Adaptive Current Differential Protection for Distribution Networks With Inverter-interfaced Distributed Generators and Branch Loads

被引:0
|
作者
Wang G. [1 ]
Feng J. [1 ]
Li J. [1 ]
机构
[1] School of Electric Power Engineering, South China University of Technology, Guangdong Province, Guangzhou
来源
基金
中国国家自然科学基金;
关键词
adaptive current differential protection; branch load; distribution network; inverter-interfaced distributed generator; positive-sequence fault component;
D O I
10.13335/j.1000-3673.pst.2023.0430
中图分类号
学科分类号
摘要
A current differential protection has a good selectivity and sensitivity. However, the access of the inverter-interfaced distributed generators (IIDGs) and the branch loads has changed the fault characteristics of distribution networks, which increases the risks of the false or failure operations for the existing current differential protection of distribution networks. Based on the fault equivalence model of the PQ-IIDGs and the branch loads, this paper investigates the magnitude characteristics of the positive-sequence currents and their phase characteristics of the fault components, taking the relative positions of the fault points, the T-connected IIDGs and the branch loads as the datum point. An adaptive double-proportional-restraint-coefficients-based differential protection using the positive-sequence current amplitude and the fault-component phase is proposed. The reliability and sensitivity of the proposed protection criterion are analyzed using the amplitude and the phase planes. The effectiveness of the proposed method is validated by the PSCAD/EMTDC simulation. Results show that the scheme has a good adaptivity to different fault types, locations and fault resistances without being affected by the access of the IIDGs and the branch loads. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:2593 / 2602
页数:9
相关论文
共 27 条
  • [11] XU Sixuan, LU Yuping, A pilot protection method for distribution network with distributed generators[J], Automation of Electric Power Systems, 39, 9, pp. 113-118, (2015)
  • [12] ZHOU Chenghan, ZOU Guibin, DU Xiaogong, A pilot protection method based on positive sequence fault component current for active distribution networks[J], Proceedings of the CSEE, 40, 7, pp. 2102-2112, (2020)
  • [13] LIANG Yingyu, LU Zhengjie, Adaptive differential protection principle based on compensation coefficient for active distribution network[J], Power System Technology, 46, 6, pp. 2268-2275, (2022)
  • [14] LIU Xingwei, LI Yongli, CHEN Xiaolong, An improved scheme of longitudinal differential protection for teed lines with inverter-based distributed generations[J], Power System Technology, 40, 4, pp. 1257-1264, (2016)
  • [15] HAN Bowen, WANG Gang, LI Haifeng, Novel pilot protection scheme for distribution networks with inverter-interfaced distributed generators[J], High Voltage Engineering, 43, 10, pp. 3453-3462, (2017)
  • [16] Houlei GAO, Juan LI, Bingyin XU, Principle and implementation of current differential protection in distribution networks with high penetration of DGs[J], IEEE Transactions on Power Delivery, 32, 1, pp. 565-574, (2017)
  • [17] XU Meng, ZOU Guibin, GAO Lei, Pilot protection of positive sequence impedance for distribution network with inverter-based distributed generator[J], Automation of Electric Power Systems, 41, 12, pp. 93-99, (2017)
  • [18] HE Jinghan, LI Wenli, ZHANG Dahai, Differential protection scheme based on current amplitude of branch node for distribution network with DG[J], Power System Technology, 42, 11, pp. 3601-3608, (2018)
  • [19] ZHANG Xuesong, MA Xiao, ZHANG Leiqi, Novel current amplitude differential protection criterion for line with unmeasurable branch in active distribution network[J], Electric Power Automation Equipment, 40, 2, pp. 76-81, (2020)
  • [20] WANG Zixuan, MA Xiao, YANG Yong, A new criterion of amplitude differential protection for active distribution network considering load power effect of unmeasurable branches[J], Proceedings of the CSEE, 40, S1, pp. 56-68, (2020)