Hybrid Control Strategy for DC Microgrid Against False Data Injection Attacks and Sensor Faults Based on Lagrange Extrapolation and Voltage Observer

被引:0
|
作者
Jo, Seong-Bae [1 ]
Tran, Dat Thanh [1 ]
Nguyen, Hieu Xuan [1 ]
Kim, Myungbok [2 ]
Kim, Kyeong-Hwa [1 ]
机构
[1] Seoul Natl Univ Sci & Technol, Res Ctr Elect & Informat Technol, Dept Elect & Informat Engn, 232 Gongneung-ro, Seoul 01811, South Korea
[2] Korea Inst Ind Technol, Purpose Built Mobil Grp, 6 Choemdan gwagiro 208-gil, Gwangju 61012, South Korea
来源
ELECTRONICS | 2025年 / 14卷 / 06期
基金
新加坡国家研究基金会;
关键词
distributed DC microgrid; false data injection attack; hybrid control strategy; Lagrange extrapolation; sensor fault; DISTRIBUTED SECONDARY CONTROL; COMMUNICATION; RESTORATION; IMPROVE; ENERGY;
D O I
10.3390/electronics14061087
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this study, to enhance the system reliability under false data injection (FDI) attacks and DC-link voltage (DCLV) sensor failures, a hybrid control strategy for a DC microgrid (DCMG) based on the Lagrange extrapolation and voltage observer is proposed. Under normal conditions without FDI attacks or DCLV sensor failures, the DCMG system works in a distributed control scheme. To enhance the reliability of the system under the DCLV sensor failure or FDI attack, the DCMG system utilizes a hybrid control strategy that combines distributed control with decentralized control. The hybrid control strategy is achieved by the proposed detection algorithms for FDI attacks and DCLV sensor failures. The detection of FDI attacks is accomplished by comparing the predicted secondary controller output based on the Lagrange extrapolation with the actual one. When a power agent detects an FDI attack, its control mode is switched to decentralized control by using the proposed hybrid control strategy. The DCLV sensor failure detection algorithm to enhance system reliability against DCLV sensor failures is achieved by comparing the estimated DCLV with the measured one from the voltage observer. Upon detecting a DCLV sensor failure, the operation of the power agent is switched to the current control mode to sustain the system operation even under DCLV sensor failures. The proposed detection algorithms are simple, effective, and precise, operating without mutual interference that deteriorates the detection accuracy. Simulation and experiments are carried out under various uncertain test conditions to validate the reliability and effectiveness of the proposed control strategy.
引用
收藏
页数:25
相关论文
共 50 条
  • [1] Sliding Mode Control Against False Data Injection Attacks in DC Microgrid Systems
    Zhang, Gufan
    Tong, Dongbing
    Chen, Qiaoyu
    Zhou, Wuneng
    IEEE SYSTEMS JOURNAL, 2023, 17 (04): : 6159 - 6168
  • [2] Voltage regulation strategy for alternating current microgrid under false data injection attacks
    Guan, Rongqiang
    Yi, Jing
    Fan, Siyuan
    Sun, Tianyi
    Liu, Peng
    Gao, Han
    ARCHIVES OF ELECTRICAL ENGINEERING, 2024, 73 (01) : 251 - 264
  • [3] Distributed Resilient Control of AC Microgrid Against False Data Injection Attacks
    Zhang L.
    Xu Y.
    Wu X.
    Wang S.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2023, 47 (08): : 44 - 52
  • [4] Lyapunov-Based Resilient Cooperative Control for DC Microgrid Clusters Against False Data Injection Cyber-Attacks
    Tan, Sen
    Xie, Peilin
    Guerrero, Josep M.
    Vasquez, Juan C.
    Alcala, Jose Matas
    Carreno, Jorge El Mariachet
    Guerrero-Zapata, Manel
    IEEE TRANSACTIONS ON SMART GRID, 2024, 15 (03) : 3208 - 3222
  • [5] Detection and mitigation against false data injection attacks using SHT and ANN in distributed control of DC microgrid
    Alankrita
    Pati, Avadh
    Adhikary, Nabanita
    ELECTRIC POWER SYSTEMS RESEARCH, 2025, 241
  • [6] Defense Strategy against False Data Injection Attacks in Ship DC Microgrids
    Zeng, Hong
    Zhao, Yuanhao
    Wang, Tianjian
    Zhang, Jundong
    JOURNAL OF MARINE SCIENCE AND ENGINEERING, 2022, 10 (12)
  • [7] Event-triggered consensus control for DC microgrids based on MKELM and state observer against false data injection attacks
    Xie, Zongkui
    Wu, Zhongqiang
    INTERNATIONAL JOURNAL OF MACHINE LEARNING AND CYBERNETICS, 2024, 15 (03) : 775 - 793
  • [8] Event-triggered consensus control for DC microgrids based on MKELM and state observer against false data injection attacks
    Zongkui Xie
    Zhongqiang Wu
    International Journal of Machine Learning and Cybernetics, 2024, 15 : 775 - 793
  • [9] A new stable scheme against false data injection attacks in distributed control microgrid
    Tahani, Vahid
    Zarif, Mohammad Haddad
    Narm, Hossein Gholizadeh
    IET CYBER-PHYSICAL SYSTEMS: THEORY & APPLICATIONS, 2024, 9 (01) : 27 - 40
  • [10] A Nonlinear Disturbance Observer Based DC Bus Voltage Control for a Hybrid AC/DC Microgrid
    Li, Xialin
    Wang, Chengshan
    Guo, Li
    Li, Yunwei
    2013 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2013, : 1655 - 1662