Investigation on the Vacuum Arc Current Commutation Criteria of the Low Voltage DC Hybrid Circuit Breaker

被引:0
|
作者
Ge G. [1 ]
Cheng X. [1 ]
Wang H. [1 ]
Xie W. [2 ]
Huang J. [3 ]
机构
[1] College of Electrical Engineering, Zhengzhou University, Zhengzhou
[2] State Grid Henan Electric Power Research Institute, Zhengzhou
[3] College of Electrical Engineering, Dalian University of Technology, Dalian
关键词
Commutation criteria; Current commutation characteristic; Low voltage DC hybrid circuit breaker; Vacuum arc;
D O I
10.19595/j.cnki.1000-6753.tces.180751
中图分类号
学科分类号
摘要
The vacuum arc current commutation characteristic plays an important role on breaking process of the low voltage DC hybrid circuit breaker (HCB). In order to gain the current commutation characteristic and the criteria, the structure and principle of the DC HCB is analyzed and the simplified circuit of the current commutation is proposed. The test circuit of the vacuum arc currentcommutation is set up. The vacuum arc development is observed by the high speed CMOS camera and the influence of the main current, commutation circuit parameters and arcing time on the current commutation is investigated. Based on the test results, the vacuum arc current commutation characteristic and criteria is obtained and the modified criteria are conducted. The breaking test of the 400V/5kA DC HCB is conducted, which also verifies the effectiveness of the criteria. The paper provides the reference of the high performance DC HCB. © 2019, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:4038 / 4047
页数:9
相关论文
共 23 条
  • [11] Polman H., Ferreira A., Kaanders M., Et al., Design of a bid-irectional 600V/6kA ZVS hybrid DC switch using IGBTs, IEEE Transaction. on Power Delivery, 16, 2, pp. 1052-1059, (2001)
  • [12] Meyer J., Rufer A., A DC hybrid circuit breaker with ultra-fast contact opening and integrated gate-commutated thyristors (IGCTs), IEEE Transactios, on Power Delivery, 21, 2, pp. 646-651, (2006)
  • [13] Huang J., Liao M., Ge G., Et al., Zero-voltage-switch hybrid DC switch for DC microgrid, HighVoltage Engineering, 41, 9, pp. 3148-3155, (2015)
  • [14] Liu L., Zhuang J., Wang C., Et al., Interruption characteristics of hybrid dc vacuum circuitbreakers with small contact gaps, Proceedings of the CSEE, 34, 33, pp. 5991-5997, (2014)
  • [15] Liu L., Zhuang J., Jiang Z., Et al., Effect of arcing time upon the interruption characteristic of the hybrid DC vacuum circuit breaker, Transactions of China Electrotechnical Society, 30, 24, (2015)
  • [16] Callavik M., Blomberg A., Hafner J., Et al., The hybrid HVDC breaker an innovation breakthrough enabling-reliable HVDC grids, ABB Grid Systems, Technical Paper, (2012)
  • [17] Hafner J., Jacobson B., Proactive Hybrid HVDC breakers-aKey Innovation for Reliable HVDC grids, CIGRE 2011, Bologna Symposium, 264, pp. 0093-9994, (2011)
  • [18] Grieshaber W., Dupraz J.P., Penache D.L., Et al., Development and Test of a 120 kV Direct Current Circuit breaker, pp. 1-10, (2014)
  • [19] Wei X., Gao C., Luo X., A novel design of high-voltage DC circuit breaker in HVDC flexible transmission grid, Automation of Electric Power Systems, 37, 15, pp. 95-102, (2013)
  • [20] Huang J., Liao M., Ge G., Et al., Current transfer characteristics of the hybrid DC circuit breaker in DC micro-grid, High Voltage Apparatus, 53, 3, pp. 119-125, (2017)