Experimental performance investigation on a desiccant-assisted two-stage evaporative cooling system in hot and humid areas

被引:3
|
作者
Zhang, Yanling [1 ,2 ]
Chen, Yi [3 ]
Yang, Hongxing [1 ]
Zhang, Hao [2 ]
Leung, Chun Wah [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Renewable Energy Res Grp, Hong Kong, Peoples R China
[2] Hong Kong Polytech Univ, Sch Profess Educ & Execut Dev, Hong Kong, Peoples R China
[3] Jimei Univ, Coll Marine Equipment & Mech Engn, Xiamen, Peoples R China
关键词
Desiccant-enhanced evaporative cooling; Two-stage indirect evaporative cooling; Air conditioning; Performance optimization; Eco-friendly air handling; DEHUMIDIFICATION; CHINA;
D O I
10.1016/j.apenergy.2024.124704
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The escalating demand for energy-efficient and eco-friendly air conditioning systems in buildings has spurred the development of comfortable, efficient, and cost-effective air handling system configurations. Desiccant cooling has shown a higher coefficient of performance (COP) compared to traditional vapor compression refrigeration (MVCR) systems. However, current desiccant cooling facilities struggle to decouple and efficiently handle indoor heat and moisture loads. The complexity of these facilities has kept intricate cooling systems remaining theoretical, requiring simplification and experimental investigation. This paper presents an experimental study on a compact, two-stage evaporative cooling system assisted by a liquid desiccant. A key innovation of this system is the inclusion of a two-stage heat exchanger that adeptly manages the decoupling of indoor heat and moisture loads under challenging high-temperature and high-humidity conditions. Performance analysis was conducted experimentally under three hot and humid climatic conditions using an optimized operating parameter scheme. Starting from an initial condition of 36.22 degrees C and a humidity ratio of 0.028 kg/kg, the proposed system achieves COP values ranging from 11.3 to 18.4 without compromising indoor comfort or facility compactness. Under high heat and high humidity conditions, the optimized system extracts 20 % of the product air as the secondary air source. It can reach a minimum supply air temperature of 18.44 degrees C, achieved under optimized conditions of low wind speed (1.0 m/s), high desiccant concentration (35 %), and substantial desiccant flow (0.09 kg/s). Experimental studies of this new system provide the possibility of achieving high efficiency in air handling over a wide range of temperatures and humidity.
引用
收藏
页数:16
相关论文
共 50 条
  • [41] Performance study of two-stage liquid desiccant dehumidification system
    Xiong, Zhen-Qin
    Dai, Yan-Jun
    Wang, Ru-Zhu
    Shanghai Jiaotong Daxue Xuebao/Journal of Shanghai Jiaotong University, 2009, 43 (05): : 783 - 788
  • [42] Use of regenerative evaporative cooling to improve the performance of a novel one-rotor two-stage solar desiccant dehumidification unit
    La, D.
    Dai, Y. J.
    Li, Y.
    Ge, T. S.
    Wang, R. Z.
    APPLIED THERMAL ENGINEERING, 2012, 42 : 11 - 17
  • [43] Investigation on solar assisted liquid desiccant dehumidifier and evaporative cooling system for fresh air treatment
    Chen, Yi
    Yang, Hongxing
    Luo, Yimo
    ENERGY, 2018, 143 : 114 - 127
  • [44] Performance investigation of solid desiccant evaporative cooling system configurations in different climatic zones
    Ali, Muzaffar
    Vukovic, Vladimir
    Sheikh, Nadeem Ahmed
    Ali, Hafiz M.
    ENERGY CONVERSION AND MANAGEMENT, 2015, 97 : 323 - 339
  • [45] Performance investigation and exergy analysis of two-stage desiccant wheel systems
    Liu, Xiao-Hua
    Zhang, Tao
    Zheng, Yu-Wei
    Tu, Rang
    RENEWABLE ENERGY, 2016, 86 : 877 - 888
  • [46] A Liquid Desiccant Enhanced Two Stage Evaporative Cooling SystemDevelopment and Performance Evaluation of a Test Rig
    Rafique, M. Mujahid
    Rehman, Shafiqur
    Alhems, Luai M.
    Shakir, Muhammad Ali
    ENERGIES, 2018, 11 (01):
  • [47] Experimental investigation on two-stage thermoelectric cooling system adopted in isoelectric focusing
    Hu, H. M.
    Ge, T. S.
    Dai, Y. J.
    Wang, R. Z.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 53 : 1 - 12
  • [48] Performance investigation of a hybrid ground-assisted desiccant cooling system
    Liang, Jyun-De
    Kao, Chia-Lin
    Tsai, Lu-Kuan
    Chiang, Yuan-Ching
    Tsai, Hsieh-Chen
    Chen, Sih-Li
    ENERGY CONVERSION AND MANAGEMENT, 2022, 265
  • [49] Simulated hygrothermal performance of a desiccant-assisted hybrid air/water conditioning system in a mixed humid climate under dynamic load
    O'Kelly, Matthew
    Walter, Mark E.
    Rowland, James R.
    ENERGY AND BUILDINGS, 2015, 86 : 45 - 57
  • [50] AN EXPERIMENTAL INVESTIGATION INTO A SOLAR ASSISTED DESICCANT-EVAPORATIVE AIR-CONDITIONING SYSTEM
    JOUDI, KA
    MADHI, SM
    SOLAR ENERGY, 1987, 39 (02) : 97 - 107