Electromagnetic Transient Research of Asymmetrical Grounding and Load Rejection of Offshore Wind Power Transmission System of Permanent Magnet Synchronous Generator

被引:0
|
作者
Wang S. [1 ]
Chen X. [1 ]
Zheng Z. [1 ]
Li J. [2 ]
Zhang Z. [2 ]
Lin R. [2 ]
Wang Y. [1 ]
Lu H. [1 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Hubei Province, Wuhan
[2] China Energy Engineering Group Guangdong Electric Power Design Institute Co., Ltd., Guangdong Province, Guangzhou
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2024年 / 44卷 / 02期
关键词
asymmetrical grounding; control and protection strategy; load rejection; offshore wind power; permanent magnet synchronous generator; transient overvoltage;
D O I
10.13334/j.0258-8013.pcsee.223179
中图分类号
学科分类号
摘要
In order to clarify the characteristics and level of the overvoltage of offshore wind power AC transmission system, the fault ride through characteristics of wind generator should be considered. Based on the control principle of the converter of permanent magnet synchronous generator, an analytical method for calculating the asymmetrical grounding overvoltage of offshore wind power system is proposed. Based on PSCAD, precise electromagnetic transient modeling and fault voltage ride through test are carried out for the wind generator model. On the background of a large-scale 500kV offshore wind power project in China, asymmetrical grounding and load rejection overvoltage of the system are simulated and calculated. The results show that the magnitude of asymmetrical grounding overvoltage in the system is related to the positive and negative sequence control strategy of the wind generator. The transient overvoltage above 1.3p.u. lasting for hundred-millisecond will be generated during the load rejection at grid side of submarine cable. The longer the overvoltage protection action delay, the more serious the transient overvoltage. The actual calculation of offshore wind power engineering needs to be closely related to the wind generator control and protection strategy, and evaluated based on the voltage tolerance level of key equipment. By optimizing the wind turbine control strategy, the system overvoltage level can be reduced. ©2024 Chin.Soc.for Elec.Eng.
引用
收藏
页码:827 / 837
页数:10
相关论文
共 23 条
  • [11] SHI Lei, ADAM G P, LI Rui, Et al., Control of offshore MMC during asymmetric offshore AC faults for wind power transmission, IEEE Journal of Emerging and Selected Topics in Power Electronics, 8, 2, pp. 1074-1083, (2020)
  • [12] CAO Shengshun, ZHANG Wenchao, WANG Meng, Et al., Study on fast analysis method transient fundamental frequency overvoltage of wind turbine generators in sending system when serious power disturbances occur in large-capacity UHVDC, High Voltage Engineering, 43, 10, pp. 3300-3306, (2017)
  • [13] LI Han, YU Peixin, LI Shurong, Et al., Study on internal overvoltages of 220kV submarine cable transmission system of the offshore oil–gas field group[J], Energy Reports, 8, pp. 377-386, (2022)
  • [14] TAO Jiayuan, YANG Qing, ZHENG Xuena, Et al., Switching transients caused by vacuum circuit breakers in collection grids of offshore wind farms[J], Wind Energy, 24, 12, pp. 1501-1516, (2021)
  • [15] LI Weixing, ZHU Meng, CHAO Pupu, Et al., Enhanced FRT and postfault recovery control for MMC-HVDC connected offshore wind farms[J], IEEE Transactions on Power Systems, 35, 2, pp. 1606-1617, (2020)
  • [16] SOLOOT A H, HOIDALEN H K, GUSTAVSEN B., The assessment of overvoltage protection within energization of offshore wind farms, Energy Procedia, 24, pp. 151-158, (2012)
  • [17] GB/T 50064—2014 Code for design of overvoltage protection and insulation coordination for AC electrical installations, (2014)
  • [18] ZHAO Yuantao, LI Jian, LUO Chujun, Research on overvoltage and insulation coordination of submarine cable for Hainan interconnection project, Smart Grid, 5, 1, pp. 17-22, (2017)
  • [19] ZHANG Tao, SUN Liuxue, ZHANG Yin, Study on switching overvoltage in off-shore wind farms, IEEE Transactions on Applied Superconductivity, 24, 5, (2014)
  • [20] LI Sisi, FANG Chun'en, PAN Lin, Et al., Research on measures suppressing high frequency transient overvoltage in offshore wind farms[J], Journal of Physics: Conference Series, 1983, (2021)