Natural pollution accumulation characteristics of overhead transmission line insulator strings of Zhejiang electric power grid

被引:0
|
作者
Wang, Shaohua [1 ]
Hu, Wentang [1 ]
Gong, Jiangang [2 ]
Pan, Jie [2 ]
Xu, Yangyong [3 ]
Liu, Haojun [1 ]
机构
[1] State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China
[2] State Grid Zhejiang Electric Power Company, Hangzhou 310007, China
[3] Maintenance Company, State Grid Zhejiang Electric Power Company, Hangzhou 311232, China
来源
Gaodianya Jishu/High Voltage Engineering | 2014年 / 40卷 / 04期
关键词
Deposition - Electric power transmission - Insulating materials - Pollution - Electric power transmission networks - Insulator contamination - Chemical analysis - Electric power distribution;
D O I
10.13336/j.1003-6520.hve.2014.04.007
中图分类号
学科分类号
摘要
The characteristics of pollution accumulation on naturally polluted insulators are fundamental for drawing pollutant distribution maps for power systems. Hence, taking some insulator strings on Zhejiang overhead transmission lines as samples, we investigated the natural pollution accumulation of insulators. Using statistical methods, we obtained and analyzed the ratio of top pollution level to bottom pollution level in aspects of equivalent salt deposition density (ESDD), non-soluble deposition density (NSDD), and the ratio between the two, which were denoted by KESDD, KNSDD and KNSDD/ESDD, respectively. Besides, we also analyzed the chemical compositions of the contamination under typical pollution resources. The results show that, for insulators of different structures, their top and bottom surfaces have quite different unevenness of pollution accumulation. For a naturally polluted insulator, the average value of ratio of KNSDD/ESDD is 4.66, while on a whole piece of insulator, the distribution of average KNSDD/ESDD varies in a tendency approximately consistent with that of the piece's bottom surface. In the contamination under study, Ca2+ is the main component of cations and SO42- is the main component of anions. For a piece of insulator, the proportion of different ions on its top surface is different from that of its bottom surface. It is recommended that these features of pollution deposit should be adequately considered in outdoor insulation designing and operation maintenance.
引用
收藏
页码:1002 / 1009
相关论文
共 48 条
  • [21] Simulation and analysis of charge accumulation characteristics of post insulator of transmission line for the CRAFT NNBI system
    Wang, RiXin
    Xu, YongJian
    Jiang, CaiChao
    Peng, XuFeng
    Yu, ZiChen
    Xie, YaHong
    Xie, YuanLai
    Hu, ChunDong
    FUSION ENGINEERING AND DESIGN, 2021, 173
  • [22] Studies on metallurgical contamination accumulation characteristics on ceramic insulator of 500 kV AC transmission line
    Lan, Lei
    Mu, Lin
    Yuan, Xiaoqing
    Yan, Jing
    Wang, Yu
    Wang, Wei
    Shen, Yang
    Hao, Lu
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (05) : 722 - 728
  • [23] Development of Inspection Tool for Live-line Insulator Strings in 154kV Power Transmission Lines
    Lee, Jae-Kyung
    Park, Joon-Young
    Cho, Byung-Hak
    Oh, Ki-Yong
    EPE: 2009 13TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS, VOLS 1-9, 2009, : 2110 - 2117
  • [24] Optimization of electric transmission line of power grid with carbon fiber composite core conductor
    Du, Shuai
    Zang, Baozhi
    JOURNAL OF ELECTRICAL SYSTEMS, 2019, 15 (03) : 448 - 458
  • [25] Power grid risk assessment system considering characteristics of transmission line failure
    Wu, Weinan
    Yang, Jun
    Hu, Wenping
    Zeng, Zhili
    Yu, Tengkai
    Liu, Pei
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (06): : 129 - 134
  • [26] Analysis of electric field intensity during live maintenance on 400 kV overhead power transmission line
    Lopatkiewicz, Radoslaw
    Nadolny, Zbigniew
    Rakowska, Aleksandra
    PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11B): : 258 - 261
  • [27] Application technique of lightning rod for lightning shielding failure prevention of overhead electric power transmission line
    State Grid Construction DC Company Limited, Beijing 100005, China
    Gaodianya Jishu/High Voltage Engineering, 2008, 34 (06): : 1301 - 1305
  • [28] CHARACTERISTICS ANALYSIS OF THE INDUCED OVERCURRENT GENERATED BY CLOSE TRIGGERED LIGHTNING ON THE OVERHEAD TRANSMISSION POWER LINE
    杨少杰
    陈绍东
    张义军
    董万胜
    王建国
    周蜜
    王孝波
    余晖
    JournalofTropicalMeteorology, 2010, 16 (01) : 59 - 65
  • [29] CHARACTERISTICS ANALYSIS OF THE INDUCED OVERCURRENT GENERATED BY CLOSE TRIGGERED LIGHTNING ON THE OVERHEAD TRANSMISSION POWER LINE
    Yang Shao-jie
    Chen Shao-dong
    Zhang Yi-jun
    Dong Wan-sheng
    Wang Jian-guo
    Zhou Mi
    Wang Xiao-bo
    Yu Hui
    JOURNAL OF TROPICAL METEOROLOGY, 2010, 16 (01) : 59 - 65
  • [30] Short-circuit Fault Characteristics Analysis for the Overhead Line in MMC-HVDC Power Grid
    Xin, Guangming
    Wang, Peiran
    Wei, Xiaoran
    Xie, Huan
    Zhang, Shuo
    Cao, Tianzhi
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2941 - 2947