Selectivity Enhancement Scheme for Zero-sequence Current Protection Based on Distance Relay for High-resistance Grounding Fault

被引:0
|
作者
Li, Yong [1 ,2 ]
Li, Yinhong [3 ,4 ]
Liu, Huanzhang [1 ,2 ]
Liu, Yang [1 ,2 ]
机构
[1] Central China Branch of State Grid Corporation of China, Wuhan,430077, China
[2] Lamor Innovation Studio of Liu Huanzhang, Wuhan,430077, China
[3] School of Electrical and Electronic Engineering, Huazhong University of Science and Technology, Wuhan,430074, China
[4] State Key Laboratory of Advanced Electromagnetic Technology, Huazhong University of Science and Technology, Wuhan,430074, China
关键词
Electric equipment protection - Electric grounding - Electric power system protection - Short circuit currents - Site selection;
D O I
10.7500/AEPS20240228008
中图分类号
学科分类号
摘要
The last section of zero-sequence current protection of AC line adopts 300 A, which has the risk of disordered tripping. Therefore, a new principle of high-resistance grounding distance relay based on zero-sequence reactance line and non-fault phase polarization is proposed. The relay adopts the technical route of phase selection before measurement. The phase selection element combines zero-sequence reactance line and non-fault phase polarization method to form a variety of combined criteria to complete the phase selection. Due to the phase difference between the zero-sequence current at the protection installation site and the zero-sequence current at the fault point, the zero-sequence reactance lines of the single-phase grounding fault phase and the leading phase of the inter-phase grounding fault have aliasing region when the fault point is near the setting point. The large variation of the operation voltage of the non-fault phase is not conducive to distinguishing the two types of faults in the aliasing region, and thus the phase selection element is divided into low-resistance module and high-resistance module. The low-resistance module adopts the zero-sequence reactance line with the downward bias, which is used to identify the near-end and low-resistance short circuit. With the assistance of the low-resistance module, the high-resistance module only needs to deal with the faults near the setting point, which reduces the difficulty in distinguishing the two types of faults. After phase selection, the operation voltage before fault is obtained by non-fault phase polarization method, so as to determine the operation characteristics of the relay. The ability of high-resistance distance relay to withstand the transition resistance is far beyond the requirements of the regulations, which improves the selectivity of grounding backup protection to high-resistance faults. © 2024 Automation of Electric Power Systems Press. All rights reserved.
引用
收藏
页码:169 / 179
相关论文
共 50 条
  • [1] Influence of Error of Zero-sequence Current Transformer on Small-current High-resistance Grounding Protection and Type Selection
    Wang P.
    Xu B.
    Chen H.
    Wang W.
    Liang D.
    Sun Z.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2023, 47 (12): : 154 - 162
  • [2] High-resistance Grounding Protection for Flexible Grounded Systems Based on Low-frequency Transient Zero-sequence Current Distortion Rate
    Li X.
    Zhang S.
    Peng C.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2024, 48 (13): : 171 - 183
  • [3] Effect of Load on Zero-Sequence Current in Low Resistance Grounding System with Complex Grounding Fault
    Yu Lei
    Tian Bing
    Lei Jinyong
    Han Bowen
    Wang Gang
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [4] Fault analysis of multi-feeder grounding fault and self-adaptive zero-sequence current protection scheme for low-resistance grounding distribution network
    Zeng D.
    Wang G.
    Li H.
    Liu Y.
    Guo J.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2019, 39 (05): : 45 - 52
  • [5] High Sensitive Zero-sequence Stage Current Protection for Low-resistance Grounding System
    Xue Y.
    Wang Y.
    Xu B.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (19): : 6217 - 6226
  • [6] A Novel Adaptive Zero-sequence Current Protection for Low Resistance Grounding System
    Guo, Xiaobin
    Lei, Jinyong
    Han, Bowen
    Wang, Gang
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 2523 - 2528
  • [7] Zero-sequence Inverse-time Overcurrent Protection in Low Resistance Grounding System with Grounding Fault
    Wang Y.
    Xue Y.
    Xu B.
    Li T.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2018, 42 (20): : 150 - 157
  • [8] High Impedance Grounding Fault Detection in Resonance Grounding System Based on Nonlinear Distortion of Zero-sequence Current
    Zhu, Jiran
    Haiguo, Tang
    Leng, Hua
    Sun, Jiao
    Huang, Chun
    2020 5TH INTERNATIONAL CONFERENCE ON SMART GRID AND ELECTRICAL AUTOMATION (ICSGEA 2020), 2020, : 74 - 78
  • [9] Grounding fault location method based on waveform similarity of zero-sequence current
    You X.
    Ge X.
    Wu P.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2019, 47 (14): : 125 - 130
  • [10] Grounding fault protection scheme based on zero-sequence off-nominal frequency component injection for microgrid
    Zhao H.
    Mu L.
    Fang C.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2022, 42 (11): : 25 - 31