Experimental analysis of artificial contamination flashover characteristics of long insulator strings on 500 kV transmission lines

被引:0
|
作者
机构
[1] Zhang, Xiuli
[2] Zhang, Qin
[3] 2,Yuan, Tian
[4] Hu, Jianxun
来源
Zhang, X. | 1600年 / Science Press卷 / 39期
关键词
Flashover - Insulator contamination - Salt deposits - Electric lines;
D O I
10.3969/j.issn.1003-6520.2013.12.032
中图分类号
学科分类号
摘要
We experimentally measured the artificial contamination flashover characteristics of 500 kV long insulator strings, since reckoning the flashover voltage of long insulator strings based on data of short insulator strings would result in large deviations. Taking XWP2-160 type two umbrella porcelain insulators as samples, we obtained the artificial contamination flashover voltages of hang single-string insulators under different equivalent salt deposit density (ESDD), different non-soluble deposit density (NSDD), and uneven deposition filthy through experiments. Moreover, we calculated the effective coefficient of creepage distance for this type of insulator string according to the experimental results, and compared the results from tests using string insulators of V type, inverted-V type and single hang type to get the correction coefficient for abnormal types of insulator strings. Experimental results reveal that, the flashover voltage of XWP2-160 insulator string is negatively correlated to ESDD and NSDD; the effective coefficient of creepage distance for the single hang type is 0.78; the flashover voltage of a single insulator from a V type or inverted-V type string is slightly higher than that from the single hang type strings; the string-structure correction coefficients of V type and inverted-V type are 1.08 and 1.15, respectively. The results can be referred by the anti-contamination works for operation of the long insulator strings on 500 kV transmission lines.
引用
收藏
相关论文
共 50 条
  • [1] Experimental analysis of the artificial contamination flashover characteristics of long insulator strings in 500 kV transmission lines
    Zhu, Yong-Kun
    Sun, Guang
    Gao, Shu-Yong
    Shi, Wen-Jiang
    Xu, Da-Peng
    Yu, Ming-Xing
    Jiang, Xian-Feng
    PROCEEDINGS OF THE 2ND ANNUAL INTERNATIONAL CONFERENCE ON ELECTRONICS, ELECTRICAL ENGINEERING AND INFORMATION SCIENCE (EEEIS 2016), 2016, 117 : 65 - 75
  • [2] Wet Snow Flashover Characteristics of the Insulator Strings in " Λ " Shape on 500 kV Transmission Lines
    Xu, Jingwei
    Li, Longji
    Jia, Zhidong
    Liu, Shunnan
    Wen, Qingfeng
    Xi, Xiaoguang
    Liu, Jiping
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 1131 - 1134
  • [3] Icing Flashover Characteristics and Discharge Process of 500 kV AC Transmission Line Suspension Insulator Strings
    Liu, Yunpeng
    Gao, Song
    Huang, Daochun
    Yao, Tao
    Wu, Xiong
    Hu, Yi
    Cai, Wei
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 434 - 442
  • [4] Wet Snow Flashover Characteristics of 500-kV AC Insulator Strings with Different Arrangements
    Xu, Jingwei
    Yin, Fanghui
    Li, Longji
    Wen, Qingfeng
    Wang, Hao
    Liu, Shunnan
    Jia, Zhidong
    Farzaneh, Masoud
    APPLIED SCIENCES-BASEL, 2019, 9 (05):
  • [5] Analysis on Air-gaps Discharge and Pollution Flashover Characteristics of Y-type Insulator Strings for ±1 100 kV Transmission Lines
    Liu Q.
    Huo F.
    Zhou K.
    Li J.
    Ye Q.
    Li Y.
    Liu, Qin (liuqin2@epri.sgcc.com.cn), 1600, Science Press (43): : 3182 - 3188
  • [7] Icing flashover characteristics of EHV AC transmission line insulator strings
    Huang, Dao-Chun
    Liu, Yun-Peng
    Hu, Yi
    Cai, Wei
    Chen, Yong
    Ruan, Jiang-Jun
    Yu, Tao
    Yao, Tao
    Xu, Zuo-Ming
    Gao, Song
    Lu, Jie
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (03): : 568 - 573
  • [8] Field measurement and analysis of voltage distribution on 500 kV transmission line insulator strings
    Ding, Yizheng
    Zhang, Junlan
    Chen, Xiongyi
    Luo, Zhenhai
    Zhongguo Dianli/Electric Power, 2000, 33 (02): : 45 - 47
  • [9] Artificial rime covering and discharge tests of 500 kV insulator strings
    Su, Fuheng
    Jia, Yimei
    Wang, Juntang
    Li, Gang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 1999, 19 (02): : 75 - 78