Experimental validation of relationship between interrupting capacity of axial magnetic field vacuum interrupters with cup type contacts and their contact diameters and contact gaps

被引:0
|
作者
School of Engineering, Xi'an Jiaotong University, Xi'an 710049, China [1 ]
不详 [2 ]
机构
来源
Gaoya Dianqi | 2006年 / 4卷 / 250-252期
关键词
D O I
暂无
中图分类号
学科分类号
摘要
The relationship between maximum interrupting capacity of AMF vacuum interrupters with cup type contacts and their contact diameters and contact gaps is proposed to be I = k × D2 × Bz0.4, which is experimentally validated in this paper. The contact diameters of the prototype vacuum interrupters are 48, 58 and 66 mm and the contact gaps are 8, 11 and 14 mm separately. 9 vacuum interrupters are tested with oscillation circuit to measure their limit interrupting capacity. Axial magnetic flux density in the 9 cases is analyzed by 3D finite element method. With the calculated axial magnetic flux density results, limit interrupting capacity of the vacuum interrupters is predicted by the equation, which is compared with the experimental results and rated interrupting capacity. Considering experimental errors, the prediction results are meaningful.
引用
收藏
相关论文
共 32 条
  • [31] Investigation on three-dimensional magnetic field between axial magnetic contacts for revolving arc type vacuum circuit breaker
    Cao, YD
    Zhao, LZ
    Wang, EZ
    Liu, XM
    ISDEIV: XXITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2004, 21 : 363 - 366
  • [32] Design Optimization of a 3/4 Coil-Type Axial Magnetic Field Contact for 126 kV Vacuum Interrupter
    Wang, Zihan
    Li, Haomin
    Shi, Dacheng
    Wu, Junhui
    Xue, Congjun
    Wang, Jianhua
    Liu, Zhiyuan
    2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 170 - 174