A Short-Circuit Protection System Considering the Negative Sequence of Fault Current Available to Long Distribution Lines

被引:0
|
作者
Hirayama K. [1 ]
Aoki M. [1 ]
Amau T. [2 ]
Otani T. [3 ]
Ozawa T. [4 ]
Tsushima K. [4 ]
机构
[1] Nagoya Institute of Technology, Gokiso-cho, Showa-ku, Nagoya
[2] Chubu Electric Power Grid Co. Inc., 1, Higashi-shincho, Higashi-ku, Nagoya
[3] Central Research Institute of Electric Power Industry, 2-6-1, Nagasaka, Yokosuka
[4] Meiryo Denshi, 38-23, Higashimaeda, Asada-cho, Nisshin
关键词
long distribution line; negative-sequence current; short-circuit protection; two-phase short-circuit fault;
D O I
10.1541/ieejpes.143.389
中图分类号
学科分类号
摘要
A fault current measured at a distribution substation is small in case of a two-phase short-circuit fault near the end of a long distribution line. This characteristic makes it difficult to settle the overcurrent relay installed at the root of line because the load current could hardly be distinguished from the fault current. On the other hand, a negative-sequence current relay likely isolates such a two-phase short-circuit fault, but it may not operate properly due to effects of load on the distribution line. This study sets a proposal of short-circuit protection system considering the negative sequence of fault current that can be applied to long distribution lines. It also demonstrates how useful the proposed system is for isolating such a two-phase short-circuit fault on a long distribution line. © 2023 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:389 / 395
页数:6
相关论文
共 50 条
  • [1] Short-Circuit Current Calculation of Flexible Direct Current Transmission Lines Considering Line Distribution Parameters
    Wang, Zhuoya
    Hao, Liangliang
    Wang, Zemin
    ENERGIES, 2024, 17 (15)
  • [2] Problem of short-circuit current protection in distribution and transmission substations
    Skare, Javor
    Lovei, Attila
    1600, Hrvatske Elektroprivrede, Zagreb, Croatia (49):
  • [3] Distribution Fault Location using Short-circuit Fault Current Profile Approach
    Das, S.
    Kulkarni, S.
    Karnik, N.
    Santoso, S.
    2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [4] Unsymmetrical short-circuit analysis for distribution system considering loads
    Mathur, Akhilesh
    Pant, Vinay
    Das, Biswarup
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 70 : 27 - 38
  • [5] Research of Active Short-circuit Protection of DC Distribution System
    Chen, Wenbo
    Zhu, Xuezhong
    Li, Wang
    Zou, Xueyi
    2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [6] SHORT-CIRCUIT PROTECTION FOR NEGATIVE VOLTAGE SENSOR
    PRASAD, SJ
    ELECTRONIC ENGINEERING, 1977, 49 (590): : 30 - 30
  • [7] A New Fault Location Scheme Based on Distributed Short-circuit, Current in Distribution System with DGs
    Ma, Jinjie
    Lu, Yuping
    Du, Jiao
    Lin, Xia
    2008 IEEE INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY TECHNOLOGIES (ICSET), VOLS 1 AND 2, 2008, : 1189 - 1194
  • [8] Optimal placement of resistive superconducting fault current limiter by considering short-circuit current and transient stability of power system
    Hafidz, Isa
    Mahendra, Rafin Aqsa Izza
    Pujiantara, Margo
    Priyadi, Ardyono
    Purnomo, Mauridhi Hery
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (19) : 4304 - 4315
  • [9] Relay protection setting calculation of wind farm collector lines considering wind turbine increased short-circuit current
    Gong Y.
    Tao Y.
    Xu C.
    Luo Z.
    Xu Y.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2020, 48 (11): : 128 - 135
  • [10] Novel Protection System for Electrical Systems with Limited Short-Circuit Current
    Grumm, Florian
    Schumann, Marc
    Meyer, Marc Florian
    Luecken, Arno
    Schulz, Detlef
    2018 2ND EUROPEAN CONFERENCE ON ELECTRICAL ENGINEERING AND COMPUTER SCIENCE (EECS 2018), 2018, : 27 - 32