摘要
The single-unit multiplication method is commonly used for fault steady-state modeling of inverter-interfaced generator stations to simply estimate the short-circuit current level. But its calculation accuracy needs to be improved. First, the decisive effect of active power output and voltage dips on the steady-state current output of the power generation unit under the constraints of the low voltage ride-through control strategy is analyzed in this paper. Then, the output characteristic curve of the fault steady-state current is derived. Based on this, the effects of the differences in electrical distance and active power output of the station on the calculation error of single-unit multiplication method are analyzed. On the basis of error analysis, an improved single-unit multiplication method considering the distribution characteristics of power generation units is proposed. The method uses the equivalent impedance to equate the electrical distance between the power generation unit and point of common coupling in the calculation of the voltage at the access point of the power generation unit. The station grouping is equated into two units for reducing the impact of the difference in active power output between the power generation units on the short-circuit characteristics. Simulation analysis in different scenarios shows that the improved method has a large improvement in the calculation accuracy compared with single-unit multiplication method. The method proposed has good engineering practicality as it can achieve station grouping and short-circuit current aggregation with simple calculations. © 2024 Automation of Electric Power Systems Press. All rights reserved.
引用
收藏
页码:182 / 191
页数:9
相关论文
共 24 条
  • [11] JIAO Yanjun, LIANG Xiao, JIANG Chenyang, Failure analysis method in distribution network considering LVRT control strategy of grid-connected photovoltaic station [J], Automation of Electric Power Systems, 40, 20, pp. 92-99, (2016)
  • [12] WANG Chenqing, SONG Guobing, CHI Yongning, Et al., Fault characteristics analysis of wind power system [J], Automation of Electric Power Systems, 39, 21, pp. 52-58, (2015)
  • [13] Bin LI, ZHOU Bohao, HE Jiawei, Et al., Applicability analysis of distance protection with positive-sequence voltage polarization for transmission lines of wind farm with direct-driven turbines[J], Automation of Electric Power Systems, 47, 22, pp. 16-24, (2023)
  • [14] YE Lin, SHI Yuanyuan, WANG Qiheng, Et al., Multi-step grouping and equivalent modeling of distributed photovoltaic clusters for transient analysis[J], Automation of Electric Power Systems, 47, 14, pp. 72-81, (2023)
  • [15] ZHOU Y H,, ZHAO L, HSIEH T Y,, Et al., A multistage dynamic equivalent modeling of a wind farm for the smart grid development[J], IEEE Transactions on Industry Applications, 55, 5, pp. 4451-4461, (2019)
  • [16] WANG Zengping, YANG Guosheng, TANG Yong, Et al., Modeling method of direct-driven wind generators wind farm based on feature influence factors and improved BP algorithm [J], Proceedings of the CSEE, 39, 9, pp. 2604-2615, (2019)
  • [17] WANG Lei, GAI Chunyang, WANG Heng, Dynamic equivalence method of PMSG wind farms based on improved DK clustering algorithm[J], Acta Energiae Solaris Sinica, 42, 3, pp. 48-55, (2021)
  • [18] QI Jinling, LI Weixing, CHAO Pupu, Et al., Practical equivalent method for direct-driven wind farm[J], Electric Power Automation Equipment, 42, 12, pp. 50-57, (2022)
  • [19] HAN Wei, LIU Sumei, XIAO Chao, Et al., Steady short-circuit calculation model for a photovoltaic station considering different generation units’ fault characteristics [J], Power System Protection and Control, 49, 20, pp. 129-135, (2021)
  • [20] JIA Ke, KONG Fanzhe, ZHANG Yang, Et al., Fault equivalent modeling method of doubly fed wind farm based on improved K-means algorithm[J], Power System Technology, 47, 10, pp. 4161-4169, (2023)