Natural pollution accumulation characteristics of overhead transmission line insulator strings of Zhejiang electric power grid

被引:0
|
作者
Wang, Shaohua [1 ]
Hu, Wentang [1 ]
Gong, Jiangang [2 ]
Pan, Jie [2 ]
Xu, Yangyong [3 ]
Liu, Haojun [1 ]
机构
[1] State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China
[2] State Grid Zhejiang Electric Power Company, Hangzhou 310007, China
[3] Maintenance Company, State Grid Zhejiang Electric Power Company, Hangzhou 311232, China
来源
Gaodianya Jishu/High Voltage Engineering | 2014年 / 40卷 / 04期
关键词
Deposition - Electric power transmission - Insulating materials - Pollution - Electric power transmission networks - Insulator contamination - Chemical analysis - Electric power distribution;
D O I
10.13336/j.1003-6520.hve.2014.04.007
中图分类号
学科分类号
摘要
The characteristics of pollution accumulation on naturally polluted insulators are fundamental for drawing pollutant distribution maps for power systems. Hence, taking some insulator strings on Zhejiang overhead transmission lines as samples, we investigated the natural pollution accumulation of insulators. Using statistical methods, we obtained and analyzed the ratio of top pollution level to bottom pollution level in aspects of equivalent salt deposition density (ESDD), non-soluble deposition density (NSDD), and the ratio between the two, which were denoted by KESDD, KNSDD and KNSDD/ESDD, respectively. Besides, we also analyzed the chemical compositions of the contamination under typical pollution resources. The results show that, for insulators of different structures, their top and bottom surfaces have quite different unevenness of pollution accumulation. For a naturally polluted insulator, the average value of ratio of KNSDD/ESDD is 4.66, while on a whole piece of insulator, the distribution of average KNSDD/ESDD varies in a tendency approximately consistent with that of the piece's bottom surface. In the contamination under study, Ca2+ is the main component of cations and SO42- is the main component of anions. For a piece of insulator, the proportion of different ions on its top surface is different from that of its bottom surface. It is recommended that these features of pollution deposit should be adequately considered in outdoor insulation designing and operation maintenance.
引用
收藏
页码:1002 / 1009
相关论文
共 48 条
  • [1] Natural Pollution Accumulation Characteristics of Composite Insulators for Overhead Transmission Lines in Hunan Power Grid
    Chao Y.
    Gao J.
    Yue Y.
    Wang F.
    Wang C.
    Huang F.
    Chao, Yafeng (yfchao5335@163.com), 2018, Science Press (44): : 2799 - 2806
  • [2] Selection of numbers of insulator of pollution insulator strings for DC transmission line
    Wu, Guangya
    Cai, Wei
    Lu, Yanlong
    Xiao, Yong
    Zhao, Quanjiang
    Xue, Chunlin
    Gaodianya Jishu/High Voltage Engineering, 2001, 27 (06):
  • [3] Impulse voltage characteristics for HV transmission line insulator strings
    Enache, R.
    Coatu, S.
    Baran, Ileana
    Nicoara, B.
    Revue roumaine de sciences techniques. Serie electrotechnique et energetique, 1988, 33 (03): : 253 - 266
  • [4] Analysis on Natural Contamination Depositing Characteristics of Imitative Insulator String for Overhead Transmission Line in Shantou
    Lu, Xilong
    Chen, Xin
    Zhang, Dongdong
    Zhang, Zhijin
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 452 - 455
  • [5] Icing flashover characteristics of EHV AC transmission line insulator strings
    Huang, Dao-Chun
    Liu, Yun-Peng
    Hu, Yi
    Cai, Wei
    Chen, Yong
    Ruan, Jiang-Jun
    Yu, Tao
    Yao, Tao
    Xu, Zuo-Ming
    Gao, Song
    Lu, Jie
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (03): : 568 - 573
  • [6] A Novel Fault Monitoring Mechanism on Overhead Transmission Line in Power Grid
    Korde, Neha
    Bhagat, Narendra
    PROCEEDINGS OF 2017 INTERNATIONAL CONFERENCE ON INTELLIGENT COMPUTING AND CONTROL (I2C2), 2017,
  • [7] Influence of pollution and defects on the surface electric field distribution of overhead line HV composite insulator
    Yahoui, Y.
    Castellon, J.
    Agnel, S.
    Pons, C.
    2020 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (2020 IEEE CEIDP), 2020, : 119 - 122
  • [8] Pollution characteristic of insulator strings for 1000 kV with transmission line double circuit on the same tower
    Xu, Tao
    Chen, Yong
    Meng, Gang
    Xie, Liang
    Xie, Xiong-Jie
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (09): : 2071 - 2075
  • [9] Research on Flashover Breakdowns and Prevention Measures of Synthetic Insulator of overhead Power Transmission Line
    Yi Guoqi
    Jia Yang
    Huang Yujun
    Yu Jintao
    PROCEEDINGS OF THE 3RD INTERNATIONAL CONFERENCE ON MECHANICAL ENGINEERING AND INTELLIGENT SYSTEMS (ICMEIS 2015), 2015, 26 : 25 - 28
  • [10] Robust Online Overhead Transmission Line Monitoring With Cost Efficiency in Smart Power Grid
    Shin, Huicheol
    Song, Yujae
    Kong, Peng-Yong
    IEEE ACCESS, 2021, 9 : 86449 - 86459