Study on Integrated Aging Characteristics of DC MOV in ±1100kV Converter Station

被引:0
|
作者
Fu Y. [1 ]
Yue B. [2 ]
Yu F. [3 ]
Wei Q. [3 ]
Guo J. [3 ]
机构
[1] Department of UHV Construction, State Grid Corporation of China, Xicheng District, Beijing
[2] State Grid Economic and Technological Research Institute Co., Ltd., Changping District, Beijing
[3] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, Shaanxi Province
来源
Yu, Fang (megpet@stu.xjtu.edu.cn) | 1600年 / Power System Technology Press卷 / 44期
关键词
DC MOV; High current impulse; Integrated aging; Lightning impulse; Switching impulse; UHVDC;
D O I
10.13335/j.1000-3673.pst.2019.1945
中图分类号
学科分类号
摘要
In UHVDC converter station, the operating voltage, overvoltage load and waveform on each device vary widely. MOVsat different nodes face different aging threats. Studying on the aging characteristics of DC MOV under various loads is of great significance for parameter selection of DC MOV. In order to analyze the effects of operating overvoltage, near-field lightning strike and far-field lightning overvoltage on DC MOV aging, three kinds of typical DC MOVs in ±1100kV converter stations are applied with multiple combined shock loads of square waves, large currents or lightning waves, and then DC accelerated aging test is carried out. Integrated agingtest results show that the influence weight ranking of impact current on MOV performance degradation is: high current > square waves >lightning waves. Formulation process has great influence on MOV degradation, andobvious polarity effect exists in MOV deterioration. © 2020, Power System Technology Press. All right reserved.
引用
收藏
页码:3149 / 3155
页数:6
相关论文
共 20 条
  • [1] LiuZehong, Yu Jun, GuoXianshan, Et al., Study on main connection line and main circuit parameters of ±1100kV UHVDC, Power System Technology, 42, 4, pp. 1015-1022, (2018)
  • [2] LiuZehong, GuoXianshan, YueBo, Et al., System design of ±1100kV/12000MW UHVDC transmission project, Power System Technology, 42, 4, pp. 1023-1031, (2018)
  • [3] Zhang Jin, ZhaoLuxing, Xie Li, Et al., Study on type selection of tubular busbars and compound electric field, Power System Technology, 42, 2, pp. 373-379, (2018)
  • [4] DingYujian, LuFangcheng, LiPeng, Et al., Discharge characteristics of ±1100 kV UHVDC tower air gaps, Power System Technology, 42, 4, pp. 1032-1038, (2018)
  • [5] XuShiyun, He Jingbo, Fan Mingjian, Et al., Stability and control of receiving-end power system after hierarchical connection of ±1100kV UHVDC, Power System Technology, 43, 5, pp. 1683-1689, (2019)
  • [6] Yang Na, Chen Yu, PanZhuohong, Et al., Influence prediction and suppression research of DC bias in eastern junggar-southernAnhui ±1100kV UHVDC receiving-end grid, Power System Technology, 42, 2, pp. 380-386, (2018)
  • [7] Zhou Peihong, He Huiwen, Dai Min, Et al., Selection of arresters arrangement, parameters and apparatuses insulation levels for ±1100 kV DC Converter Station, High Voltage Engineering, 36, 9, pp. 2871-2884, (2014)
  • [8] (2017)
  • [9] (2006)
  • [10] Zhang Cheng, Yang Zhongjiang, Research on the polarity effect of MOV under direct current, Electronic Components and Materials, 31, 9, pp. 19-22, (2012)