Unbiased Euclidean Direction Search Algorithm for Partial Discharge Location in Cable Systems

被引:0
|
作者
Wang, Jie [1 ]
Lu, Lu [1 ]
Zhu, Guangya [2 ]
Yin, Kai-Li [3 ]
Zhou, Kai [2 ]
Chen, Badong [4 ]
机构
[1] Sichuan Univ, Coll Elect & Informat Engn, Chengdu 610065, Peoples R China
[2] Sichuan Univ, Coll Elect Engn, High Voltage Lab, Chengdu 610065, Peoples R China
[3] Qingdao Univ Sci & Technol, Coll Automat & Elect Engn, Qingdao 266520, Peoples R China
[4] Xi An Jiao Tong Univ, Inst Artificial Intelligence & Robot IAIR, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Noise measurement; Signal processing algorithms; Noise; Power cables; Cable insulation; Accuracy; Estimation; Cable shielding; Vectors; Transient analysis; Cable systems; location; normalized Euclidean direction search (EDS); partial discharge (PD); transient behavior; TOTAL LEAST-SQUARES; LOCALIZATION; KERNEL;
D O I
10.1109/TIM.2025.3538076
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Utilizing the unbiasedness criterion, this article proposes a bias-compensated normalized Euclidean direction search (BC-NEDS) algorithm with noisy inputs, which can effectively mitigate the impact of the bias by estimating the statistical properties of inputs. Moreover, the theoretical analysis of the BC-NEDS algorithm is conducted in a transient regime. Simulations verify the validity of the theoretical analysis and showcase the improved performance of the BC-NEDS algorithm. Partial discharge (PD) location techniques can be utilized to effectively monitor the condition of the electrical apparatus. Considering the performance of the conventional location algorithms based on the time difference of arrival (TDOA) method may notably degrade with noisy inputs. Hitherto, scarce literature concentrates on the PD location problem by leveraging adaptive filtering techniques. Such problem is essentially characterized by a noisy input model. This work aims to propose a new one-step algorithm to simultaneously denoise and achieve improved location accuracy with noisy input. The BC-NEDS algorithm is employed for solving the PD location problem. The BC-NEDS algorithm demonstrates the effectiveness in mitigating the bias arising from noisy inputs in both the direct and reflected PD signals and estimating the time difference to locate the PD signal of cable systems. Simulations and experimental studies exhibit that the BC-NEDS algorithm verifies the effectiveness and achieves enhanced location accuracy for cable systems.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Partial Discharge Location With Gradient-Descent Total Least-Squares Euclidean Direction Search Algorithm for Cable Systems
    Wang, Jie
    Lu, Lu
    Zhou, Kai
    Zhu, Guangya
    Pan, Songkun
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2025, 21 (02) : 1469 - 1478
  • [2] Partial Discharge Location Algorithm Based on Total Least-Squares With Matern Kernel in Cable Systems
    Lu, Lu
    Zhou, Kai
    Zhu, Guangya
    Yang, Xiaomin
    Chen, Badong
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2023, 19 (03) : 2421 - 2431
  • [3] The Euclidean Direction Search algorithm for adaptive filtering
    Xu, GF
    Bose, T
    Schroeder, J
    ISCAS '99: PROCEEDINGS OF THE 1999 IEEE INTERNATIONAL SYMPOSIUM ON CIRCUITS AND SYSTEMS, VOL 3: ANALOG AND DIGITAL SIGNAL PROCESSING, 1999, : 146 - 149
  • [4] The Euclidean Direction Search algorithm in adaptive filtering
    Bose, T
    Xu, GF
    IEICE TRANSACTIONS ON FUNDAMENTALS OF ELECTRONICS COMMUNICATIONS AND COMPUTER SCIENCES, 2002, E85A (03) : 532 - 539
  • [5] Partial discharge detection and location in cable joint
    Wu, XY
    Xie, HK
    Peng, ZR
    Pang, QP
    1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 721 - 723
  • [6] Study on time delay estimation algorithm in cable partial discharge location based on wavelet transform
    Du, Yan
    Liao, Rui-Jin
    Zhou, Quan
    Lu, Yun-Cai
    Gaoya Dianqi, 2007, 5 (389-393): : 389 - 393
  • [7] Euclidean Direction Search Algorithm Based on Maximum Correntropy Criterion
    Wang, Jie
    Lu, Lu
    Shi, Long
    Zhu, Guangya
    Yang, Xiaomin
    IEEE SIGNAL PROCESSING LETTERS, 2023, 30 : 1032 - 1036
  • [8] Application of Distance-based Cross-correlation Algorithm in Partial Discharge Location of Power Cable
    Zhou K.
    Rao X.
    Wang X.
    Xie M.
    Li M.
    Xi H.
    Rao, Xianjie (1953520244@qq.com), 1600, Science Press (47): : 2946 - 2954
  • [9] Channel equalization using an Euclidean Direction Search based adaptive algorithm
    Xu, GF
    Bose, T
    Schroeder, J
    GLOBECOM 98: IEEE GLOBECOM 1998 - CONFERENCE RECORD, VOLS 1-6: THE BRIDGE TO GLOBAL INTEGRATION, 1998, : 3479 - 3484
  • [10] Partial Discharge Location for Power Cable Based on the Time Reversal Technique
    Xie M.
    Zhou K.
    He M.
    Zhao S.
    Zhang F.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2018, 38 (11): : 3402 - 3409