Ma S.
    Zeng W.
    Xiong J.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (03): : 326 - 335
  • [25] Design of energy management for composite energy storage system consisting of lithium battery and flywheel based on adaptive wavelet-fuzzy control strategy
    Sun, Binbin
    Zhao, Hailan
    Xie, Mengxue
    Li, Bo
    JOURNAL OF THE BRAZILIAN SOCIETY OF MECHANICAL SCIENCES AND ENGINEERING, 2024, 46 (07)
  • [26] SOC Consistency Optimization Control Strategy of Flywheel Array Energy Storage System for Grid Primary Frequency Regulation
    Wang, Kaituo
    Tian, Lijun
    Li, Jie
    Jiang, Tao
    2022 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA (I&CPS ASIA 2022), 2022, : 1517 - 1524
  • [27] Control Strategy of Battery State of Charge for Wind/Battery Hybrid Power System
    Li, Xiangjun
    Hui, Dong
    Wu, Li
    Lai, Xiaokang
    IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE 2010), 2010, : 2723 - 2726
  • [28] Sliding Mode Control Based on PSO Adaptive Frequency- Decoupling for Hybrid Energy Storage System with Battery State of Charge estimation
    Benariba, Hassan
    Boumediene, Abdelmadjid
    PRZEGLAD ELEKTROTECHNICZNY, 2024, 100 (01): : 165 - 171
  • [29] Coordinated Control of a Hybrid Energy Storage System for Improving the Capability of Frequency Regulation and State-of-Charge Management
    Thien-An Nguyen-Huu
    Van Thang Nguyen
    Hur, Kyeon
    Shim, Jae Woong
    ENERGIES, 2020, 13 (23)
  • [30] Impact of State-of-Charge Control Integrated with Load-Frequency Control on Battery Energy Storage System in Islanded Microgrid System
    Sitompul, Sandro
    Fujita, Goro
    2021 IEEE 12TH ENERGY CONVERSION CONGRESS AND EXPOSITION - ASIA (ECCE ASIA), 2021, : 199 - 203