Optimization of Parameters of a Vertical Ground Heat Exchanger in a Geothermal Heating System

被引:0
|
作者
Jezierski, Walery [1 ]
Rynkowski, Piotr [1 ]
机构
[1] Bialystok Tech Univ, Fac Civil Engn & Environm Sci, Dept Sustainable Construct & Bldg Syst, Wiejska 45E St, PL-15351 Bialystok, Poland
关键词
geothermal heating system; vertical ground heat exchanger; deterministic mathematical model; optimization; PUMP SYSTEMS;
D O I
10.3390/buildings14123722
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study presents the results of an original study on the influence of selected parameters on the thermal efficiency of a vertical ground heat exchanger (VGHE) in a ground-source heat pump (GSHP) system. The research objective was an analysis of the specific thermal efficiency of a vertical ground heat exchanger q, received by a U-shaped element made of plastic pipes placed in a borehole, depending on seven direct influencing factors: the ground temperature Tg; the soil thermal conductivity coefficient lambda g; the thermal conductivity coefficient of the well material lambda m; the temperature of the heating medium (glycol) Tw at the feed to the ground heat exchanger and its flow rate M; the internal diameter of the pipes of the ground heat exchanger dw; and the distances between the external walls of the pipes of the ground heat exchanger L. The analysis was carried out for the climatic conditions of the Podlasie Voivodeship (Poland). Based on the results of the computational experiment obtained using the TRNSYS numerical environment, a deterministic mathematical model of this relationship was developed, and the effects of the influence of selected factors on the specific thermal efficiency q of the vertical ground heat exchanger, received by the U-shaped element, were analysed. Based on the model, the contribution of each parameter to the efficiency of the heat exchanger was determined. It turned out that changes in the values of the factors Tg (X1), lambda g (X2), lambda m (X3), M (X5), dw (X6) and L (X7) from the lower to the upper level caused an increase in the specific efficiency q of the heat exchanger by 34.04, 7.90, 15.20, 55.42, 6.58 and 24.26%. Only factor Tw (X4), with such a change, caused a decrease in the thermal efficiency of the tested heat exchanger by 44.22%. The parameters of the tested element of the geothermal heating system were also optimized according to the energy criterion using a numerical method in the Matlab environment. The information may be useful for scientists, designers, producers and consumers of heating systems based on heat pumps with a vertical ground heat exchanger as the lower heat source.
引用
收藏
页数:21
相关论文
共 50 条
  • [41] The key parameters method of calculating geothermal heat exchanger length
    Tian, Hui-Feng
    Cao, Wei-Wu
    Tumu Jianzhu yu Huanjing Gongcheng/Journal of Civil, Architectural and Environmental Engineering, 2009, 31 (01): : 110 - 113
  • [42] VENTILATION SYSTEM WITH GROUND HEAT EXCHANGER
    Pisarev, Vyacheslav
    Rabczak, Slawomir
    Nowak, Krzysztof
    JOURNAL OF ECOLOGICAL ENGINEERING, 2016, 17 (05): : 163 - 172
  • [43] Operation optimization of the coaxial deep borehole heat exchanger coupled with ground source heat pump for building heating
    Wang, Yaran
    Wang, Yeming
    You, Shijun
    Zheng, Xuejing
    Wei, Shen
    APPLIED THERMAL ENGINEERING, 2022, 213
  • [44] DESIGN OF AN IMPROVED VERTICAL SPIRAL CLOSED LOOP GEOTHERMAL HEAT EXCHANGER
    Malhotra, Tarun
    Davis, Dorian
    Adams, Deshawn
    Gebre, Fisseha L.
    Xu, JiaJun
    PROCEEDINGS OF ASME 2022 INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, IMECE2022, VOL 8, 2022,
  • [45] Simulation of the Periodical Heat Transfer Performance of Vertical Ground Heat Exchanger
    Song, Xinnan
    Zhang, Zhipeng
    Liu, Lihong
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1949 - 1956
  • [46] Seasonal performance for Heat pump with vertical ground heat exchanger in Riga
    Jaundalders, S.
    Stanka, P.
    Rusovs, D.
    3RD INTERNATIONAL CONFERENCE ON INNOVATIVE MATERIALS, STRUCTURES AND TECHNOLOGIES (IMST 2017), 2017, 251
  • [47] Preliminary Investigation of the Effect of Horizontal Piping on the Performance of a Vertical Ground Heat Exchanger System
    Cullin, James R.
    Spitler, Jeffrey D.
    Lee, Edwin
    ASHRAE TRANSACTIONS 2013, VOL 119, PT 2, 2013, 119 : 302 - 311
  • [48] ACHIEVEMENT OF GEOTHERMAL ENERGY USING GROUND HEAT EXCHANGER IN MA'EN
    Al-Dabbas, Mohammed Awwad Ali
    ENERGY & ENVIRONMENT, 2011, 22 (08) : 1029 - 1050
  • [49] Achievement of geothermal energy using ground heat exchanger in Ma'en
    Al-Dabbas, Mohammed Awwad Ali
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2011, 25 (08) : 2013 - 2023
  • [50] A performance of a heat pump system connected a new conic helicoidal geothermal heat exchanger for a greenhouse heating in the north of Tunisia
    Boughanmi, Hassen