Optimization of Parameters of a Vertical Ground Heat Exchanger in a Geothermal Heating System

被引:0
|
作者
Jezierski, Walery [1 ]
Rynkowski, Piotr [1 ]
机构
[1] Bialystok Tech Univ, Fac Civil Engn & Environm Sci, Dept Sustainable Construct & Bldg Syst, Wiejska 45E St, PL-15351 Bialystok, Poland
关键词
geothermal heating system; vertical ground heat exchanger; deterministic mathematical model; optimization; PUMP SYSTEMS;
D O I
10.3390/buildings14123722
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study presents the results of an original study on the influence of selected parameters on the thermal efficiency of a vertical ground heat exchanger (VGHE) in a ground-source heat pump (GSHP) system. The research objective was an analysis of the specific thermal efficiency of a vertical ground heat exchanger q, received by a U-shaped element made of plastic pipes placed in a borehole, depending on seven direct influencing factors: the ground temperature Tg; the soil thermal conductivity coefficient lambda g; the thermal conductivity coefficient of the well material lambda m; the temperature of the heating medium (glycol) Tw at the feed to the ground heat exchanger and its flow rate M; the internal diameter of the pipes of the ground heat exchanger dw; and the distances between the external walls of the pipes of the ground heat exchanger L. The analysis was carried out for the climatic conditions of the Podlasie Voivodeship (Poland). Based on the results of the computational experiment obtained using the TRNSYS numerical environment, a deterministic mathematical model of this relationship was developed, and the effects of the influence of selected factors on the specific thermal efficiency q of the vertical ground heat exchanger, received by the U-shaped element, were analysed. Based on the model, the contribution of each parameter to the efficiency of the heat exchanger was determined. It turned out that changes in the values of the factors Tg (X1), lambda g (X2), lambda m (X3), M (X5), dw (X6) and L (X7) from the lower to the upper level caused an increase in the specific efficiency q of the heat exchanger by 34.04, 7.90, 15.20, 55.42, 6.58 and 24.26%. Only factor Tw (X4), with such a change, caused a decrease in the thermal efficiency of the tested heat exchanger by 44.22%. The parameters of the tested element of the geothermal heating system were also optimized according to the energy criterion using a numerical method in the Matlab environment. The information may be useful for scientists, designers, producers and consumers of heating systems based on heat pumps with a vertical ground heat exchanger as the lower heat source.
引用
收藏
页数:21
相关论文
共 50 条
  • [1] Optimization of ground heat exchanger parameters of ground source heat pump system for space heating applications
    Sivasakthivel, T.
    Murugesan, K.
    Sahoo, P. K.
    ENERGY, 2014, 78 : 573 - 586
  • [2] Control of Heat Transfer in a Vertical Ground Heat Exchanger for a Geothermal Heat Pump System
    Salhein, Khaled
    Kobus, C. J.
    Zohdy, Mohamed
    ENERGIES, 2022, 15 (14)
  • [3] Heat Transfer Performance Factors in a Vertical Ground Heat Exchanger for a Geothermal Heat Pump System
    Salhein, Khaled
    Kobus, C. J.
    Zohdy, Mohamed
    Annekaa, Ahmed M.
    Alhawsawi, Edrees Yahya
    Salheen, Sabriya Alghennai
    ENERGIES, 2024, 17 (19)
  • [4] Impact of Seasonal Heat Accumulation on Operation of Geothermal Heat Pump System with Vertical Ground Heat Exchanger
    Timofeev, D. V.
    Malyavina, E. G.
    INTERNATIONAL CONFERENCE ON CONSTRUCTION, ARCHITECTURE AND TECHNOSPHERE SAFETY (ICCATS 2017), 2017, 262
  • [5] A study on optimization of horizontal ground heat exchanger parameters for space heating application
    Thangavel, Sivasakthivel
    Verma, Vikas
    Tarodiya, Rahul
    Kaliyaperumal, Parameswari
    MATERIALS TODAY-PROCEEDINGS, 2021, 47 : 2293 - 2298
  • [6] Parameters optimization of a vertical ground heat exchanger based on response surface methodology
    Khalajzadeh, Vahid
    Heidarinejad, Ghassem
    Srebric, Jelena
    ENERGY AND BUILDINGS, 2011, 43 (06) : 1288 - 1294
  • [7] Numerical study of geothermal district heating from a ground heat exchanger coupled with a heat pump system
    Zhang, Xiong
    APPLIED THERMAL ENGINEERING, 2021, 185
  • [8] Various criteria in optimization of a geothermal air conditioning system with a horizontal ground heat exchanger
    Sayyaadi, Hoseyn
    Amlashi, Emad Hadaddi
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (03) : 233 - 248
  • [9] Heating system with vapour compressor heat pump and vertical U-tube ground heat exchanger
    Hanuszkiewicz-Drapala, Malgorzata
    Skladzien, Jan
    ARCHIVES OF THERMODYNAMICS, 2010, 31 (04) : 93 - 110
  • [10] The effects of ground heat exchanger parameters changes on geothermal heat pump performance - A review
    Noorollahi, Younes
    Saeidi, Reza
    Mohammadi, Mohammad
    Amiri, Ali
    Hosseinzadeh, Mehdi
    APPLIED THERMAL ENGINEERING, 2018, 129 : 1645 - 1658